Cat. No. I521-E1-04  
INSTALLATION MANUAL  
SYSDRIVE 3G3EV-Ajjjj-CUE  
(Standard/Multi-function Model)  
(EC Directives Models)  
Thank you for purchasing the compact, low-noise, and easy-to-use SYSDRIVE 3G3EV-series  
Inverter (UL/CUL and EC Directives Models). This installation manual describes installation and  
wiring methods for the SYSDRIVE 3G3EV-Ajjj(M)-CUE (UL/CUL and EC Directives Models).  
Read this manual thoroughly along with the User’s Manual of the Inverter (Standard Model (I011)  
or Multi-function Model (I013)) and handle and operate the product with care.  
1. To ensure safe and proper use of the OMRON Inverters, please read this INSTALLA-  
TION MANUAL (Cat. No. I521-E1) to gain sufficient knowledge of the devices, safety  
information, and precautions before actual use.  
2. The products are illustrated without covers and shieldings for closer look in this INSTALLATION  
MANUAL. For actual use of the products, make sure to use the covers and shieldings as speci-  
fied.  
3. This INSTALLATION MANUAL and other related user’s manuals are to be delivered to the actual  
end users of the products.  
4. Please keep this manual close at hand for future reference.  
5. If the product has been left unused for a long time, please inquire at our sales representative.  
NOTICE  
1. This manual describes the functions of the product and relations with other products. You  
should assume that anything not described in this manual is not possible.  
2. Although care has been given in documenting the product, please contact your OMRON rep-  
resentative if you have any suggestions on improving this manual.  
3. The product contains potentially dangerous parts under the cover. Do not attempt to open the  
cover under any circumstances. Doing so may result in injury or death and may damage the  
product. Never attempt to repair or disassemble the product.  
4. We recommend that you add the following precautions to any instruction manuals you pre-  
pare for the system into which the product is being installed.  
S Precautions on the dangers of high-voltage equipment.  
S Precautions on touching the terminals of the product even after power has been turned off.  
(These terminals are live even with the power turned off.)  
5. Specifications and functions may be changed without notice in order to improve product per-  
formance.  
Items to Check Before Unpacking  
Check the following items before removing the product from the package:  
S Has the correct product been delivered (i.e., the correct model number and specifications)?  
S Has the product been damaged in shipping?  
S Are any screws or bolts loose?  
Notice:  
OMRON products are manufactured for use according to proper procedures by a qualified  
operator and only for the purposes described in this manual.  
The following conventions are used to indicate and classify precautions in this manual. Al-  
ways heed the information provided with them. Failure to heed precautions can result in inju-  
ry to people or damage to property.  
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death  
!
or serious injury. Additionally, there may be severe property damage.  
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death  
!
!
or serious injury. Additionally, there may be severe property damage.  
Caution  
Indicates a potentially hazardous situation which, if not avoided, may result in minor  
or moderate injury, or property damage.  
OMRON Product References  
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when  
it refers to an OMRON product, regardless of whether or not it appears in the proper name  
of the product.  
The abbreviation “Ch,” which appears in some displays and on some OMRON products, of-  
ten means “word” and is abbreviated “Wd” in documentation in this sense.  
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation  
for anything else.  
Visual Aids  
The following headings appear in the left column of the manual to help you locate different  
types of information.  
Note Indicates information of particular interest for efficient and convenient operation of the product.  
OMRON, 1997  
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,  
in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior  
written permission of OMRON.  
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because  
OMRON is constantly striving to improve its high-quality products, the information contained in this manual  
is subject to change without notice. Every precaution has been taken in the preparation of this manual. Never-  
theless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for dam-  
ages resulting from the use of the information contained in this publication.  
Warning Label  
A warning label is attached to the product as shown in the following illustration. Be sure to  
observe the precautionary items specified on the label.  
Warning label  
Contents of Warning Label  
Read and Understand this Manual  
Please read and understand this manual before using the product. Please consult your OMRON  
representative if you have any questions or comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for  
a period of one year (or other period if specified) from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING  
NON–INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE  
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR  
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL  
DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE  
PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR  
STRICT LIABILITY.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on  
which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS  
REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS  
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO  
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to  
the combination of products in the customer’s application or use of the products.  
At the customer’s request, OMRON will provide applicable third party certification documents identifying  
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a  
complete determination of the suitability of the products in combination with the end product, machine,  
system, or other application or use.  
The following are some examples of applications for which particular attention must be given. This is not  
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the  
uses listed may be suitable for the products:  
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions  
or uses not described in this manual.  
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical  
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate  
industry or government regulations.  
Systems, machines, and equipment that could present a risk to life or property.  
Please know and observe all prohibitions of use applicable to the products.  
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR  
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO  
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.  
PROGRAMMABLE PRODUCTS  
OMRON shall not be responsible for the user’s programming of a programmable product, or any  
consequence thereof.  
Disclaimers  
CHANGE IN SPECIFICATIONS  
Product specifications and accessories may be changed at any time based on improvements and other  
reasons.  
It is our practice to change model numbers when published ratings or features are changed, or when  
significant construction changes are made. However, some specifications of the products may be  
changed without any notice. When in doubt, special model numbers may be assigned to fix or establish  
key specifications for your application on your request. Please consult with your OMRON representative  
at any time to confirm actual specifications of purchased products.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when  
tolerances are shown.  
PERFORMANCE DATA  
Performance data given in this manual is provided as a guide for the user in determining suitability and  
does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users  
must correlate it to actual application requirements. Actual performance is subject to the OMRON  
Warranty and Limitations of Liability.  
ERRORS AND OMISSIONS  
The information in this manual has been carefully checked and is believed to be accurate; however, no  
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.  
Table of Contents  
Chapter 1. Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1  
1-1 Items to be Checked when Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2  
1-2 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3  
Chapter 2. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1  
2-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2  
2-2 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4  
Chapter 3. Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1  
3-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
3-1-1 Outside/Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2  
3-1-2 Installation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4  
3-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6  
3-2-1 Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7  
3-2-2 Wiring Around the Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11  
3-2-3 Wiring Control Circuit Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19  
Chapter 4. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1  
4-1 Specifications of Main Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2  
4-2 Specifications of Noise Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6  
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
I-1  
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R-1  
1
Chapter 1  
Getting Started  
1-1 Items to be Checked when Unpacking  
1-2 Precautions  
Getting Started  
Chapter 1  
1-1 Items to be Checked when Unpacking  
H Checking the Product  
On delivery, always check that the delivered product is the SYSDRIVE 3G3EV Inverter that you order-  
ed.  
Should you find any problems with the product, immediately contact your nearest local sales represen-  
tative.  
D Checking the Nameplate  
Inverter model  
Input specifications  
Output specifications  
D Checking the Model  
3G3EV-A4002M-CUE  
Special Specification  
Specification  
Maximum applicable motor capacity  
Voltage class  
Installation type/Option  
Series name: 3G3EV Series  
Specifications  
Voltage Class  
Blank Standard model  
2
B
4
Three-phase 200-VAC input  
M
Multi-function model  
Single/Three-phase 200-VAC input  
Three-phase 400-VAC input  
Maximum Applicable Motor Capacity  
001  
002  
004  
007  
015  
0.1 kW  
Installation Type/Option  
0.2 (0.37) kW  
0.4 (0.55) kW  
0.75 (1.1) kW  
1.5 kW  
A
P
Panel mounting  
Option  
Special Specification  
Note The figures in parentheses indicate  
-CUE UL/CUL and EC Directives Models  
capacities for 400-VAC class models.  
D Checking for Damage  
Check the overall appearance and check for damage or scratches resulting from transportation.  
H Checking Accessories  
Note that this manual and the User’s Manual are the accessories provided with the 3G3EV (Multi-func-  
tion Model). Set screws and other necessary parts must be prepared by customers.  
1-2  
Getting Started  
Chapter 1  
1-2 Precautions  
To ensure safe operation of the 3G3EV, note the following items:  
H Always Hold the Heat Sink During Removal  
When moving the 3G3EV, always hold the heat sink (aluminum portion on the rear of the Unit).  
Heat sink  
H Watch Out for Residual Voltage On Charged Portions  
After the power is turned off, residual voltage remains in the capacitor inside the Inverter. Therefore,  
touching terminals immediately after turning the power off may cause an electrical shock.  
If an inspection or some other task is to be performed, always wait at least one minute from the time all  
indicators on the front panel go off.  
(Note that this warning is applicable whenever you perform any task after turning the main circuit off.)  
H Do Not Remove the Digital Operator When the Main Circuit is Still On.  
Always turn the main circuit off before removing the Digital Operator.  
Removing the Digital Operator with the main circuit ON may cause an electrical shock and damage the  
equipment.  
H Do Not Modify Wiring or Check Signals When the Main Circuit is ON  
Always turn the main circuit off before modifying wiring or checking signals.  
Touching terminals while the main circuit is on may cause an electrical shock and damage the equip-  
ment.  
H Do Not Conduct a Dielectric Strength Test  
Because the 3G3EV Inverter is an electronic control unit using semiconductor, never conduct a dielec-  
tric strength test or an insulation resistance test for the control circuit.  
H Modify Constant Settings Correctly  
Always modify the constant settings according to the procedures described in this manual and the  
User’s Manual.  
1-3  
2
Chapter 2  
Overview  
2-1 Features  
2-2 Nomenclature  
Overview  
Chapter 2  
2-1 Features  
H 3G3EV-series Models (EC Directives Models)  
Standard and multi-function 3G3EV-series Inverters of EC Directives Models are available.  
The maximum applicable motor capacities for the 200-VAC class are 0.1 to 1.5 kW (5 models) and 0.2 to  
1.5 kW (4 models) for the 400-VAC class.  
Type  
Voltage class  
Enclosure  
rating  
Max. applicable motor  
capacity  
Model  
Standard  
200-VAC input  
(three-phase)  
Enclosed panel  
mounted  
0.1 kW  
3G3EV-A2001-CUE  
3G3EV-A2002-CUE  
3G3EV-A2004-CUE  
3G3EV-A2007-CUE  
3G3EV-A2015-CUE  
3G3EV-AB001-CUE  
3G3EV-AB002-CUE  
3G3EV-AB004-CUE  
3G3EV-AB007-CUE  
3G3EV-AB015-CUE  
3G3EV-A4002-CUE  
3G3EV-A4004-CUE  
3G3EV-A4007-CUE  
3G3EV-A4015-CUE  
3G3EV-A2001M-CUE  
3G3EV-A2002M-CUE  
3G3EV-A2004M-CUE  
3G3EV-A2007M-CUE  
3G3EV-A2015M-CUE  
3G3EV-AB001M-CUE  
3G3EV-AB002M-CUE  
3G3EV-AB004M-CUE  
3G3EV-AB007M-CUE  
3G3EV-AB015M-CUE  
3G3EV-A4002M-CUE  
3G3EV-A4004M-CUE  
3G3EV-A4007M-CUE  
3G3EV-A4015M-CUE  
0.2 kW  
0.4 kW  
0.75 kW  
1.5 kW  
200-VAC input  
(single/three-  
phase)  
Enclosed panel  
mounted  
0.1 kW  
0.2 kW  
0.4 kW  
0.75 kW  
1.5 kW  
400-VAC input  
(three-phase)  
Enclosed panel  
mounted  
0.2 (0.37) kW  
0.4 (0.55) kW  
0.75 (1.1) kW  
1.5 kW  
Multi-function 200-VAC input  
(three-phase)  
Enclosed panel  
mounted  
0.1 kW  
0.2 kW  
0.4 kW  
0.75 kW  
1.5 kW  
200-VAC input  
(single/three-  
phase)  
Enclosed panel  
mounted  
0.1 kW  
0.2 kW  
0.4 kW  
0.75 kW  
1.5 kW  
400-VAC input  
(three-phase)  
Enclosed panel  
mounted  
0.2 (0.37) kW  
0.4 (0.55) kW  
0.75 (1.1) kW  
1.5 kW  
Note Model numbers with a suffix of “-CUE” indicate models approved by UL. (Approval has not been  
obtained for models with a model number suffix of “-CE.”)  
2-2  
Overview  
Chapter 2  
H LVD and EMC Directives  
The SYSDRIVE EC Directives Models conform to the LVD (prEN50178) and the EMC (EN50081-2,  
EN50082-2) Directives.  
However, when the product is built into a unit, the connected switches, optional items, or motors may not  
