SC200-12-R/300 [MSYSTEM]
Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER;型号: | SC200-12-R/300 |
厂家: | M-SYSTEM |
描述: | Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER |
文件: | 总12页 (文件大小:530K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: SC200
Language
Single Loop Controller Series
blank: Japanese
/E: English
MULTI-FUNCTION PID CONTROLLER
(color LCD with touch-panel, Modbus/NestBus
communication)
(Language (Japanese or English) can be chosen by front
panel setting.)
Configurator Interface
blank: Infrared
/1: Stereo jack
(If external noise interference is a concern, stereo jack
type is recommended.)
Terminal block
blank: One block terminal
/T: Separable terminal
144
(5.67)
Other Options
*
mm (inch)
blank: none
/Q: Option other than the above (specify the specification)
*Selectable with option code
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
MODEL: SC200–[1][2]–[3][4]
/C02: Polyurethane coating
ORDERING INFORMATION
• Code number: SC200-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. SC200-11-M2/3/E/1/T/Q)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Specify the specification for option code /Q
(e.g. /C01/S01)
FUNCTIONS & FEATURES
Functions & Features
• Color LCD with touch panel
[1] DISCRETE OUTPUT
1: Relay contact
• Five Operation views (digital display, bargraph, dual-loop
bargraph, short trend and user's parameter table views)
• Enhanced screen functions for engineering (configuration,
programming and tuning views)
2: Photo MOSFET relay
[2] MODBUS
1: Modbus-RTU
2: Modbus/TCP
• Universal input x 2 points, analog input x 4 points,
discrete input x 6 points, pulse input x 5 points, high speed
pulse input x 1 point
• Current output (4-20 mA) x 2 points, voltage output (1-5
V) x 2 points, relay or photo-MOSFET relay output x 5 points
• RUN contact output (relay) x 1 point
[3] POWER INPUT
AC Power
• I/O signals can be added with remote I/O modules
connected via NestBus peer-to-peer communication
• Computation cycle selectable between 50 msec. and 3
sec. (control cycle selectable between 1 and 64 times of the
computation cycle)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Two PID function blocks
[4] OPTIONS (multiple selections)
Housing Depth
• Advanced computation and sequence control functions
• Auto-tuning function
blank: 250 mm
• Parameter input and changing with touch panel
• Function parameter setting, list printing and data
downloading/uploading available with Loop Configuration
Builder Software (model: SFEW3E)
/300: 300 mm (Discontinued, select /3)
/400: 400 mm (Discontinued, select /4)
/3: 300 mm
/4: 400 mm
• Short trend export (CSV), display parameter setting,
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 1/12
http://www.m-system.co.jp/
MODEL: SC200
saving and transfer with PC Configurator Software (model:
SCCFG)
Integral time (I): 0.01 to 100 minutes
Derivative time (D): 0.01 to 10 minutes
Auto-tuning: Limit cycle method
• Control and supervision by SCADA software via Modbus
TCP/IP or RTU communication
Alarm: PV high & low, deviation, rate of change
Computation: 48 functions blocks available for arithmetic
operations, time functions, signal selection, limit, alarm and
other functions
• Selectable housing depth for ease of using existing wires
in replacement: 250 mm, 300 mm and 400 mm
• Separable terminal block
Sequence operation: Logic sequence and step sequence
(max. 1068 commands)
Typical Applications
• Replacement of conventional controllers
• Panel operation for small-scale instrumentation
Computation cycle: 50 msec. to 3 sec. (control cycle
selectable among 1, 2, 4, 8, 16, 32 and 64 times of the
computation cycle)
MV output range: -15 - +115 %
RELATED PRODUCTS
Parameter setting: With touch panel or PC (Loop
Configuration Builder Software model: SFEW3E)
Self diagnostics: CPU monitoring with a watchdog timer
RUN contact: OFF in error detected by diagnostic (including
NestBus)
• PC Configurator cable (model: COP-US)
• Loop configuration builder software (model: SFEW3E Ver.
