R8-DCT4D/Q [MSYSTEM]
Remote I/O R8 Series RELAY OUTPUT MODULE;型号: | R8-DCT4D/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R8 Series RELAY OUTPUT MODULE 输出元件 |
文件: | 总4页 (文件大小:215K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R8-DCT4D
Remote I/O R8 Series
GENERAL SPECIFICATIONS
Connection
• Output: Tension clamp
Applicable wire size: 0.2 - 2.5 mm
Stripped length: 10 mm
• Excitation supply, internal bus:
RELAY OUTPUT MODULE
(4 points, Tension clamp terminal block)
Functions & Features
2
• 4 channels for relay output, compact size remote I/O
module
Connected to internal bus connector
• Internal power: Via bus connector
• 8 pins tension clamp connector
Isolation: Output 1 to output 2 to output 3 to output 4 to
exc. supply to internal bus or internal power
Module address: With DIP switch
24 (.94)
Output at the loss of communication: Selectable with the
side DIP SW
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the
instruction manual.
115 (4.53)
Discrete output status indicators: Green LED; Refer to the
instruction manual.
73 (2.87)
mm (inch)
OUTPUT SPECIFICATIONS
Output: Relay contact 4 points
Output common: Common per one point (4 terminals)
Maximum load current: 2 A per point
Rated load: 250 V AC @2 A (cos ø = 1)
30 V DC @2 A (resistive load)
MODEL: R8–DCT4D[1]
ORDERING INFORMATION
• Code number: R8-DCT4D[1]
Specify a code from below for [1].
(e.g. R8-DCT4D/Q)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @1 mA
Mechanical life: 2 × 10 cycles (rate 300/min.)
7
• Specify the specification for option code /Q
(e.g. /C01)
When driving an inductive load, external contact protection
and noise quenching are recommended.
ON delay: ≤ 10 msec.
[1] OPTIONS
OFF delay: ≤ 10 msec.
blank: none
/Q: With options (specify the specification)
INSTALLATION
Max. current consumption: 100 mA
Exc. supply current consumption: 40 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
Weight: 120 g (0.26 lb)
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
PERFORMANCE
Data allocation: 1
Module addresses in use: 1
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute (output 1 to output 2 to output 3 to
output 4 to exc. supply to internal bus or internal power to
ground)
R8-DCT4D SPECIFICATIONS
ES-9798 Rev.1 Page 1/4
https://www.m-system.co.jp/
MODEL: R8-DCT4D
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (output)
Pollution Degree 2
Output to exc. supply or internal bus or internal power:
Basic insulation (250 V)
RoHS Directive
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
Status Indicator LED
DIP SW
Discrete Output
RUN
Status Indicator LED
1
2
3
4
SW1
SW2
8
7
6
5
4
3
2
1
Internal Bus Connector
Output Connectors
On
Do
1
8
R8-DCT4D SPECIFICATIONS
ES-9798 Rev.1 Page 2/4
https://www.m-system.co.jp/
MODEL: R8-DCT4D
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW2-1 through 2-7 are unused. Be sure to turn
off unused ones.
■Module Address
SW1-1 through 1-4 determine the tenth place digit, while
SW1-5 through 1-8 do the ones place digit of the module
address.
Address is selected between 0 to 31.
(Factory setting: 0)
SW1
MODULE ADDRESS
×10
×1
1
2
3
4
5
6
7
8
0
1
2
3
4
5
6
7
8
9
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
■ Output at the Loss of Communication
SW2
OUTPUT AT THE LOSS OF COMMUNICATION
5
Output Hold (*)
OFF
(last data correctly received is hold)
Stop output (Output !xed at OFF)
ON
■ Terminator DIP SW
SW2
TERMINATOR SW
6
Without (*)
OFF
ON
With
■ Con!guration Mode
SW2
8
CONFIGURATION MODE
DIP switch setting (*)
OFF
ON
PC Configurator and communication
R8-DCT4D SPECIFICATIONS
ES-9798 Rev.1 Page 3/4
https://www.m-system.co.jp/
MODEL: R8-DCT4D
DIMENSIONS unit: mm (inch)
73 (2.87)
55 (2.17)
[4 (.16)]
24 (.94)
[3 (.12)]
DIN RAIL
(35 mm wide)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
OUTPUT
LED STATUS LED
+24V
Isolation
Ry
OUTPUT
CONNECTOR
Comm.
Circuit
INTERNAL BUS
Control
Circuit
1
2
Do 1
Do 2
Do 3
Do 4
Ry
Ry
Ry
INTERNAL POWER
DIP SW
3
4
+24V
0V
Output
Circuit
EXC. SUPPLY
5
6
7
8
0V
Specifications are subject to change without notice.
R8-DCT4D SPECIFICATIONS
ES-9798 Rev.1 Page 4/4