W2XF-S2V3Z1-R [MSYSTEM]
Space-saving Dual Output Signal Conditioners Mini-MW Series;型号: | W2XF-S2V3Z1-R |
厂家: | M-SYSTEM |
描述: | Space-saving Dual Output Signal Conditioners Mini-MW Series |
文件: | 总4页 (文件大小:115K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: W2XF
(Configurator software is used to change the input type and
precise range.)
Space-saving Dual Output Signal Conditioners
Mini-MW Series
[2] OUTPUT 1
Current
LINEARIZER
(PC programmable)
Z1: Range 0 – 20 mA DC
Voltage
Functions & Features
• Accepting non-linear input and providing a linearized
output, proportional to the process variables
• 101-point calibration
V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC
• PC programmable
• High-density mounting
[3] OUTPUT 2
Same range availability as Output 1
Typical Applications
Y: None
• V-notch weir
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)
• Gas analyzer
• Irregular-shaped tank level input for volume calculation
• Square root extracting for DP transmitter
[4] POWER INPUT
29.5 (1.16)
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
88.5
(3.48)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
124
(4.88)
[5] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N: Without CE
mm (inch)
Other Options
MODEL: W2XF–[1][2][3]-[4][5]
blank: none
/Q: Option other than the above (specify the specification)
ORDERING INFORMATION
• Code number: W2XF-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. W2XF-S2Z1V3-M2/N/Q)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Input range (e.g. 1 – 5 V DC)
/C02: Polyurethane coating
• Output 1 range (e.g. 4 – 20 mA DC)
• Output 2 range (e.g. 1 – 5 V DC)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
EX-FACTORY SETTING
Note: If one of the outputs should be a current range,
specify it for the Output 1 to allow a greater load.
/SET: Preset according to the Ordering Information Sheet
(No. ESU-5507)
[1] INPUT
Current
RELATED PRODUCTS
• PC configurator software (model: W2CFG)
Z1: Range 0 – 50 mA DC (Input resistance 24.9 Ω)
Voltage
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
S1: Range -1 – +1 V DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
W2XF SPECIFICATIONS
ES-5507 Rev.4 Page 1/4
http://www.m-system.co.jp/
MODEL: W2XF
cable types.
maintained.
Load resistance: Output drive 12 V max. for Output 1; 7 V
max. for Output 2
GENERAL SPECIFICATIONS
Construction: Plug-in
(e.g. 4 – 20 mA: 600 Ω [12 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
Code V2 (wide spans)
Operational range: -11.5 – +11.5 V DC
Minimum span: 1 V
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Overrange output: -15 to +115 %
Code V3 (narrow spans)
Operational range: -6 – +6 V DC
Minimum span: 0.5 V
(Negative current output is not available.)
Zero adjustment: -5 to +5 % (PC programming)
Span adjustment: 95 to 105 % (PC programming)
Programming: Downloaded from PC; input range, output
range, zero and span,
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V2: 0 – 10 V DC
response time, linearization table, simulating output, etc.
Linearization: 101 points max. within the range of
-15 – +115 % input or output; represented as percentage of
full-scale (No table setting is done at shipping. [gain = 1])
Status indicator LED: Tri-color (green/amber/red) LED;
Blinking patterns indicate operation status of the
transmitter.
V3: 1 – 5 V DC
INSTALLATION
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
Power Consumption
•AC:
Approx. 5 VA at 100 V
Approx. 6 VA at 200 V
INPUT SPECIFICATIONS
■ DC Current: Input resistor incoporated
(If not specified, the input range is 4 – 20 mA DC.)
Input range: 0 – 50 mA DC
Approx. 7 VA at 264 V
•DC: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)
Minimum span: 2 mA
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
■ DC Voltage
Code S1 (narrow spans)
PERFORMANCE in percentage of span
Overall accuracy:
Input range: -1 – +1V DC
Minimum span: 100 mV
Input accuracy + output accuracy [gain ≤ 1]
(inp. accuracy + out. accuracy) × gain [gain > 1]
Inversely proportional to the span.
See CALCULATION EXAMPLES OF OVERALL ACURACY.
• Input accuracy: (% of max. input range)
-1 – +1 V : ±0.01 %
Code S2 (wide spans)
Input range: -10 – +10 V DC
Minimum span: 1 V
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
S1: 0 – 100 mV DC
-10 – +10 V : ±0.01 %
0 – 50 mA : ±0.02 %
S2: 1 – 5 V DC
• Output accuracy: ±0.04 % of max. output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
at -5 to +55°C [23 to 131°F]
OUTPUT SPECIFICATIONS
■ DC Current
Response time: (0 – 90 %)
Standard: ≤ 500 msec.
Operational range: 0 – 23 mA DC
Minimum span: 1 mA
Fast: ≤ 25 msec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
W2XF SPECIFICATIONS
ES-5507 Rev.4 Page 2/4
http://www.m-system.co.jp/
MODEL: W2XF
Dielectric strength: 2000 V AC @1 minute (input to output
1 to output 2 to power to ground)
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Type -10 – +10 V, Input Range 1 – 5 V,
Output Type 0 – 20 mA, Output Range 4 – 20 mA
Max. Input Range (20 V) ÷ Span (4 V) × 0.01 % = 0.05 %
Max. Output Range (20 mA) ÷ Span (16 mA) × 0.04 %
= 0.05 %
Overall accuracy = 0.05 + 0.05 = ±0.10 %
EXTERNAL VIEW
FRONT VIEW
SIDE VIEW
LED1 (LD1)
Output 1
Configuration DIP SW
LED2 (LD2)
1 2 3 4
ON
LED3 (LD3)
OFF
Configurator Jack
Output 2
Configuration DIP SW
1 2 3 4
ON
*
SW2
SW1
OFF
*Provided only for two-output type.
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
6 (.23)
DIN RAIL
35mm wide
3
2
5
1
4
6
2–
4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
9
8
7
11–M3
SCREW
11 10
22 (.87)
29.5 (1.16)
21.5 (.87) 10 (.39)
84 (3.31)
114 (4.49)
[4 (.16)]
• When mounting, no extra space is needed between units.
W2XF SPECIFICATIONS
ES-5507 Rev.4 Page 3/4
http://www.m-system.co.jp/
MODEL: W2XF
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
DIP SW
Isolation
24.9Ω
+
Output
Driver
+
–
1
7
8
CURRENT
(Z1)
OUTPUT 1
–
Digital
Computation
Circuit
Low Drift
Amplifier
2
–
VOLTAGE
(S1, S2)
DIP SW
Isolation
5
+
Output
Driver
+
3
6
OUTPUT 2
POWER
4
–
9
U(+)
V(–)
10
11
CONFIGURATOR
JACK
Base Socket
Remark: The section enclosed by broken line is only with 2nd output option.
Specifications are subject to change without notice.
W2XF SPECIFICATIONS
ES-5507 Rev.4 Page 4/4
http://www.m-system.co.jp/