satisfy these Directives. In such a case, either use components that meet the Directives or take ap-  
propriate countermeasures such as providing surge killers or other noise prevention devices.  
H Required Conditions  
There are several conditions that must be satisfied for this Inverter to conform to the LVD and EMC  
Directives. To satisfy the Directives, meet the instructions in this manual for the following installation  
conditions.  
Installation of noise filters and clamp core.  
Shield braided cables must be used for input and output cables.  
Limitations on the lengths of cables.  
Installation of recommended fuses on the input side.  
H Other Functions  
This manual describes installation and wiring methods for conforming to the LVD and EMC Directives.  
Refer to the User’s Manual for detailed information on the functions of the Inverter.  
3G3EV-series Standard Model:  
SYSDRIVE 3G3EV Compact Low-noise Inverter (I011-E1)  
3G3EV-series Multi-function Model:  
SYSDRIVE 3G3EV Compact Low-noise Inverter (I013-E1)  
2-3  
Overview  
Chapter 2  
2-2 Nomenclature  
H Main Unit  
Main Circuit Terminals (Input)  
Power input  
terminals  
Braking resistor  
connection terminals  
L1 N/L2 L3 B1 B2  
Digital Operator  
Run indicator  
Alarm indicator  
Control circuit terminals  
(input/output)  
Control circuit terminals (output)  
S2 S3 SC AM AC PA PC  
MA MB MC  
SF SR S1 SC FS FR FC  
U
V
W
Ground terminal  
Motor output  
terminals  
Main Circuit Terminals (Output)  
Note This diagram shows the Inverter with all terminal block covers removed.  
The standard Inverters are not provided with the upper terminal block (S2 to PC).  
2-4  
Overview  
Chapter 2  
H Digital Operator  
Data display section  
Monitor item indicators  
In-service item indicators (green indicators)  
These items can be monitored or set even  
during operation.  
Display  
section  
Stopped item indicators (red indicators)  
These items can be set only when the  
Inverter is stopped.  
Operation keys  
Mode Key  
Constant item indicators  
Enter Key  
Increment Key  
RUN Key  
Decrement Key  
STOP/RESET Key  
2-5  
3
Chapter 3  
Design  
3-1 Installation  
3-2 Wiring  
Design  
Chapter 3  
3-1 Installation  
3-1-1 Outside/Mounting Dimensions  
Note All dimensions are in millimeters.  
H 3G3EV-A2001(M)-CUE to 3G3EV-A2004(M)-CUE (0.1 to 0.4 kW):  
Three-phase 200-VAC Input  
H 3G3EV-AB001(M)-CUE to 3G3EV-AB002(M)-CUE (0.1 to 0.2 kW):  
Single/Three-phase 200-VAC Input  
4.5 dia.  
Note 1. For the 3G3EV-A2001(M)-CUE, 3G3EV-A2002(M)-CUE, and 3G3EV-AB001(M)-CUE, a U-  
shaped notch (4.5 mm wide) is provided instead of the upper mounting hole (4.5 mm in diame-  
ter).  
Note 2. Install the Inverter with two M4 bolts.  
D Three-phase 200-VAC Input Model  
3G3EV model  
Output  
W
H
D
W1  
H1  
118  
T
Weight  
(kg)  
Approx.  
0.5  
Approx.  
0.6  
Approx.  
0.9  
68  
128  
56  
A2001(M)-CUE 0.1 kW  
A2002(M)-CUE 0.2 kW  
A2004(M)-CUE 0.4 kW  
75  
3
3
5
88  
110  
3-2  
Design  
Chapter 3  
D Single/Three-phase 200-VAC Input Model  
3G3EV model  
Output  
W
H
D
W1  
H1  
118  
T
Weight  
(kg)  
Approx.  
0.5  
Approx.  
0.6  
68  
128  
56  
AB001(M)-CUE 0.1 kW  
AB002(M)-CUE 0.2 kW  
75  
3
3
108  
H 3G3EV-A2007(M)-CUE to 3G3EV-A2015(M)-CUE (0.75 to 1.5 kW):  
Three-phase 200-VAC Input  
3G3EV-AB004(M)-CUE to 3G3EV-AB015(M)-CUE (0.4 to 1.5 kW):  
Single/Three-phase 200-VAC Input  
3G3EV-A4002(M)-CUE to 3G3EV-A4015(M)-CUE (0.2 to 1.5 kW):  
Three-phase 400-VAC Input  
Two, 4.5 dia.  
Note Install the Inverter with four M4 bolts.  
D Three-phase 200-VAC Input Model  
3G3EV model  
Output  
W
H
D
D
W1  
W1  
H1  
H1  
Weight (kg)  
Approx. 1.3  
Approx. 1.5  
108  
128  
96  
118  
118  
A2007(M)-CUE 0.75 kW  
A2015(M)-CUE 1.5 kW  
130  
155  
D Single/Three-phase 200-VAC Input Model  
3G3EV model  
Output  
W
H
Weight (kg)  
Approx. 1.3  
Approx. 1.3  
Approx. 2.0  
108  
130  
128  
130  
170  
96  
AB004(M)-CUE 0.4 kW  
AB007(M)-CUE 0.75 kW  
AB015(M)-CUE 1.5 kW  
118  
3-3  
Design  
Chapter 3  
D Three-phase 400-VAC Input Model  
3G3EV model  
A4002(M)-CUE  
A4004(M)-CUE  
A4007(M)-CUE  
A4015(M)-CUE  
Output  
0.2 kW  
W
H
D
W1  
H1  
Weight (kg)  
Approx. 1.0  
Approx. 1.0  
Approx. 1.5  
Approx. 2.0  
108  
128  
96  
118  
92  
0.4 kW  
0.75 kW  
1.5 kW  
110  
140  
170  
130  
118  
3-1-2 Installation Conditions  
H Installation Site  
Install the Inverter under the following conditions:  
Ambient temperature for operation: –10°C to 50°C  
Humidity: 90% RH or less (non-condensing)  
Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally en-  
closed panel that is completely shielded from suspended dust.  
When installing or operating the Inverter, always take special care so that metal powder, oil, water, or  
other foreign matter do not get in the Inverter.  
Do not install the Inverter on inflammables such as wood.  
H Direction of Installation  
Install the Inverter on a vertical surface so that the characters on the nameplate are oriented upward.  
H Installation Space  
When installing the Inverter, always provide the following installation space to allow normal heat dis-  
sipation from the Inverter:  
100 mm min.  
W= 30 mm min.  
Air  
Side  
Air  
100 mm min.  
3-4  
Design  
Chapter 3  
H Ambient Temperature Control  
To enhance operation reliability, the Inverter should be installed in an environment free from extreme  
temperature rises.  
If the Inverter is installed in an enclosed environment such as a box, use a cooling fan or air conditioner  
to maintain the internal air temperature below 50°C.  
The surface temperature of the Inverter may reach 30°C higher than the ambient temperature. There-  
fore, keep all thermally susceptible devices and wires away from the Inverter.  
H Protecting the Inverter from Foreign Matter during Installation  
Place a cover over the Inverter to shield it from metal powder produced by drilling during installation.  
(Upon completion of installation, always remove the cover from the Inverter. Otherwise, ventilation  
will be affected, causing the invert to overheat.)  
3-5  
Design  
Chapter 3  
3-2 Wiring  
H Cautions and Warnings  
WARNING  
WARNING  
WARNING  
WARNING  
WARNING  
WARNING  
WARNING  
Be sure that the power supply is turned OFF before wiring. Wait for at least one  
minute after turning off the power supply. Otherwise, an electric shock may occur.  
!
Wiring must be performed by authorized persons specialized in electrical work.  
Otherwise, an electric shock or fire may occur.  
!
!
!
!
!
!
Be sure to check for proper operation after wiring the emergency stop circuit.  
Otherwise, physical injury may occur.  
Be sure to ground the ground terminal. Otherwise, an electric shock or fire may  
occur.  
Be sure to connect the ground to the supply neutral for 400-VAC-class Inverters.  
Otherwise, an electric shock or equipment damage may occur.  
Be sure to confirm that the rated voltage of the Inverter coincides with the voltage  
of the AC power supply. Otherwise, a fire, injury, or equipment trouble may occur.  
When connecting the braking resistor or Braking Resistor Unit, be sure to follow  
the instructions specified in the Installation Manual. Otherwise, a fire may occur.  
WARNING  
WARNING  
Be sure to wire correctly. Otherwise, injury or equipment damage may occur.  
!
!
Be sure to firmly tighten the screws on the terminal block. Otherwise, a fire, inju-  
ry, or equipment damage may occur.  
Caution  
!
Do not connect the AC power to the output terminal U, V, or W. Otherwise, equip-  
ment damage or trouble may occur.  
3-6  
