125-JC6DT3 [MTU]
DIESEL ENGINE-GENERATOR SET; 柴油机发电机组型号: | 125-JC6DT3 |
厂家: | MTU ONSITE ENERGY CORPORATION |
描述: | DIESEL ENGINE-GENERATOR SET |
文件: | 总4页 (文件大小:423K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
A ꢀogꢁuꢂ gꢃouP BꢃAꢁꢄ
DIESEL ENGINE-GENERATOR SET
125-JC6DT3
/
/
/
/
125 ekW 60 Hz Standby
115 ekW 60 Hz Prime
208 - 600V
SySTEm RATINGS
Standby
Vꢅltaꢆe (L-L)
Phase
240V**
1
240V**
1
208V**
3
240V**
3
480V**
3
600V**
3
PF
1.0
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
60
kW
kVA
AMPS
125
125
521
125
125
521
125
156.25
434
125
156.25
376
125
156.25
188
125
156.25
150
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
136
195
250
250
330
334
431PSL6204
130°C/27°C
12 LEAD ZIG-ZAG
431PSL6224
130°C/27°C
4 LEAD
363CSL1607
130°C/27°C
12 LEAD LOW WYE
363CSL1607
130°C/27°C
12 LEAD HI DELTA
363CSL1607
130°C/27°C
12 LEAD HI WYE
363PSL1658
125°C/40°C
4 LEAD WYE
Prime
Vꢅltaꢆe (L-L)
Phase
240V
1
240V
1
208V
3
240V
3
480V
3
600V
3
PF
Hz
1.0
60
1.0
60
0.8
60
0.8
60
0.8
60
0.8
60
kW
kVA
AMPS
115
115
479
115
115
479
115
138
399
115
143.75
346
115
143.75
173
115
143.75
138
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
136
195
250
250
330
335
431PSL6204
105°C/40°C
12 LEAD ZIG-ZAG
431PSL6224
105°C/40°C
4 LEAD
363PSL1607
105°C/40°C
12 LEAD LOW WYE
363PSL1607
105°C/40°C
12 LEAD HI DELTA
363PSL1607
105°C/40°C
12 LEAD HI WYE
363PSL1658
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
/ // /
2
125-JC6ꢄꢀ3
FACTS
//
//
//
EPA Tier 3 Certified
Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
Complete Range of Accessories
Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
//
//
//
//
//
//
//
//
//
UL2200, CSA Listing Offered
- 300% Short Circuit Capability
- 2/3 Pitch Windings
Digital Control Panel(s)
Accepts Rated Load in One Step Per NFPA 110, Level 1
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
Custom Design for Any Application
6068HF285 Diesel Engine
//
//
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
- 6.8 Liter Displacement
- 4-Cycle
STANDARD EQUIPmENT
//
Enꢆine
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
Air Cleaners
Oil Pump
Full Flow Oil Filter
130°C Standby Temperature Rise
1 Bearing, Sealed
Jacket Water Pump
Flexible Coupling
Thermostat
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±1% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electric Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//
ꢄiꢆital Cꢅntrꢅl Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
//
generatꢅr
Multilingual Capability
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
Event Recording
, CE Approved
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
/ // /
3
125-JC6ꢄꢀ3
APPLICATION DATA
//
//
Enꢆine
Fꢇel Cꢅnsꢇmptiꢅn
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
John Deere
6068HF285
4-Cycle
6 In-Line
415 (6.8)
4.19 (10.6)
5 (12.7)
19:1
STANDBY
At 100% of Power Rating: gal/hr (lit/hr) 8.9 (33.7)
PRIME
8 (30.3)
6.2 (23.5)
4.5 (17)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
6.9 (26.1)
5 (18.9)
//
Cꢅꢅlinꢆ - ꢃadiatꢅr System
1,800
STANDBY
PRIME
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
JDEC
Ambient Capacity of Radiator: °F (°C)
Maximum Allowable Static
Pressure on Rad. Exhaust: in. H20 (kPa) 0.5 (0.12)
Water Pump Capacity: gpm (lit/min)
122 (50)
122 (50)
237 (177)
216 (161)
±.25%
0.5 (0.12)
48 (180)
48 (180)
Frequency
60 Hz
Heat Rejection to Coolant: BTUM (kW)
5,324 (93.5) 4,792 (84.3)
Air Cleaner
Dry
Heat Rejection to Air to Air: BTUM (kW) 1,821 (32)
1,702 (30)
815 (14.3)
Heat Radiated to Ambient: BTUM (kW)
922 (16.2)
//
Liqꢇid Capacity (Lꢇbricatiꢅn)
//
Air ꢃeqꢇirements
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
5.28 (20)
3.25 (12.3)
6 (22.7)
STANDBY
480 (13.6)
PRIME
452 (12.8)
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
17,712 (502) 17,712 (502)
//
Electrical
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
Electric Volts DC
12
2,080 (59)
1,837 (52)
Cold Cranking Amps Under 0°F (-17.8°C)
800
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//
//
Fꢇel System
Exhaꢇst System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
28.3 (107.2)
STANDBY
PRIME
916 (491)
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
941 (505)
1,201 (34)
30 (7.5)
1,165 (33)
30 (7.5)
Total Fuel Flow: gal/hr (lit/hr)
Back Pressure: in. H20 (kPa)
/ // /
4
125-JC6ꢄꢀ3
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
System
ꢄimensiꢅns (LxWxH)
Weiꢆht (less tank)
OPU
105 x 36 x 52 in (2,670 x 910 x 1,320 mm)
2,821 lb (1,280 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
unit ꢀype
Standby Fꢇll Lꢅad
Standby ꢁꢅ Lꢅad
Prime Fꢇll Lꢅad
Prime ꢁꢅ Lꢅad
OPU w/Critical Grade Muffler (dBA)
Sound Attenuated Enclosure (dBA)
Measurements for sound data are taken at 23 ft (7 m).
91.5
83.5
84
76
90
82
84
76
EmISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
//
ꢁox + ꢁꢂHC
Co
Pꢂ
Ambient capability factor at 984 ft (300 m). Consult your
2.65
0.98
0.13
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capa-
bility for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
//
All ꢇnits are in ꢆ/hp-hr and are EPA ꢄ2 cycle valꢇes.
Emission levels of the engine may vary as a function of ambi-
ent temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one engine
representing this rating. The data was obtained under cont-
rolled environmental conditions with calibrated instrumentation
traceable to the United States National Bureau of Standards
and in compliance with US EPA regulations found within 40 CFR
Part 89. The weighted cycle value from each engine is guaran-
teed to be below the US EPA Standards at the US EPA defined
conditions.
//
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO-8528/1, overload power in accordance
with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For
limited running time and base load ratings, consult the
factory.
//
Deration Factor:
Altitꢇde: 0.5% per 1,000 ft (305 m) above 5,000 ft (1,524 m)
and 4% per 1,000 ft (305 m) above 10,000 ft (3,048 m).
ꢀemperatꢇre: 0.5% per 10°F (5.5°C) above 77°F (25°C).
Materials and specifications subject to change without notice.
// ꢀꢅꢆnꢇm grꢅꢇp Cꢅmpanies: Eꢇrꢅpe / ꢂiddle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com // uSA / Canada / ꢂexicꢅ / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com // Wꢅrldwide fꢅr Hꢅtꢂꢅdꢇle / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com
相关型号:
125-R309-FT
Fixed Resistor, Wire Wound, 1.5W, 0.309ohm, 55V, 1% +/-Tol, 90ppm/Cel, Through Hole Mount, AXIAL LEADED
RCD
©2020 ICPDF网 联系我们和版权申明