3250-XC6DT2-STANDBY [MTU]

DIESEL GENERATOR SET;
3250-XC6DT2-STANDBY
型号: 3250-XC6DT2-STANDBY
厂家: MTU ONSITE ENERGY CORPORATION    MTU ONSITE ENERGY CORPORATION
描述:

DIESEL GENERATOR SET

文件: 总4页 (文件大小:294K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
DIESEL GENERATOR SET  
3250-XC6DT2  
/
/
3250 kWe 60 Hz Standby  
480 - 13.8kV  
SYSTEM RATINGS  
Standby  
Voltage (L-L)  
Phase  
480V**  
3
600V  
3
4160V  
3
12470V  
3
13200V  
3
13800V  
3
PF  
0.8  
0.8  
0.8  
0.8  
0.8  
0.8  
Hz  
60  
60  
60  
60  
60  
60  
kW  
kVA  
Amps  
3250  
4062.5  
4887  
3250  
4062.5  
3909  
3250  
4062.5  
564  
3250  
4062.5  
185  
3250  
4062.5  
175  
3250  
4062.5  
167  
skVA@30%  
Voltage Dip  
Generator Model*  
Temp Rise  
5500  
1030FDL1110  
130 °C/40 °C  
6125  
1030FDS1128  
130 °C/40 °C  
6300  
1030FDM1188  
130 °C/40 °C  
6300  
1040FDH1256  
130 °C/40 °C  
6850  
1040FDH1256  
130 °C/40 °C  
7400  
1040FDH1256  
130 °C/40 °C  
Connection  
6 LEAD WYE  
6 LEAD WYE  
6 LEAD WYE  
6 LEAD WYE  
6 LEAD WYE  
6 LEAD WYE  
* Consult the factory for alternate conguration.  
** UL 2200 Oered  
CERTIFICATIONS AND STANDARDS  
//  
//ꢀ  
Emissions – EPA Tier 2 Certied  
Performance Assurance Certification (PAC)  
- Generator Set Tested to ISO 8528-5 for Transient Response  
- Veried product design, quality and performance integrity  
- All engine systems are prototype and factory tested  
//ꢀ  
Generator set is designed and manufactured  
in facilities certied to standards ISO 9001:2008 and  
ISO 14001:2004  
//ꢀ  
Power Rating  
//ꢀ  
UL 2200 Listed – Optional  
- Accepts Rated Load in One Step Per NFPA 110  
- Permissible average power output during 24 hours of  
operation is approved up to 85%.  
/ // /  
2
3250-XC6DT2  
STANDARD FEATURES*  
//ꢀ  
//ꢀ  
MTU Onsite Energy is a single source supplier  
Global Product Support  
2 Year Standard Warranty  
20V 4000 Diesel Engine  
- 95.4 Liter Displacement  
- Common Rail Fuel Injection  
- 4-Cycle  
Generator  
- Brushless, Rotating Field Generator  
- 2/3 Pitch Windings  
- PMG (Permanent Magnet Generator) supply to regulator  
- 300% Short Circuit Capability  
Digital Control Panel(s)  
- UL Recognized, CSA Certied, NFPA 110  
- Complete System Metering  
- LCD Display  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
//ꢀ  
Complete Range of Accessories  
Cooling System  
- Integral Set-Mounted  
- Engine Driven Fan  
STANDARD EQUIPMENT*  
//ꢀ  
Engine  
Air Cleaners  
Oil Pump  
Oil Drain Extension & S/O Valve  
Full Flow Oil Filter  
Closed Crankcase Ventilation  
Jacket Water Pump  
No Load to Full Load Regulation  
Brushless Alternator with Brushless Pilot Exciter  
4 Pole, Rotating Field  
130 °C Maximum Standby Temperature Rise  
2 Bearings, Sealed  
Flexible Coupling  
Inter Cooler Water Pump  
Thermostats  
Full Amortisseur Windings  
125% Rotor Balancing  
Blower Fan & Fan Drive  
Radiator - Unit Mounted  
Electric Starting Motor - 24V  
Governor – Electronic Isochronous  
Base - Structural Steel  
SAE Flywheel & Bell Housing  
Charging Alternator - 24V  
Battery Box & Cables  
Flexible Fuel Connectors  
Flexible Exhaust Connection  
EPA Certied Engine  
3-Phase Voltage Sensing  
±0.25% Voltage Regulation  