Design  
Chapter 3  
3-2-1 Terminal Blocks  
H Name of Each Terminal Block  
Main Circuit Terminals (Input)  
Power input  
terminals  
Braking resistor  
connection terminals  
L1 N/L2 L3 B1 B2  
Control circuit terminals  
(input/output)  
Control circuit terminals (output)  
S2 S3 SC AM AC PA PC  
MA MB MC  
SF SR S1 SC FS FR FC  
U
V
W
Ground terminal  
Motor output  
terminals  
Main Circuit Terminals (Output)  
Note This diagram shows an Inverter with all terminal block covers removed.  
The standard Inverters are not provided with the S2 to PC terminal block.  
3-7  
Design  
Chapter 3  
H Main Circuit Terminals  
D Input Terminals (Top Section)  
Terminal  
symbol  
Name and description  
L1  
Power input terminals  
N/L2  
L3  
AB:  
Single-phase 200 to 240 VAC, 50/60 Hz  
Three-phase 200 to 230 VAC, 50/60 Hz  
Three-phase 380 to 460 VAC, 50/60 Hz  
A4:  
Note: Single-phase power must be input between terminals L1 to N/L2  
Braking resistor connection terminals (see note)  
B1  
B2  
Terminals for connecting an optional braking resistor  
Note Before shipping, a resin plate is attached to each braking resistor connection terminal to prevent  
incorrect wiring.  
When connecting a braking resistor, always remove the resin plates with a pair of long-nose  
pliers.  
D Output Terminals (Bottom Section)  
Terminal  
symbol  
Name and description  
U
V
W
Motor output terminals  
Three-phase power output terminals for operating the motor. (Never connect an AC power  
supply to these terminals.)  
ABj: Three-phase 200 to 230 VAC  
A4j: Three-phase 380 to 460 VAC  
Note: Depends on the input voltage.  
Ground terminal  
Always use a grounding terminal with a ground resistance of followings,  
100 or less of 200-VAC class  
10 or less of 400-VAC class  
(Connect also to the power supply neutral to conform to the EC Directives.)  
Be sure to connect a grounding line to the FG terminal and also connect directly to the FG  
terminal of the motor.  
Terminal block screw (M3.5)  
Crimp terminal  
6.2 mm max.  
3-8  
Design  
Chapter 3  
H Control Circuit Terminals  
D Input Terminals (On Right-hand Side)  
No external power supply is required because a built-in power supply is provided.  
Terminal  
symbol  
Name and description  
Interface  
SF  
Forward/Stop (see note 3)  
24 V  
The motor will rotate in the forward direction when the  
signal on this terminal is turned ON. The motor will stop  
rotating when the signal is turned OFF.  
3.3 K  
S1 to S3  
SR  
Reverse/Stop (see note 3)  
0.1 µ  
The motor will rotate in the reversed direction when the  
signal on this terminal is turned ON. The motor will stop  
rotating when the signal is turned OFF.  
S1 to S3  
SC  
Multi-function input (see notes 1, 3)  
Sequence input common  
Input terminal common for SF to S3  
Frequency reference power supply  
FS  
12 V  
Output voltage: 12 VDC  
Permissible current: 20 mA  
20 K  
FR  
FC  
Frequency reference input (see note 2)  
0 to 10 VDC  
Input impedance  
Frequency reference common  
20 kΩ  
Note 1. Functions are set with constants n06 to n08. Only n06: S1 is, however, available to the stan-  
dard model.  
Refer to the following for factory settings:  
S1: Fault reset  
S2: External fault (input to contact a) (n07=2)  
S3: Multi-step speed command (n08=4)  
(n06=1)  
Note 2. The FR terminal will function as a 4- to 20-mA input terminal with the setting of the internal  
switch 1 (SW1) and n02 for operation mode selection.  
Note 3. The sequential input method will change with the setting of the internal switch 2 (SW2).  
D Output Terminals (On Left-hand Side)  
Terminal  
symbol  
Name and description  
Interface  
MA  
Multi-function contact output (contact a) (see note)  
MB  
MC  
Multi-function contact output (contact b) (see note)  
Multi-function contact output (common)  
30 VDC  
250 VAC  
Note Constant No. 09 (n09) is used to set the function. This constant is factory set to “during running.”  
3-9  
Design  
Chapter 3  
D Output Terminals (On Right-hand Side)  
Terminal  
symbol  
Name and description  
Interface  
PA  
Multi-function photocoupler output (see note)  
PC  
Multi-function photocoupler output (common)  
50 mA at 48 VDC max.  
Note Constant No. 10 (n10) is used to set this function. This constant is factory-set to “fault.”  
The standard model does not have multi-function photocoupler output.  
D Analog Output Terminals (On Right-hand Side)  
Terminal  
symbol  
Name and description  
Interface  
AM  
Multi-function analog output (see note)  
AC  
Multi-function analog output (common)  
2 mA at  
0 to +10 VDC max.  
Note Constant No. 44 (n44) is used to set this function and constant No. 45 (n45) is used to set the  
multiplying factor, which are factory-set to “output frequency” and “3V at maximum frequency”  
respectively.  
The standard model does not have analog output.  
H Standard Connection Diagram  
D Main Circuit Terminal Connections  
Braking Unit (Optional)  
Circuit  
Clamp core  
Three-phase,  
breaker  
Noise Filter  
200 VAC  
Single-phase,  
200 VAC  
Three-phase,  
400 VAC  
Note 1. Three-phase 200 VAC (400 VAC) can be input to L1, L2, and L3.  
Note 2. For the 400-VAC-class Inverter, be sure to ground the supply neutral.  
3-10  
Design  
Chapter 3  
D Control Circuit Terminal Connections  
Multi-function contact  
output (Contact a)  
Forward/Stop  
Reverse/Stop  
Clamp core  
(Contact b)  
Common  
S1 to S3  
Multi-function input  
Sequence input common  
Multi-function  
photocoupler output  
Multi-function  
photocoupler output  
common  
Clamp  
core  
Frequency reference adjuster  
Frequency reference  
power supply (12 V)  
Multi-function analog output  
Voltmeter  
Frequency reference  
input  
Frequency reference  
input common  
Multi-function analog  
output common  
(2 k, 1/4 W min.)  
Note 1. The standard model does not have the S2, S3, PA, PC, AM, or AC terminal.  
Note 2. The sequence input and the sequence output can be wired with a single shielded cable.  
3-2-2 Wiring Around the Main Circuit  
System reliability and noise resistance are affected by the wiring method used. There-  
fore, always follow the instructions given below when connecting the Inverter to periph-  
eral devices and other parts.  
H Wire Size  
For the main circuit and ground, always use 600-V polyvinyl chloride (PVC) cables.  
If the cable is long and may cause voltage drops, increase the wire size according to the cable length.  
2
Model  
3G3EV-A2001(M)-CUE  
3G3EV-AB001(M)-CUE  
Terminal symbol  
R S T B1 B2  
Terminal screw  
M3.5  
Wire size (mm )  
0.75 to 2  
U V W  
R S T B1 B2  
U V W  
M3.5  
M3.5  
M3.5  
M3.5  
0.75 to 2  
0.75 to 2  
0.75 to 2  
3G3EV-A2002(M)-CUE  
3G3EV-AB002(M)-CUE  
3G3EV-A4002(M)-CUE  
3G3EV-A2004(M)-CUE  
3G3EV-AB004(M)-CUE  
3G3EV-A4004(M)-CUE  
3G3EV-A2007(M)-CUE  
3G3EV-AB007(M)-CUE  
3G3EV-A4007(M)-CUE  
3G3EV-A2015(M)-CUE  
3G3EV-AB015(M)-CUE  
3G3EV-A4015(M)-CUE  
R S T B1 B2  
U V W  
R S T B1 B2  
U V W  
R S T B1 B2  
U V W  
1.25 to 2  
0.75 to 2  
Note Tighten the M3.5 terminal screw to the torque of 0.8 N S m.  
3-11  
Design  
Chapter 3  
Determining the Wire Size  
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.  
Line voltage drop VD is calculated as follows:  
Ǹ
VD (V) =  
x wire resistance (/km) x wire length (m) x amperage (A) x 10–3  
3
H Conformance to EMC Directives  
D Wiring Power Supply  
Install the Inverter and Noise Filter on ground plates.  
Be sure to wire the Inverter through a dedicated Noise Filter.  
Reduce the length of the ground wire as much as possible and connect the ground wire to the ground  
securely.  
Reduce length of the cable between the Inverter and the Noise Filter as much as possible. The cable  
length must not exceed 400 mm.  
Three-phase 200-VAC Noise Filter  
Inverter  
Model 3G3EV-  
A2001(M)-CUE  
A2002(M)-CUE  
A2004(M)-CUE  
A2007(M)-CUE  
A2015(M)-CUE  
Single-phase Noise Filter (Soshin Electric)  
Model 3G3EV- Rated current (A)  
PNF3006A-YN  
6
PNF3010A-YN  
10  
Single-phase 200-VAC Noise Filter  
Inverter  
Single-phase Noise Filter (Soshin Electric)  
Model 3G3EV-  
AB001(M)-CUE  
AB002(M)-CUE  
AB004(M)-CUE  
AB007(M)-CUE  
AB015(M)-CUE  
Model 3G3EV-  
PNF2003A-YN  
Rated current (A)  
Weight (kg)  
Approx. 0.5  
Dimensions  
66 × 117 × 67  
3
PNF2010A-YN  
PNF2020A-YN  
10  
20  
Approx. 0.6  
Approx. 1.0  
66 × 117 × 67  
74 × 128 × 72  
Single-phase 200-VAC Noise Filter  
Inverter  
Single-phase Noise Filter (Soshin Electric)  
Rated current (A) Weight (kg)  
Approx. 1.0  
Model 3G3EV-  
A4002(M)-CUE  
A4004(M)-CUE  
A4007(M)-CUE  
A4015(M)-CUE  
Model 3G3EV-  
PNF3007C-YN  
Dimensions  
108 × 128 × 75  
7
3-12  
Design  
Chapter 3  
D Wiring between Inverter and Motor  
Be sure to use a shield braided cable to connect the Inverter and motor.  
Reduce the length of the cable as much as possible and ground the shield on the Inverter side and motor  
side. The cable length must not exceed 20 m. Furthermore, attach a clamp core close to the Inverter’s  
output terminals and the shield of the Inverter side.  
Recommended Clamp Core  
Product name  
Clamp filter  
Model  
ZCAT3035-1330  
Manufacturer  
TDK  
D Wiring Control Circuit Cable  
Be sure to use a shield braided cable for the control circuit and ground the shield on the inverter side at  
one point. Further more, attach a clamp core close to the Inverter.  
Braking Unit (Optional)  
Circuit  
breaker  
Clamp core  
Three-phase,  
200 VAC  
Noise Filter  
Single-phase,  
200 VAC  
Three-phase,  
400-VAC  
Note For the 400-VAC-class Inverter, be sure to ground the supply neutral.  
D Grounding the Braided Shield  
It is recommended that a cable clamp be attached to the braided shield for grounding, which allows the  
secure grounding of the braided shield.  
Cable clamp  
Ground plate  
Cable  
Shield  
3-13  
Design  
Chapter 3  
H Conformance to LVD  
Be sure to insert a molded-case circuit breaker (MCCB) into the power line connected to the Inverter for  
short-circuit protection. A single MCCB is required by each Inverter.  
The frequency reference power supply (FS) is basic isolation. Its insulation needs to be reinforced when  
connecting to a peripheral device.  
Inverter  
MCCB  
Model 3G3EV-  
Rated current (A)  
Type  
NF30 model (Mitsubishi Electric)  
NF30 model (Mitsubishi Electric)  
NF30 model (Mitsubishi Electric)  
A2001(M)-CUE  
5
A2002(M)-CUE  
A2004(M)-CUE  
A2007(M)-CUE  
A2015(M)-CUE  
AB001(M)-CUE  
AB002(M)-CUE  
AB004(M)-CUE  
AB007(M)-CUE  
AB015(M)-CUE  
A4002(M)-CUE  
A4004(M)-CUE  
A4007(M)-CUE  
A4015(M)-CUE  
5
5
10  
20  
5
5
10  
20  
20  
5
5
5
10  
H Wiring on the Input Side of Main Circuit  
D Safe Power Supply Sequence  
If a single MCCB is shared by more than one Inverter or other equipment, refer to the following and  
provide a sequence that will turn off the power when abnormal output results.  
3-phase/  
single phase  
200 VAC  
Noise filter  
Fuse  
L1 (R)  
L2 (S)  
L3 (T)  
Fault output (NC)  
SYSDRIVE 3G3EV  
3-14  
Design  
Chapter 3  
D Installing a Ground Fault Interrupter  
Inverter outputs use high-speed switching, so high-frequency leakage current is generated. In general,  
a leakage current of approximately 100 mA will occur for each Inverter (when the power cable is 1 m),  
and approximately 5 mA for each additional meter of power cable. Therefore, at the power supply input  
area, use a special-purpose breaker for Inverters, which detects only the leakage current in the frequen-  
cy range that is hazardous to humans and excludes high-frequency leakage current.  
Countermeasures taken for the EMC tend to increase the leakage current, therefore careful attention  
must be paid in selecting a breaker.  
For the special-purpose breaker for Inverters, choose a ground fault interrupter with a sensitivity am-  
perage of at least10 mA per Inverter.  
When using a general leakage breaker, choose a ground fault interrupter with a sensitivity amperage  
of 200 mA or more per Inverter and with an operating time of 0.1 s or more.  
D Installing a Magnetic Contactor  
This Inverter can be used without a magnetic contactor (MC) on the power supply side.  
If the power supply for the main circuit is to be shut off because of the sequence, a magnetic contactor  
can be used instead of a molded-case circuit breaker.  
However, when a magnetic contactor is installed on the primary side of the main circuit to forcibly stop a  
load, note that regenerative braking does not work and the load coasts to a stop.  
A load can be started and stopped by opening and closing the magnetic contactor on the primary side.  
Note, however, that frequently opening and closing the magnetic contactor may cause the Inverter to  
break down.  
When the Inverter is operated with a Digital Operator, automatic operation cannot be performed after  
recovery from a power interruption.  
D Connecting Input Power Supply to the Terminal Block  
Because the phase sequence of input power supply is irrelevant to the phase sequence (L1, L2/N, L3) of  
the terminal block, input power supply can be connected to any terminal on the terminal block.  
D Installing an AC Reactor  
It is recommended that an AC reactor be inserted in the input power supply side to suppress harmonics.  
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or the phase  
advance capacitor is switched, an excessive peak current may flow through the input power circuit,  
causing the converter unit to break down. To prevent this, install an optional AC reactor on the input side  
of the Inverter. This also improves the power factor on the power supply side.  
D Installing a Surge Absorber  
Always use a surge absorber or diode for the inductive loads to be connected to the Inverter. These  
inductive loads include magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and  
magnetic brakes.  
D Wiring of Braking Resistor/Braking Resistor Unit  
When using an Inverter for loads with a large inertia or for vertical axis loads, regenerative energy will be  
fed back.  
3-15  
Design  
Chapter 3  
If the regenerative energy exceeds the Inverter capacity, overvoltage will be detected in the main circuit.  
In such a case, use a Braking Resistor or Braking Resistor Unit.  
Note Be sure to create a sequence that will turn OFF the Inverter power supply when resistor over-  
heating occurs. When using a Braking Resistor, be sure to install a thermal relay to detect resis-  
tor overheating. When using a Braking Resistor Unit, use an error output contact. Otherwise, a  
fire may occur.  
Model 3G3IV-  
Model 3G3EV-  
Minimum connected  
resistance  
Braking Resistor  
Braking Resistor Unit  
(Duty Cycle 10%ED)  
(Duty Cycle 3%ED)  
PERF150WJ401 (400 ) ---  
200 Ω  
A2001(M)-CUE  
A2002(M)-CUE  
A2004(M)-CUE  
A2007(M)-CUE  
A2015(M)-CUE  
AB001(M)-CUE  
AB002(M)-CUE  
AB004(M)-CUE  
AB007(M)-CUE  
AB015(M)-CUE  
A4002(M)-CUE  
A4004(M)-CUE  
A4007(M)-CUE  
A4015(M)-CUE  
PERF150WJ201 (200 ) PLKEB20P7 (200 70 W)  
80 Ω  
PERF150WJ101 (100 ) PLKEB21P5 (100 260 W) 60 Ω  
PERF150WJ401 (400 ) ---  
200 Ω  
PERF150WJ201 (200 ) PLKEB20P7 (200 70 W)  
80 Ω  
PERF150WJ101 (100 ) PLKEB21P5 (100 260 W) 60 Ω  
PERF150WJ751 (750 ) PLKEB40P7 (750 70 W)  
750 Ω  
510 Ω  
PERF150WJ401 (400 ) PLKEB41P5 (400 260 W) 240 Ω  
Note Do not use a Resistor whose resistance is below the minimum connected resistance. Other-  
wise, the Inverter will be damaged.  
H Wiring on the Output Side of Main Circuit  
D Connecting the Terminal Block to the Load  
Connect output terminals U, V, and W to motor lead wires U, V, and W, respectively.  
D Never Connect Power Supply to Output Terminals  
Caution  
Never connect a power supply to output terminals L1, N/L2, and L3.  
If voltage is applied to the output terminals, the internal mechanism of the Inverter  
will be damaged.  
!
D Never Short or Ground the Output Terminals  
Caution  
If the output terminals are touched with bare hands or the output wires come into  
contact with the Inverter casing, an electric shock or grounding will occur. This is ex-  
tremely hazardous. Also, be careful not to short the output wires.  
!
D Do Not Use a Phase Advance Capacitor or LC/RC Noise Filter  
Never connect a phase advance capacitor or LC/RC Noise Filter to the output circuit. Doing so may  
result in damage to the Inverter or cause other parts to burn.  
3-16  
Design  
Chapter 3  
D Do Not Use an Electromagnetic Switch  
Do not connect an electromagnetic switch or magnetic contactor to the output circuit. If a load is con-  
nected to the Inverter during operation, an inrush current will actuate the overcurrent protective circuit in  
the Inverter.  
D Installing a Thermal Relay  
This Inverter has an electronic thermal protection function to protect the motor from overheating. If,  
however, more than one motor is operated with one Inverter or a multipolar motor is used, always install  
a thermal relay (THR) between the Inverter and the motor and set to “0.0” (no thermal protection) for  
constant No. 31 (“THR” indicator).  
In this case, program the sequence so that the magnetic contactor on the input side of the main circuit is  
turned off by the contact of the thermal relay.  
D Installing a Noise Filter on the Output Side  
Connect a Noise Filter to the output side of the Inverter to reduce radio noise and induction noise.  
3G3EV  
3G3IV-PLF  
Noise Filter  
Power supply  
Induction noise  
Radio noise  
Signal line  
Controller  
AM radio  
Induction Noise:  
Radio Noise:  
Electromagnetic induction generates noise on the signal line, causing the control-  
ler to malfunction.  
Electromagnetic waves from the Inverter and cables cause the broadcasting radio  
receiver to make noise.  
D How to Prevent Radio Noise  
Radio noise is generated from the Inverter as well as the input and output lines. To reduce radio noise,  
install Noise Filters on both input and output sides, and also install the Inverter in a totally enclosed steel  
box.  
3-17  
Design  
Chapter 3  
The cable between the Inverter and the motor should be as short as possible.  
Steel box  
Metal pipe  
3G3EV  
Power supply  
Noise  
Filter  
Noise  
Filter  
D Cable Length between Inverter and Motor  
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase,  
causing the Inverter output current to increase as well. This may affect peripheral devices. To prevent  
this, adjust the carrier frequency (set in n37) as shown in the table below.  
Cable length between Inverter and motor  
Carrier frequency (n37)  
20 m max.  
100 m max.  
10 kHz max. (1, 2, 3, 4)  
5 kHz max. (1, 2)  
Note When the cable length between Inverter and motor exceeds 20 m, the system must be con-  
firmed for conformity to the EMC Directives.  
H Ground Wiring  
Always use a ground terminal with the following ground resistance.  
200-VAC Class:  
400-VAC Class:  
100 or less  
10 or less  
Also connect to the power supply neutral.  
Do not share the ground wire with other devices such as a welder or power tool.  
Always use a ground wire that complies with technical standards on electrical equipment. Route the  
ground wire so that the total length is as short as possible.  
3-18  
Design  
Chapter 3  
When using more than one Inverter, be careful not to loop the ground wire.  
3-2-3 Wiring Control Circuit Terminals  
The control signal line must be 50 m or less and must be separated from the power line.  
Use batch shielded cable for sequence input. If frequency references are input  
externally, use a twisted-pair shielded line.  
H Wiring Sequence Input/Output Terminals  
Wire the sequence input terminals (SF, SR, S1 to S3, and SC), multi-function contact output terminals  
(MA, MB, and MC), and multi-function photocoupler output terminals (PA and PC) as described below.  
D Wires to be Used  
Wire type  
Single wire  
Stranded wire  
Wire size  
Wire to be used  
Polyethylene-shielded cable  
2
0.5 to 1.25 mm  
2
0.5 to 0.75 mm  
3-19  
Design  
Chapter 3  
D Solderless Terminals for Control Circuit Terminals  
The use of solderless terminals for the control circuit terminals is recommended because solderless  
terminals are easy to connect securely.  
d1 dia.  
d2 dia.  
Wire thickness  
Model  
d1  
d2  
Manufacturer  
Terminal  
2
Phoenix Contact  
0.5 mm  
A1 0.5-8WH  
1.00  
2.60  
SF, SR, S1 to  
S3, SC, FS, FR,  
FC  
2
MA, MB, MC  
0.7 mm  
A1 0.75-8GY  
A1 1-8RD  
1.20  
1.40  
2.80  
3.00  
2
1 mm  
D Wiring Method  
Wire each terminal as follows:  
a) Loosen the terminal screw with a thin-slotted screwdriver.  
b) Insert the wire from underneath the terminal block.  
c) Tighten the terminal screw firmly.  
Always separate the control signal line from the main circuit cables and other power cables.  
Insulate the shielded sections with insulation tape, etc., from other signal lines or equipment and  
ground on the Inverter side.  
Thin-slotted screwdriver  
Control circuit  
terminal block  
Length of stripped  
portion: Approx. 5.5 mm  
Do not solder this portion.  
(Otherwise, faulty contact may result.)  
Wire  
3-20  
Design  
Chapter 3  
H Wiring Frequency Reference Input Terminals  
If frequency references are input using a D/A Unit (digital-to-analog converter) or external power supply,  
wire the frequency reference input terminals (FR and FC) as described below.  
D Wires to be Used  
Always use twisted-pair shielded wires to prevent malfunctions due to noise.  
Wire type  
Single wire  
Wire size  
Wire to be used  
2
Polyethylene-insulated cable for instrumentation (with  
shield)  
0.5 to 1.25 mm  
2
Stranded wire  
0.5 to 1.25 mm  
D Wiring Method  
The wiring procedure is the same as for sequence input/output terminals, described previously.  
Always separate the cables from the main circuit cables and other power cables.  
Connect the shield to the ground terminal of the Inverter. Do not connect to the controller.  
Insulate the shield with tape to prevent it from coming into contact with other signal lines and devices.  
H Tightening Torque of Control Circuit Terminals  
Tighten the control circuit terminals to the torque of 0.5 N S m which is the same torque as for the M3  
screws.  
Note 1. Applying a torque of greater than 0.5 N S m may damage the terminal block.  
Note 2. If the tightening torque is insufficient, wires may be disconnected.  
H Selection of Frequency Reference or Sequential Input  
Caution  
Do not touch the terminals of the Inverter within one minute after the Inverter is  
turned off, otherwise an electric shock may be received.  
!
Mounting or Dismounting the Digital Operator  
1. To dismount the Digital Operator, insert a flat-blade screwdriver into the groove on the bottom of the  