1.40 or later)
• Infrared communication adaptor (model: COP-IRDA)
• PC configurator software (model: SCCFG Ver.1.50 or later)
Builder software and configurator software are
downloadable at M-System’s web site.
Infrared communication: Transmission distance max. 0.2
meter (for use with the COP-IRDA)
Short trend
Storing interval: 1, 2, 5, 10, 20, 30 sec.,
1, 2, 5, 10, 30, 60 min.
ACCESSORIES
• Precision resistor module (model: REM4): 2
Capacity: 400 points (display 200 points)
• Cold junction sensor: 2
• Mounting brackets: 2
■ Display
• Connector adapter: 1
Display device: 4.3-inch TFT LCD
(included in Stereo jack type. The jack on the unit and the
plug of PC Configurator cable (not included in the product)
are different in size.)
Display colors: 256
Resolution: 480 × 272 pixels
Pixel pitch: 0.198 × 0.198 mm (128 × 128 DPI)
Backlight: LED
Backlight life: Approx. 50 000 hours (at 50 % brightness)
Note: The backlight can be replaced in M-System factory.
The LCD must be replaced at the same time.
Screen saver standby time: 1 to 99 minutes
Scaling range: -32000 to +32000
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Degree of protection: IP55; ensured for the front panel of
the unit independently mounted to a panel
Connection
Decimal point position: 10-1, 10-2, 10-3, 10-4, 10-5 or none
Scale divisions: 2 to 10
Terminal screws: M3.5 screw terminals (torque 1.0 N·m)
Terminal fixing screws: M4 screw terminals
(torque 1.2 N·m)
Engineering unit indication: Max. 8 characters
Auto/Man indicator: Green/Amber LED
Ethernet: RJ-45 Modular Jack
Screw terminal
Terminal screws: Nickel-plated steel (standard) or stainless
steel
Terminal fixing screws: Chrome-plated steel
Housing material: Flame-resistant resin (gray), steel
Isolation: Pv1 to Pv2 to supply output to Ai1 or Ai2 or Ai3 or
Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or
Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 to Ao1 or Ao2 to Do1
to Do2 to Do3 to Do4 to Do5 to Do6 to NestBus to Modbus-
RTU to Modbus/TCP to power to FG
PID control: Single loop, cascade, advanced
Proportional band (P): 1 to 1000 %
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 2/12
http://www.m-system.co.jp/
MODEL: SC200
Protocol: Modbus/TCP
Data: RTU (binary)
Connections: 2
FACTORY DEFAULT
■ LOOP 1
P : 100%
I : No integral action
D : No derivative action
Transmission media:
CAS
10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length: 100 meters
Port number: 502
H
L
PID
G02
SEQ
G81
Reverse Action
Ai 1
Pv 1
Mv 1
(PV /MV
)
1
1
*
*
1 – 5 V DC
IP address: 192.168.0.1 (factory setting)
1 – 5 V DC
4 – 20 mA DC
AL1
AL2
SUPPLY OUTPUT
Output voltage:
■ LOOP 2
P : 100%
: No integral action
D : No derivative action
24 V DC ±10 % with no load
18 V DC min. at 20 mA
Current rating: ≤ 22 mA DC
∙Shortcircuit protection
Current limited: Approx. 30 mA
I
CAS
H
L
PID
G03
SEQ
G81
Reverse Action
Ai 2
Pv 2
Mv 2
(PV /MV
)
1
1
*
*
1 – 5 V DC
1 – 5 V DC
4 – 20 mA DC
INPUT SPECIFICATIONS
■ Pv1, Pv2 (universal input)
AL3
AL4
∙Current input: 4 – 20 mA DC with input resistance 250 Ω
(REM4)
*1. Factory default setting
Use Loop Configuration Builder Software (model: SFEW3E)
to modify setting.