5% Maximum Total Harmonic Distortion  
//ꢀ  
Digital Control Panel(s)  
Digital Metering  
Engine Parameters  
Generator Protection Functions  
Engine Protection  
CAN Bus ECU Communications  
Windows®-Based Software  
Multilingual Capability  
//ꢀ  
Generator  
Remote Communications to RDP-110 Remote Annunciator  
16 Programmable Contact Inputs  
Up to 11 Contact Outputs  
NEMA MG1, IEEE and ANSI standards compliance for temperature rise  
and motor starting  
Sustained short circuit current of up to 300% of the rated current for  
up to 10 seconds  
UL Recognized, CSA Certied, CE Approved  
Event Recording  
Self-Ventilated and Drip-Proof  
Superior Voltage Waveform  
IP 54 Front Panel Rating with Integrated Gasket  
NFPA110 Compatible  
Digital, Solid State, Volts-per-Hertz Regulator  
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional congurations.  
/ // /  
3
3250-XC6DT2  
APPLICATION DATA  
//ꢀ  
//ꢀ  
Engine  
Fuel Consumption  
Manufacturer  
Model  
Type  
Arrangement  
Displacement: L (in3)  
Bore: cm (in)  
MTU  
STANDBY  
844 (223)  
644 (170)  
447 (118)  
20V 4000 G83L 6 ECT  
At 100% of Power Rating: L/hr (gal/hr)  
At 75% of Power Rating: L/hr (gal/hr)  
At 50% of Power Rating: L/hr (gal/hr)  
4-Cycle  
20-V  
95.4 (5,822)  
17 (6.69)  
//ꢀ  
Stroke: cm (in)  
Compression Ratio  
Rated RPM  
21 (8.27)  
16.4:1  
Cooling - Radiator System  
1,800  
STANDBY  
43 (108)  
Engine Governor  
Maximum Power: kWm (bhp)  
Speed Regulation  
Air Cleaner  
Electronic Isochronous (ADEC)  
Ambient Capacity of Radiator: °C (°F)  
Maximum Restriction of Cooling Air, Intake,  
and Discharge Side of Rad.: kPa (in. H20)  
Water Pump Capacity: L/min (gpm)  
After Cooler Pump Capacity: L/min (gpm)  
Heat Rejection to Coolant: kW (BTUM)  
Heat Rejection to After Cooler: kW (BTUM)  
Heat Radiated to Ambient: kW (BTUM)  
Fan Power: kW (hp)  
3,490 (4,678)  
±0.25%  
0.12 (0.5)  
1,567 (414)  
567 (150)  
1,300 (73,929)  
970 (55,163)  
237 (13,472)  
60.6 (81.3)  
Dry  
//ꢀ  
Liquid Capacity (Lubrication)  
Total Oil System: L (gal)  
390 (103)  
205 (54.2)  
30 (7.9)  
Engine Jacket Water Capacity: L (gal)  
After Cooler Water Capacity: L (gal)  
System Coolant Capacity: L (gal)  
//ꢀ  
860 (227)  
Air Requirements  
STANDBY  
264 (9,323)  
Aspirating: *m3/min (SCFM)  
Air Flow Required for Rad.  
//ꢀ  
Electrical  
Electric Volts DC  
Cold Cranking Amps Under -17.8 °C (0 °F)  
24  
4,200  
Cooled Unit: *m3/min (SCFM)  
Remote Cooled Applications;  
Air Flow Required for Dissipation  
of Radiated Gen-set Heat for a  
Max of 25 °F Rise: *m3/min (SCFM)  
3,082 (108,843)  
866 (30,384)  
//ꢀ  
Fuel System  
Fuel Supply Connection Size  
Fuel Return Connection Size  
#16 JIC 37° Female  
1” NPT Adapter Provided * Air density = 1.184 kg/m3 (0.0739 lbm/ft3)  
#16 JIC 37° Female  
//ꢀ  
1” NPT Adapter Provided  
1 (3)  
Exhaust System  
Maximum Fuel Lift: m (ft)  
Recommended Fuel  
Total Fuel Flow: L/hr (gal/hr)  
Diesel #2  
1,620 (428)  
STANDBY  
525 (977)  
Gas Temp. (Stack): °C (°F)  
Gas Volume at Stack  
Temp: m3/min (CFM)  
702 (24,791)  
8.5 (34.1)  
Maximum Allowable  
Back Pressure: kPa (in. H20)  
/ // /  
4
3250-XC6DT2  
WEIGHTS AND DIMENSIONS  
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website  
for unit specic template drawings.  
System  
Dimensions (LxWxH)  
Weight (less tank)  
OPU  
7,766 x 3,099 x 3,569 mm (305.75 x 122 x 140.5 in)  
29,651 kg (65,369 lb)  
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specic generator set.  
SOUND DATA  
Unit Type  
Standby Full Load  
Level 0: Open Power Unit dB(A)  
95.1  
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with innite exhaust.  
EMISSIONS DATA  
RATING DEFINITIONS AND CONDITIONS  
//ꢀ  
NOx + NMHC  
5.1  
CO  
0.6  
PM  
0.03  
Standby ratings apply to installations served by a reliable  
utility source. The standby rating is applicable to varying  
loads for the duration of a power outage. No overload  
capability for this rating. Ratings are in accordance with  
ISO 8528-1, ISO 3046-1, BS 5514, AS 2789, and DIN 6271.  
Deration Factor:  
Altitude: Consult your local MTU Onsite Energy Power  
Generation Distributor for altitude derations.  
Temperature: Consult your local MTU Onsite Energy Power  
Generation Distributor for temperature derations.  
All units are in g/hp-hr and at 100% load.  
Emission levels of the engine may vary as a function of ambient  
temperature, barometric pressure, humidity, fuel type and  
quality, installation parameters, measuring instrumentation,  
etc. The data provided are laboratory results from one  
engine representing this rating. The data was obtained  
under controlled environmental conditions with calibrated  
instrumentation traceable to the United States National Bureau  
of Standards and in compliance with US EPA regulations found  
within 40 CFR Part 89. The weighted cycle value (not shown)  
from each engine is guaranteed to be below the US EPA  
Standards at the US EPA dened conditions.  
//ꢀ  
Materials and specications subject to change without notice.  
C/F = Consult Factory/MTU Onsite Energy Distributor  
MTU Onsite Energy  
A Rolls-Royce Power Systems Brand  
www.mtuonsiteenergy.com  

相关型号:

3250.01MMXP

Electric Fuse, Time Lag Blow, 0.01A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.01MVXP

Electric Fuse, Time Lag Blow, 0.01A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.031MHXP

Electric Fuse, Time Lag Blow, 0.031A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.031MMXP

Electric Fuse, Time Lag Blow, 0.031A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.031MVXP

Electric Fuse, Time Lag Blow, 0.031A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.125MHXP

Electric Fuse, Time Lag Blow, 0.125A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.125MMXP

Electric Fuse, Time Lag Blow, 0.125A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.125MVXP

Electric Fuse, Time Lag Blow, 0.125A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.15MHXP

Electric Fuse, Time Lag Blow, 0.15A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.15MMXP

Electric Fuse, Time Lag Blow, 0.15A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.175MHXP

Electric Fuse, Time Lag Blow, 0.175A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE

3250.175MMXP

Electric Fuse, Time Lag Blow, 0.175A, 250VAC, 100A (IR), Through Hole, ROHS COMPLIANT
LITTELFUSE