Digital Operator and lift the Digital Operator.  
2. After the connector is removed, hold the lower part of the Digital Operator and slide the Digital Oper-  
ator downwards.  
3-21  
Design  
Chapter 3  
To mount the Digital Operator, connect the upper part of the Digital Operator first, and press the Digital  
Operator until the internal connector is securely connected.  
D Selecting Frequency Reference Input (Current Input)  
1. Change of Constant  
Set constant n02 for operation mode selection to 4 or 5.  
n02 = 4: The Inverter is operated with the Digital Operator while frequency references are pro-  
vided as terminal input (current input).  
n02 = 5: The Inverter is operated and frequency references are provided through terminals (cur-  
rent input).  
2. SW1 Selector  
Set SW1 to ON by sliding SW1 to the right to operate the Inverter with current input.  
Sequential Input Selection (NPN/PNP Transistor)  
Select NPN or PNP transistor input with SW2.  
24 V  
24 V  
S1 to S3  
S1 to S3  
3.3 K  
3.3 K  
0.1 µ  
0.1 µ  
3-22  
4
Chapter 4  
Specifications  
4-1 Specifications of Main Unit  
4-2 Specifications of Noise Filter  
Specifications  
Chapter 4  
4-1 Specifications of Main Unit  
H Ratings  
Model 3G3EV-  
A2001(M)- A2002(M)- A2004(M)- A2007(M)- A2015(M)-  
CUE CUE CUE CUE CUE  
Three  
phase,  
200 VAC  
Power  
supply  
Rated voltage and Three-phase, 200 to 230 VAC, 50/60 Hz  
frequency  
Allowable voltage –15% to 10 %  
fluctuation  
Allowable  
frequency  
fluctuation  
5%  
Heating value (W)  
Weight (kg)  
11.9  
0.5  
18.8  
0.6  
33.2  
0.9  
51.7  
71.6  
1.3  
1.5  
1.5  
Maximum applicable motor capacity  
(kW)  
0.1  
0.2  
0.4  
0.75  
Output  
specifi-  
cations  
Rated output capacity (kVA) 0.3  
0.6  
1.5  
1.1  
3.0  
1.9  
5.0  
2.7  
7.0  
Rated output current (A)  
Rated output voltage  
0.8  
Three-phase, 200 to 230 VAC (Corresponds to the input  
voltage)  
Maximum output frequency  
400 Hz (Parameter setting)  
Self-cooling  
Cooling method  
Model 3G3EV-  
AB001(M)- AB002(M)- AB004(M)- AB007(M)- AB015(M)  
CUE  
CUE  
CUE  
CUE  
-CUE  
Single  
phase/  
Three  
phase,  
200 VAC  
Power  
supply  
Rated voltage and Single-phase/Three-phase, 200 to 240 VAC, 50/60 Hz  
frequency  
Allowable voltage –15% to 10 %  
fluctuation  
Allowable  
frequency  
fluctuation  
5%  
Heating value (W)  
Weight (kg)  
Maximum applicable motor capacity  
(kW)  
12.6  
0.5  
20.3  
0.6  
25.3  
1.3  
55.3  
1.3  
78.4  
2.0  
1.5  
0.1  
0.2  
0.4  
0.75  
Output  
specifi-  
cations  
Rated output capacity (kVA) 0.3  
0.6  
1.5  
1.1  
3.0  
1.9  
5.0  
2.7  
7.0  
Rated output current (A)  
Rated output voltage  
0.8  
Three-phase, 200 to 230 VAC (Corresponds to the input  
voltage)  
Maximum output frequency  
400 Hz (Parameter setting)  
Self-cooling  
Cooling method  
Note Model numbers with a suffix of “-CUE” indicate models approved by UL. (Approval has not been  
obtained for models with a model number suffix of “-CE.”)  
4-2  
Specifications  
Chapter 4  
Model 3G3EV-  
---  
A4002(M)- A4004(M)- A4007(M)- A4015(M)-  
CUE  
CUE  
CUE  
CUE  
Three  
phase,  
400 VAC  
Power  
supply  
Rated voltage and  
frequency  
Allowable voltage  
fluctuation  
Three-phase, 380 to 460 VAC, 50/60 Hz  
–15% to 10 %  
Allowable frequency 5%  
fluctuation  
Heating value (W)  
Weight (kg)  
---  
25.5  
1.0  
34.7  
1.0  
56.0  
1.5  
78.5  
2.0  
Maximum applicable motor capacity  
(kW)  
0.2 (0.37) 0.4 (0.55) 0.75 (1.1) 1.5 (1.5)  
Output  
specifi-  
cations  
Rated output capacity (kVA)  
Rated output current (A)  
Rated output voltage  
0.9  
1.2  
1.4  
1.8  
2.6  
3.4  
3.7  
4.8  
Three-phase, 380 to 460 VAC (Corresponds to the input  
voltage)  
Maximum output frequency  
400 Hz (Parameter setting)  
Self-cooling  
Cooling method  
H General Specifications  
Installation type  
Enclosed wall-mounted type (IP20)  
Indoor (free from corrosive gases and dust)  
–10° to 50°C  
90% or less (no-condensing)  
–20° to 60°C  
Installation site  
Ambient temperature for operation  
Humidity  
Ambient temperature for storage  
Altitude  
1,000 m max.  
2
Vibration resistance  
Less than 20 Hz:  
20 to 50 Hz:  
1G {9.8 m/s } or less  
2
0.2G {1.96 m/s } or less  
Cable length between Inverter and  
motor  
20 m max. (When the cable length exceeds 20 m, the system  
must be confirmed for conformity to the EMC Directives. )  
Applicable standards  
prEN50178, EN50081, EN50082 (with RFI filter and shielded  
cable)  
UL/CUL standards  
4-3  
Specifications  
Chapter 4  
H Control Characteristics  
Control method  
Sine-wave PWM method (automatic torque boost)  
Frequency control range  
0.5 to 400 Hz (standard model: 1.5 to 400 Hz)  
Frequency accuracy  
(temperature fluctuation)  
Digital command:  
0.01% (–10°C to 50°C)  
Analog command:  
1% (25 10°C)  
Frequency setting  
resolution  
Digital command:  
0.1 Hz (less than 100 Hz), 1 Hz (100 Hz or more)  
Analog command:  
0.06 Hz (60 Hz)  
Frequency output resolution 0.1 Hz (operation resolution)  
Overload resistance  
1 minute or less when 150% of rated output current is received  
Frequency setting signal  
0 to 10 VDC (20 k) or 4 to 20 mA (250 )  
Note This setting can be switched using the internal DIP switch.  
Acceleration/Deceleration  
time  
0.0 to 999 seconds (acceleration and deceleration times are set separately)  
Braking torque (continuous Approximately 20%  
regenerative braking)  
Note 125% to 220% when braking resistor is externally installed.  
Voltage/Frequency  
characteristics  
Simple V/f pattern setting  
H Protection Functions  
Motor protection  
Electronic thermal protection  
Instantaneous overcurrent  
protection  
When 250% of the rated output amperage is exceeded  
Overload protection  
When 150% of the rated output amperage is exceeded for one minute  
Overvoltage protection  
Stops the system when DC voltage of the main circuit exceeds  
approximately 410 V (400-VAC class: 820 V)  
Voltage drop protection  
3G3EV-A2j: Stops the system when voltage drops below approximately  
200 VDC  
3G3EV-ABj: Stops the system when voltage drops below approximately  
160 VDC  
3G3EV-A4j: Stops the system when voltage drops below approximately  
400 VDC  
Protection from  
instantaneous power  
interruption  
Stops the system when a power interruption lasts for 15 ms or more.  
Operation can be continued by setting constant No. 36 as follows:  
Operation is continued if a power interruption only lasts for approximately 0.5  
second or less.  
Operation is continued unconditionally.  
Detects a fin temperature of 110 10°C  
Radiation fin overheat  
protection  
Ground protection  
Overcurrent level protection  
4-4  
Specifications  
Chapter 4  
H Operation Specifications  
Three photocoupler input terminals (24 VDC, 8 mA)  
Control input  
Forward/stop [SF]  
Reverse/stop [SR]  
Multi-function input [S1] (set in constant No. 06)  
Multi-function input [S2] (set in constant No. 07)  
Multi-function input [S3] (set in constant No. 08)  
Note When 3-wire sequence mode (constant No. 01 = “9”) is selected, the  
terminals become as follows:  
Run command [SF]  
Stop command [SR]  
Forward/reverse rotation command [S1]  
Note The standard Inverters are not provided with S2 and S3 terminals.  
One analog input terminal (0 to 10 VDC or 4 to 20 mA)  
Frequency reference input [Between FC and FR]  
Control output  
Analog output  
One SPDT relay contact output terminal [MA, MB]  
(30 VDC and 1A; 250 VAC and 1A)  
Multi-function contact output (set in constant No. 09)  
