DS150D6S [MTU]
DIESEL GENERATOR SET;型号: | DS150D6S |
厂家: | MTU ONSITE ENERGY CORPORATION |
描述: | DIESEL GENERATOR SET |
文件: | 总4页 (文件大小:535K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
DIESEL GENERATOR SET
DS150D6S
/
/
150 kWe 60 Hz Standby
208 - 600V
(Reference DP135D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
DS150D6SGA
DS150D6SDA
DS150D6SPA
DS150D6SJA
DS150D6SRA
DS150D6SNA
Voltage (L-L)
Phase
240V**
1
240V**
1
208V**
3
240V**
3
480V**
3
600V**
3
PF
1.0
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
60
kW
kVA
Amps
150
150
625
150
150
625
150
187.5
520
150
187.5
451
150
187.5
226
150
187.5
180
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
182
195
296
296
394
315
431CSL6208
130 °C/40 °C
12 LEAD ZIG-ZAG
431PSL6224
130 °C/40 °C
4 LEAD
431CSL6202
130 °C/40 °C
12 LEAD LOW WYE
431CSL6202
130 °C/40 °C
12 LEAD HI DELTA
431CSL6202
130 °C/40 °C
12 LEAD HI WYE
431PSL6240
130 °C/40 °C
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Emissions – EPA Tier 3 Certified
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
- Verified product design, quality and performance integrity
ISO 14001:2004
- All engine systems are prototype and factory tested
//ꢀ
//ꢀ
Seismic Certification – Optional
Power Rating
– IBC Certification
- Accepts Rated Load in One Step Per NFPA 110
– OSHPD Pre-Approval
//ꢀ
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
/ // ꢀ/
2
DS150D6S
STANDARD FEATURES*
//ꢀ
//ꢀ
//ꢀ
//ꢀ
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
6068HF285 Diesel Engine
- 6.8 Liter Displacement
- 4-Cycle
Engine-generator resilient mounted
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
//ꢀ
//ꢀ
//ꢀ
//ꢀ
//ꢀ
Complete Range of Accessories
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT*
//ꢀ
Engine
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Air Cleaner
Oil Pump
Flexible Coupling
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Full Amortisseur Windings
125% Rotor Balancing
Fuel Filter with Water Separator
Jacket Water Pump
Thermostat
3-Phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electronic Isochronous
Base - Formed Steel
//ꢀ
Digital Control Panel(s)
Digital Metering
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
16 Programmable Contact Inputs
Up to 11 Contact Outputs
//ꢀ
Generator
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
/ // ꢀ/
3
DS150D6S
APPLICATION DATA
//ꢀ
//ꢀ
Engine
Fuel Consumption
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
John Deere
6068HF285
4-Cycle
6-Inline
6.8 (415)
10.6 (4.19)
12.7 (5)
19:1
1,800
JDEC
177 (237)
±0.25%
Dry
STANDBY
44.7 (11.8)
34.8 (9.2)
25.4 (6.7)
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
//ꢀ
Cooling - Radiator System
STANDBY
50 (122)
Ambient Capacity of Radiator: °C (°F)
Maximum Allowable Static
Pressure on Rad. Exhaust: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM )
Heat Rejection to Air to Air: kW (BTUM )
Heat Radiated to Ambient: kW (BTUM )
Fan Power: kW (hp)
0.12 (0.5)
180 (48)
93.5 (5,324)
32 (1,821)
25.7 (1,461)
10.7 (14.3)
//ꢀ
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
20 (5.28)
12.3 (3.25)
22.7 (6)
//ꢀ
Air Requirements
STANDBY
13.6 (480)
//ꢀ
Electrical
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
12
925
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
304 (10,732)
94 (3,295)
//ꢀ
Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
3/8” NPT
3/8” NPT
2 (6.7)
Diesel #2
107.2 (28.3)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
//ꢀ
Exhaust System
Total Fuel Flow: L/hr (gal/hr)
STANDBY
505 (941)
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
34 (1,201)
7.5 (30)
Maximum Allowable
Back Pressure: kPa (in. H20)
/ // ꢀ/
4
DS150D6S
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Dimensions (LxWxH)
Weight (less tank)
OPU
2,845 x 1,219 x 1,283 mm (112 x 48 x 50.5 in)
1,592 kg (3,510 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Standby Full Load
Level 0: Open Power Unit dB(A)
85.1
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//ꢀ
NOx + NMHC
2.6
CO
0.8
PM
0.09
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value from each
engine is guaranteed to be below the US EPA Standards at the
US EPA defined conditions.
//ꢀ
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
相关型号: