R8-PS1-R [MSYSTEM]
Remote I/O R8 Series EXTENSION POWER SUPPLY MODULE;型号: | R8-PS1-R |
厂家: | M-SYSTEM |
描述: | Remote I/O R8 Series EXTENSION POWER SUPPLY MODULE |
文件: | 总3页 (文件大小:207K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R8-PS1
YV4N is 160 mA.
Remote I/O R8 Series
1.6 (A) < 160 (mA) x 16 = 2.56 (A)
Inserting the R8-PS1 between 10th and 11th R8-YV4N
enables to connect 16 of R8-YV4N.
EXTENSION POWER SUPPLY MODULE
(non-isolated)
POWER UP
Functions & Features
Turn the power on at the same time as the power/network
module or turn the R8-PS1 on before the power/network
module turned on. If the R8-PS1 is not turned on within 3
seconds after the power/network module is turned on, I/O
modules are not correctly recognized
• Inserted between I/O modules and supply the power
• Up to two R8-PS1 use is available
24 (.94)
GENERAL SPECIFICATIONS
Connection
115
•Power input, excitation supply: Tension clamp (Front Twin
connection)
(4.53)
Applicable wire size: 0.2 - 1.5 mm
2
Stripped length: 10 mm
72 (2.83)
•Internal bus or internal power: Via connector
Max. number of I/O modules: 16
mm (inch)
(Max. consumption current of I/O modules: 1.6 A)
Isolation: Internal bus or internal power or power input to
exc. supply to FE1
MODEL: R8–PS1-R[1]
Power LED: Green light turns on when the power is supplied.
ORDERING INFORMATION
• Code number: R8-PS1-R[1]
Specify a code from below for [1].
(e.g. R8-PS1-R/Q)
INSTALLATION
Power consumption
• Specify the specification for option code /Q
(e.g. /C01)
•DC: Approx. 11 W 24 V DC (@ internal power max. current
1.6 A)
Internal power supply (power supply for I/O module):
• DC power supply: 5 V DC
POWER INPUT
DC power
• Current capacity: 1.6 A
Excitation supply output (excitation for I/O module)
•DC: 24 V DC ±10 %
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
•Operational current: 8 A
(From power supply, exitation supply connector, via
connector for internal bus, supplied to each I/O module.
Power output current consumption must be under
operational current.)
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Weight: 100 g (3.53 oz)
/C02: Polyurethane coating
PERFORMANCE
CAUTION
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(internal bus or internal power or power input to exc. supply
to FE1)
OUTPUT CURRENT & NUMBER OF CONNECTABLE UNIT
It is NOT available to connect 16 of R8-YV4N to
power/network module because of limitation of output
current of internal supply. The max. output current for
internal supply of power/network module is 1.6 A.
The max. consumption current for internal supply of R8-
http://www.m-system.co.jp/
R8-PS1 SPECIFICATIONS
ES-9789 Rev.4 Page 1/3
MODEL: R8-PS1
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Power indicator LED
Power
Unused
Internal Bus Connector
Connector for Power Supply and
Excitation Supply
24V
0V
+
-
FE1
CONNECTION DIAGRAMS
■ POWER SUPPLY, EXCITATION SUPPLY CONNECTOR ASSIGNMENT
Printed-circuit board connector (Phoenix Contact)
Unit side connector: MC1,5/5-GF-3,5
Cable side connector: TFMC1,5/5-STF-3,5
PIN
ID
FUNCTION
1
2
3
4
5
No.
1
24V Power supply 24V DC
2
0V
+
Power supply 0V DC
3
Excitation supply 24V DC
Excitation supply 0V DC
4
−
5
FE1 Grounding
Note: The numbers marked on the connector have no relationship to the pin number of the unit.
Wire according to the instruction manual of the unit.
http://www.m-system.co.jp/
R8-PS1 SPECIFICATIONS
ES-9789 Rev.4 Page 2/3
MODEL: R8-PS1
DIMENSIONS unit: mm (inch)
[4 (.16)]
[72 (2.83)]
55 (2.17)
[3 (.12)]
24 (.95)
DIN RAIL
(35 mm wide)
SCHEMATIC CIRCUITRY
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.
INTERNAL BUS
INTERNAL BUS
POWER LED
INTERNAL POWER (5V)
EXC. SUPPLY (24V)
Power
+24V
Circuit
0V
(No isolation)
+
-
FE1
Internal bus is connected for the modules near to the power/network module out of the modules connected to the R8-PS1. Internal
power and Exc. supply are not connected. All modules far from the power/network module are connected.
Specifications are subject to change without notice.