One photocoupler input terminal [PA] (48 VDC, 50 mA)  
Multi-function photocoupler output (set in constant No. 10)  
Note The standard Inverters are not provided with the multi-function photo-  
coupler output.  
One analog voltage output [AM] (0 to 10 VDC, 2 mA)  
Multi-functional analog output (Constant No. 44 is used to set the function  
and constant No. 45 is used to set the multiplying factor.)  
The output frequency or output current can be monitored. The Inverter is fac-  
tory-set to output frequency monitoring.  
Note The standard Inverters are not provided with the multi-function analog  
output.  
4-5  
Specifications  
Chapter 4  
4-2 Specifications of Noise Filter  
Three-phase 200-VAC Noise Filter  
Inverter  
Single-phase Noise Filter (Soshin Electric)  
Model 3G3EV-  
Inverter  
capacity (kVA)  
Model 3G3EV-  
Rated voltage Rated current  
Weight (kg)  
(V)  
(A)  
PNF3006A-YN  
250 VAC  
6
Approx. 0.8  
A2001(M)-CUE  
A2002(M)-CUE  
A2004(M)-CUE  
A2007(M)-CUE  
A2015(M)-CUE  
0.3  
0.6  
1.1  
1.9  
2.7  
PNF3010A-YN  
10  
Single-phase 200-VAC Noise Filter  
Inverter  
Single-phase Noise Filter (Soshin Electric)  
Model 3G3EV-  
Inverter  
capacity (kVA)  
Model 3G3EV-  
Rated voltage Rated current  
Weight (kg)  
(V)  
(A)  
PNF2003A-YN  
PNF2010A-YN  
PNF2020A-YN  
250 VAC  
3
Approx. 0.5  
Approx. 0.6  
Approx. 1.0  
AB001(M)-CUE  
AB002(M)-CUE  
AB004(M)-CUE  
AB007(M)-CUE  
AB015(M)-CUE  
0.3  
0.6  
1.1  
1.9  
2.7  
10  
20  
Three-phase 400-VAC Noise Filter  
Inverter  
Single-phase Noise Filter (Soshin Electric)  
Model 3G3EV-  
Inverter  
capacity (kVA)  
Model 3G3EV-  
Rated voltage Rated current  
Weight (kg)  
(V)  
(A)  
PNF3007C-YN  
460 VAC  
7
Approx. 1.0  
A4002(M)-CUE  
A4004(M)-CUE  
A4007(M)-CUE  
A4015(M)-CUE  
0.9  
1.4  
2.6  
3.7  
4-6  
Specifications  
Chapter 4  
H Dimensions  
D 3G3EV-PNF3006A-YN/-PNF3010A-YN  
5.0 dia.  
84 1  
118 1  
128 2  
4-7  
Specifications  
Chapter 4  
D 3G3EV-PNF2003A-YN/-PNF2010A-YN  
Two, 5.0 dia.  
4-8  
Specifications  
Chapter 4  
D 3G3EV-PNF2020A-YN  
5.0 dia.  
5
93 1  
118 1  
128 2  
4-9  
Specifications  
Chapter 4  
D 3G3EV-PNF3007C-YN  
Four, 5.0 dia.  
95 2  
118 1  
128 2  
4-10  
Index  
A–C  
M
magnetic contactor, main circuit  
input side, 3-15  
output side, 3-17  
AC reactor, main circuit, input side, 3-15  
cables, length, main circuit, 3-18  
cautions, wiring, 3-6  
main circuit  
clamp core, main circuit, 3-13  
connection diagrams, 3-10  
input terminals, 3-8  
output terminals, 3-8  
terminal connections, 3-10  
wiring, 3-11  
constant settings, warning, 1-3  
control circuit  
MCCB, main circuit, 3-14  
analog output terminals, 3-10  
input terminals, 3-9  
output terminals, 3-9, 3-10  
terminal connections, 3-11  
wiring, 3-19  
models, list, 1-2, 2-2  
molded-case circuit breaker. See MCCB  
N–R  
nameplate, 1-2  
D
Noise Filters, main circuit, 3-12  
output side, 3-16, 3-17  
dielectric strength test, warning, 1-3  
Digital Operator  
mounting, 3-21  
warning, 1-3  
nomenclature  
Digital Operator, 2-5  
Inverter, 2-4  
dimensions  
Inverter, 3-2  
Noise Filter, 4-7  
phase advance capacitor, main circuit, output side, 3-16  
precautions, 1-3  
radio noise, main circuit, output side, 3-17  
residual voltage, warning, 1-3  
E–H  
electromagnetic switch, main circuit, output side, 3-17  
S
EMC Directives, conformance, 2-3  
Noise Filters, 3-12  
sequential input  
control circuit, wiring, 3-19  
selection, 3-22  
frequency reference  
input, selection, 3-22  
wiring, control circuit, 3-21  
signals, warning, 1-3  
ground, wiring, main circuit, 3-18  
ground fault interrupter, main circuit, input side, 3-15  
heat sink, 1-3  
solderless terminals, round, control circuit, 3-20  
specifications  
Inverter, 4-2  
Noise Filter, 4-6  
surge absorber, main circuit, input side, 3-15  
I–L  
installation, 3-4  
conditions, 3-4  
orientation, 3-4  
space, 3-4  
T
temperature, 3-5  
terminals, 3-7  
Low-voltage Directives. See LVD Directives  
control circuit, 3-9  
main circuit, 3-8  
LVD Directives, conformance, 2-3  
MCCB, 3-14  
thermal relay, main circuit, output side, 3-17  
I-1  
Index  
wires  
frequency reference input, 3-21  
W
warnings, 1-3  
sequential input, 3-19  
constant settings, modifying, 1-3  
dielectric strength test, 1-3  
Digital Operator, 1-3  
heat sink, 1-3  
sizes, control circuit, 3-21  
solderless terminals, 3-20  
residual voltage, 1-3  
signals, modifying, 1-3  
wiring, 3-6  
wiring  
caution, 3-6  
modifying, 1-3  
warning, 1-3, 3-6  
I-2  
Revision History  
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.  
Cat. No. I521-E1-04  
Revision code  
The following table outlines the changes made to the manual during each revision. Page numbers refer to the  
previous version.  
Revision code  
Date  
Revised content  
1
2
April 1997  
Original production  
November 1997  
Information on new models added throughout the manual.  
Page 1-2: Model number description changed.  
Page 2-2: Table of available models changed. Note in Required Conditions  
corrected.  
Page 3-3: Three-phase 400-VAC input models added.  
Page 3-5: Warning to connect the ground to the supply neutral added for the  
400-VAC models.  
Page 3-7: Descriptions of terminals changed.  
Page 3-8: Information added above the table for the input terminals.  
Pages 3-9, 3-11: Changes to the diagram made to include the 400-VAC mod-  
els. Note added also.  
Page 3-10: Information added to the frequency reference input of the control  
circuit diagram. Wire size table changed. Note added also.  
Page 3-11: Information added to the beginning of Wiring Power Supply. Noise  
filter table changed.  
Page 3-12: LVD conformance table changed.  
Page 3-13: Braking Resistor Unit information removed from Installing a Mag-  
netic Contactor. Information added to Installing an AC Reactor. A section on  
wiring a Braking Resistor/Braking Resistor Unit has been added.  
Page 3-15: Ground resistance information added to Ground Wiring.  
Page 3-18: A section on the tightening torque of control circuit terminals  
added.  
Page 4-2: Ratings changed.  
Page 4-3: Information on 400-VAC models added to the overvoltage and volt-  
age drop descriptions in Protection Functions.  
Page 4-5: Noise Filter tables changed. New Noise Filter dimensions added.  
3
November 1998  
September 2005  
Models with the special specification “-CE” have been removed throughout the  
manual. Information on new three-phase, 200-VAC models added throughout the  
manual.  
Page 2-3, 3-7, 3-11, 4-6: Note on the unavailability of noise filter that conforms  
to EC Directives removed.  
Page 4-3: Applicable standards added to General Specifications.  
Page 4-7: 3G3EV-PNF3006A-YN/-PNF3010A-YN dimensions added.  
Following changes made to front matter.  
04  
General precautionary notes added to the first page.  
Notice: Information on general precautions notation added.  
Read and Understand this Manual: Information on liability and warranty added.  
R-1  

相关型号:

3G3EV-A4004

Compact Low-noise Inverter
OMRON

3G3EV-A4004-CUE

EC Directives Models)
OMRON

3G3EV-A4004M

Compact Low-noise Inverter
OMRON

3G3EV-A4004M-CE179875

INVERTER AC 0.4KW
ETC

3G3EV-A4004M-CUE

EC Directives Models)
OMRON

3G3EV-A4007

Compact Low-noise Inverter
OMRON

3G3EV-A4007-CUE

EC Directives Models)
OMRON

3G3EV-A4007M

Compact Low-noise Inverter
OMRON

3G3EV-A4007M-CE179887

INVERTER AC 0.7KW
ETC

3G3EV-A4007M-CUE

EC Directives Models)
OMRON

3G3EV-A4015

Compact Low-noise Inverter
OMRON

3G3EV-A4015-CUE

EC Directives Models)
OMRON