∙Voltage input: -10 – +10 V DC
-1 – +1 V DC
0 – 10 V DC
EXTERNAL INTERFACE
■ NestBus
1 – 5 V DC
0 – 1 V DC
Configuration: Bus type multi-drop
Standard: Conforms to TIA/EIA-485-A
Transfer rate: 19.2 kbps
Input resistance: ≥ 1 MΩ
∙Thermocouple input: K, E, J, T, B, R, S, C, N, U, L, P, PR (See
Table 1)
Protocol: NestBus (M-System’s own protocol)
Max. transmission distance: 1 kilometer
Transmission media:
Input resistance: ≥ 30 kΩ
Burnout sensing: ≤ 0.3 µA
Burnout indication: 115 % of the measuring range (upscale)
∙RTD input: Pt100 (JIS ’97, IEC), Pt100 (JIS ’89), JPt100 (JIS
’89), Pt50Ω (JIS ’81), Ni100 (See Table 2)
Maximum lead wire resistance: 100 Ω per wire
Burnout indication: 115 % of the measuring range (upscale)
Sensing current: ≤ 1 mA
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Address setting: 0 - F (16 nodes)
■ Modbus-RTU
Configuration: Half-duplex, asynchronous, no procedure
Standard: Conforms to TIA/EIA-485-A
Max. transmission distance: 500 meters
Transfer rate: 4800, 9600, 19.2 k, 38.4 k bps
Data bit: 8
∙Potentiometer input: Total resistance 100 Ω to 10 kΩ
Minimum span: 50 % of total resistance
Excitation: ≤ 0.6 V DC
■ Ai1, Ai2, Ai3, Ai4
Parity bit: Odd, even, none
∙Voltage input: 1 – 5 V DC
Max. node number: 15 (except the master)
Transmission media:
Input resistance: ≥ 1 MΩ
■ Pi1, Pi2, Pi3, Pi4, Pi5: Dry contact
(Di1 through Di5 are assigned to the same terminals
respectively.)
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
Terminating resistor: incorporated
Node address setting: 1 - 247
Maximum frequency: 20 Hz
■ Modbus/TCP (Ethernet)
Minimum pulse width: 25 msec.
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
Physical layer standard: IEEE 802.3u
Data link layer: 10BASE-T / 100BASE-TX
Transfer rate: 10 / 100 Mbps, Auto Negotiation
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 3/12
http://www.m-system.co.jp/
MODEL: SC200
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Pi6: Dry contact
OUTPUT SPECIFICATIONS
■ Mv1, Mv2
∙Current output: 4 – 20 mA DC
Load resistance: ≤ 600 Ω
(Di6 is assigned to the same terminal.)
Maximum frequency: 10 kHz
■ Ao1, Ao2
Minimum pulse width: 0.05 msec.
Common: Negative common
∙Voltage output: 1 – 5 V DC
Load resistance: ≥ 10 kΩ
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
Excitation: 12 V DC ±10%, 15 mA
Current limiting circuit: Approx. 30 mA
■ Di1, Di2, Di3, Di4, Di5: Dry contact
(Pi1 through Pi5 are assigned to the same terminals
respectively.)
■ Discrete Output
∙Do1, Do2, Do3, Do4, Do5, RUN contact (Do6): Relay
contact
Rated load: 250 V AC @1 A (cos ø = 1)
30 V DC @1 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 60 W
Minimum load: 5 V DC @10 mA
Common: Negative common per 5 points
Sensing: Approx. 12 V DC, 6 mA
ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ
■ Di6: Dry contact
Mechanical life: 2 × 10 cycles
7
∙Do1, Do2, Do3, Do4, Do5: Photo MOSFET relay
Rating: 200 V AC/DC @0.5 A (resistive load)
ON resistance: 2.1 Ω
Maximum frequency: 4 Hz @24 V, 10 mA
ON delay time: ≤ 5.0 msec.
(Pi6 is assigned to the same terminal.)
Common: Negative common
OFF delay time: ≤ 3.0 msec.
Sensing: Approx. 12 V DC, 12 mA
ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ
OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ
[Table 1 (Thermocouple input)]
INSTALLATION
Power input
∙AC:
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
≤ 25 VA at 100 V AC
T/C
K (CA)
≤ 40 VA at 240 V AC
-272 to +1472
-272 to +1100
-260 to +1300
-272 to +500
24 to 1920
-150 to +1370
-170 to +1000
-180 to +1200
-170 to +400
1000 to 1760
380 to 1760
400 to 1760
100 to 2315
-130 to +1300
-200 to +600
-200 to +900
0 to 1395
•DC: ≤ 650 mA
E (CRC)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 90 %RH (non-condensing)
Mounting: Panel flush mounting (high-density mounting in
horizontal direction)
J (IC)
T (CC)
B (RH)
R
-100 to +1860
-100 to +1860
-52 to +2416
-272 to +1400
-252 to +700
-252 to +1000
-52 to +1496
-52 to +1860
Weight:
S
Approx. 1.8 kg (3.97 lb) for 250 mm depth type
Approx. 2.0 kg (4.41 lb) for 300 mm depth type
Approx. 2.5 kg (5.51 lb) for 400 mm depth type
C (WRe 5-26)
N
U
L
P (Platinel II)
PERFORMANCE
(PR)
300 to 1760
Accuracy
Overrange input (out of the usable range) is handled as burnout.
DC input: ±0.1 % ±1 digit
Thermocouple input: ±1℃ ±1 digit
±2℃ ±1 digit for B, R, S, C and PR
RTD input: ±1℃ ±1 digit
[Table 2 (RTD input)]
USABLE
RANGE (°C)
CONFORMANCE
RANGE (°C)
RTD
Pt 100 (JIS ’97, IEC
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
Pt 50Ω (JIS ’81)
Ni 100
)
-240 to +900
-240 to +900
-236 to +560
-236 to +700
-100 to +252
-200 to +850
-200 to +660
-200 to +510
-200 to +649
-80 to +250
Potentiometer input: ±0.2 % ±1 digit
DC output: ±0.1 %
Precision resistor module (REM4): ±0.1 %
Cold junction compensation:
±2°C at 25°C ±10°C
Overrange input (out of the usable range) is handled as burnout.
±4°C for S, R and PR
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 4/12
http://www.m-system.co.jp/
MODEL: SC200
DC input: ±0.015 %/°C (±0.008 %/°F)
Thermocouple input: ±0.015 %/°C (±0.008 %/°F)
RTD input: ±0.015 %/°C (±0.008 %/°F)
Potentiometer input: ±0.015 %/°C (±0.008 %/°F)
DC output: ±0.015 %/°C (±0.008 %/°F)
Precision resistor module (REM4): ±0.015 %/°C (±0.008
%/°F)
Line voltage effect: ±0.1 % over voltage range
Calendar clock accuracy: Monthly deviation 3 minutes at
25°C
RAM memory duration in power failure for hot start:
10 minutes assured
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to
Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or
Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Ao1 or Ao2 to Do1 to Do2
or Do3 or Do4 or Do5 or Do6 to NestBus to Modbus-RTU to
Modbus/TCP to power to FG)
500 V AC @ 1 minute (Pv2 to Ai1 or Ai2 or Ai3 or Ai4)
500 V AC @ 1 minute (Mv2 to Ao1 or Ao2)
500 V AC @ 1 minute (Do2 to Do3 to Do4 to Do5 to Do6)
500 V AC @ 1 minute (Pv1 to supply output)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (contact output)
Installation Category II (power)
Pollution degree 2
Input or output to contact output – Basic insulation (300
V)
Input or output to power - Reinforced insulation (300 V)
RoHS Directive
EN 50581
Protection against access to the terminal blocks:
Finger protection (VDE 0660-514)
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 5/12
http://www.m-system.co.jp/
MODEL: SC200
EXTERNAL VIEW
■ CONTROL MODULE FRONT VIEW
• Infrared communication type
• Stereo jack type
1
1
Auto/Man
Auto/Man
2
7
3
5
6
4
6
3
4
5
1. TFT Color LCD with touch panel
Provides operation and engineering views to facilitate monitoring and setting
2. Infrared communication port
Used to communicate with PC via IRDA Communication Adaptor (model: COP-IRDA) to program and change parameters
using Loop Configuration Builder Software (model: SFEW3E) or PC Configurator Software (model: SCCFG)
3. MV value (DOWN) button
4. Acceleration button
(Accelerates MV signal’s changing speed by pressing simultaneously with MV value button)
5. MV value (UP) button
6. Auto / Man selector (changes the control mode for MV output)
7. Configurator jack and cap
Connects with a PC where Loop Configuration Builder Software (model: SFEW3E) or PC configurator software (model: SCCFG)
is installed via a PC configurator cable (model: COP-US) and enables programming and parameter setting
COMMUNICATION CABLE CONNECTIONS
■ NestBus
SML
T1
SML
T1
This unit
T1
T2
T2
T2
*1
*1
T3
T3
T3
T4
T4
T4
*2
FG
■ Modbus-RTU
R2K-1
RS-485
RS-485
This unit
T1
This unit
T1
T1
T2
T3
T4
RS-232-C
T2
T2
*1
*1
T3
T3
T4
T4
*2
FG
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shield cables to all sections and ground them at single point.
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 6/12
http://www.m-system.co.jp/
MODEL: SC200
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ INFRARED COMMUNICATION TYPE
175 (6.89)
210 (8.27) max.
• ONE BLOCK TERMINAL
(without option /T)
1
RJ-45 CONNECTOR
52–M3.5 SCREW
*
MOUNTING BRACKETS
TERMINAL COVER
14
40
41
42
43
44
45
46
47
48
49
50
51
52
1
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
72 (2.83)
24
*2
67.5 (2.66)
(.94)
• SEPARABLE TERMINAL
(with option /T)
*1. For Modbus/TCP only
*2. Standard model: 250 mm (9.84”)
300 mm (11.81”)
400 mm (15.75”)
Option /3:
Option /4:
1
RJ-45 CONNECTOR
52–M3.5 SCREW
*
4–M4 SCREW FOR
FIXING TERMINAL
14
1
40
41
42
43
44
45
46
47
48
49
50
51
52
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
67.5 (2.66)
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 7/12
http://www.m-system.co.jp/
MODEL: SC200
■ STEREO JACK TYPE
175 (6.89)
210 (8.27) max.
• ONE BLOCK TERMINAL
(without option /T)
1
RJ-45 CONNECTOR
52–M3.5 SCREW
*
MOUNTING BRACKETS
TERMINAL COVER
14
40
41
42
43
44
45
46
47
48
49
50
51
52
1
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
Jack cap
11
25
12
26
13
72 (2.83)
1 (.04)
24
*2
67.5 (2.66)
(.94)
• SEPARABLE TERMINAL
(with option /T)
*1. For Modbus/TCP only
*2. Standard model: 250 mm (9.84”)
300 mm (11.81”)
400 mm (15.75”)
Option /3:
Option /4:
1
*
RJ-45 CONNECTOR
52–M3.5 SCREW
4–M4 SCREW FOR
FIXING TERMINAL
14
1
40
41
42
43
44
45
46
47
48
49
50
51
52
27
28
29
30
31
32
33
34
35
36
37
38
39
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
13
67.5 (2.66)
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 8/12
http://www.m-system.co.jp/
MODEL: SC200
MOUNTING REQUIREMENTS unit: mm
■ PANEL CUTOUT unit: mm
• Single mounting
• Clustered mounting
[68+72×(n - 1)] +1
68 +0.7
0
0
n = number of units
Panel thickness 2.3 – 20
■ Caution
• IP55 is ensured for the front panel of the unit mounted independently according to a panel. Test the sealing at the mounting
surface once the device is installed.
• Set the unit on a vertical surface with its operation buttons at the lower side. Mounting in other directions may cause heat
built up inside the unit and shorten its life span or degrade its performance.
• Ensure that there is sufficient space for ventilation inside a panel. Do not install above the devices that generate high heat
such as heaters, transformers or resistors. Leave at least 30 mm (1.2 inch) space above, below and behind the unit for
maintenance purpose (e.g. wiring, removing or installing).
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 9/12
http://www.m-system.co.jp/
MODEL: SC200
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
Isolation
Isolation
Shielded Twisted-pair Cable
+
+
+
+
+
34
35
36
37
40 T1
27 T2
28 T3
41 T4
To Other
NestBus
Devices
Discrete
Input
Circuit
Di 1 / Pi 1
Di 2 / Pi 2
Di 3 / Pi 3
Di 4 / Pi 4
Di 5 / Pi 5
–
1
Jumper*
SHLD
Shielded Twisted-pair Cable
Isolation
+
T1
1
To Other
Modbus-RTU
Devices
–
14 T2
15 T3
+
–
38
39
2
Jumper*
SHLD
Isolation
2
T4
Sensor
Excitation
SENSOR EXC
31
RJ-45 CONNECTOR Modbus/TCP
Di 6 / Pi 6
Isolation
16
Digital
Do 1
Input
Circuit
Computation
INPUT
COM
32
33
17
18
Isolation
Isolation
Isolation
Do 2
A1 42
B1 43
C1 44
A2 45
B2 46
C2 47
19
A/D
Converter
Pv 1
UNIVERSAL INPUT
20
Do 3
21
22
A/D
Converter
Do 4
Pv 2
UNIVERSAL INPUT
23
24
Do 5
+
+
+
48
49
50
25
A/D
Converter
Ai 1
Ai 2
Ai 3
Ai 4
10
Do 6
RUN CONTACT
11
Isolation
Isolation
Isolation
Output
Driver
+
3
Mv 1
+
–
51
52
–
+
–
+
4
5
6
7
Output
Driver
Isolation
Mv 2
Excitation
Supply
+
–
29
30
Output
Driver
2-WIRE TRANSMITTER
Ao 1
Ao 2
PC CONFIGURATOR/
BUILDER SOFTWARE
Output
Driver
Infrared Port / Jack
+
–
8
9
Display /
Setting
12 U(+)
13 V(–)
26 FG
POWER
*1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring).
*2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring).
■ DISCRETE INPUT PULSE
INPUT CONNECTION E.G.:
+12V
■ UNIVERSAL INPUT CONNECTION E.G.
POTENTIOMETER
max.
RTD
A
B
B
3
2
1
+
+
–
+
–
A
A
B
A
B
C
A
B
C
29
30
A
Dry contact
2-Wire
XMTR
T/C
1 or 2kΩ
*3
+
–
+
B
C
+
–
VOLT / CURRENT
INPUT
R
–
–
C
min.
CJC SENSOR
B
*4
*5
R
*3. Connect input resistor module (model: REM4) for current input.
*4. Connect CJC sensor for thermocouple input.
C
*5. Connect input resistor module (model: REM4).
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 10/12
http://www.m-system.co.jp/
MODEL: SC200
SYSTEM CONFIGURATION EXAMPLES
■ SINGLE LOOP CONTROL
■ CASCADE CONTROL
Multi-Function PID Controller
Model: SC200
Multi-Function PID Controller
Model: SC200
Ai
PV
PV
MV
MV
Flow
Level
■ I/O EXPANDED VIA NESTBUS
NestBus
Multi-Function PID Controller
Model: SC200
Multi-Function PID Controller
Model: SC200
Remote I/O Module
Model: SML
PWR
RUN
PV
PV
MV
MV
■ CONTROL / SUPERVISION VIA MODBUS/TCP
SCADA System
Modbus/TCP
Ethernet Communication Adaptor
Model: 72EM2-M4
Multi-Function PID Controller
Model: SC200
PV
ETHERNET
RS-485
RUN
SEND
FIELD
CNFG
MV
Modbus-RTU
Multi-Function PID Controller
Model: SC200
Multi-Function PID Controller
Model: SC200
PV
PV
MV
MV
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 11/12
http://www.m-system.co.jp/
MODEL: SC200
■ CONTROL / SUPERVISION VIA MODBUS-RTU
SCADA System
RS-485/RS-232-C
Converter
Model: R2K-1
Modbus-RTU
Multi-Function PID Controller
Model: SC200
Multi-Function PID Controller
Model: SC200
PV
PV
MV
MV
Specifications are subject to change without notice.
SC200 SPECIFICATIONS
ES-6338 Rev.17 Page 12/12
http://www.m-system.co.jp/