R5-SV2S/Q [MSYSTEM]
Remote I/O R5 Series;型号: | R5-SV2S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R5 Series |
文件: | 总3页 (文件大小:109K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R5-SV
Input range: Selectable with the side DIP SW
Remote I/O R5 Series
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
DC VOLTAGE INPUT MODULE
18 (.71)
INPUT SPECIFICATIONS
■ Narrow Span: -1 – +1 V, 0 – 1 V DC
Input resistance: 100 kΩ min.
■ Wide Span: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
90
(3.54)
96.5
(3.80)
Input resistance: 1 MΩ min.
mm (inch)
INSTALLATION
MODEL: R5-SV[1][2][3]
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 100 g (3.53 oz)
ORDERING INFORMATION
• Code number: R5-SV[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. R5-SV2W/Q)
• Specify the specification for option code /Q
(e.g. /C01)
PERFORMANCE
Conversion accuracy: ±0.05 %
Data range: 0 – 10000 of the input range
Data allocation: 1 (2 for 2-channel type)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to internal bus or internal power)
[1] NO. OF CHANNELS
1: 1 channel
2: 2 channels
[2] COMMUNICATION MODE
S: Single
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
W: Dual
[3] OPTIONS
blank: none
STANDARDS & APPROVALS
EU conformity:
/Q: With options (specify the specification)
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
EN 50581
/C02: Polyurethane coating
/C03: Rubber coating
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R5-BS)
Input: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
Internal power: Via the base (model: R5-BS)
Isolation: Input 1 to input 2 to internal bus or internal power
R5-SV SPECIFICATIONS
ES-6116 Rev.8 Page 1/3
http://www.m-system.co.jp/
MODEL: R5-SV
EXTERNAL VIEW
■ SIDE VIEW
■ FRONT VIEW
RUN
RUN LED
1 2 3 4 5 6 7 8
Input 1
Input 2
4
1
5
2
6
3
Euro Type
Connector Terminals
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
LOCKING CLAMP
18 (.71)
6.5
90 (3.54)
(.26)
4
1
5
2
6
3
POSITIONING GUIDE
*
*Euro type connector terminals (4, 5 and 6) provided only with 2-ch. option.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED DIP SW
Isolation
INTERNAL BUS A
Communication
Circuit
1
2
3
+
+
–
INTERNAL BUS B*
WIDE SPAN
NARROW SPAN
INPUT 1
Control
Circuit
INTERNAL POWER
Isolation
4
5
6
+
+
–
WIDE SPAN
NARROW SPAN
INPUT 2
*For dual redundant communication.
Note: Connect either wide or narrow span terminals for each channel.
The section enclosed by broken line is with 2-ch. option.
R5-SV SPECIFICATIONS
ES-6116 Rev.8 Page 2/3
http://www.m-system.co.jp/
MODEL: R5-SV
Specifications are subject to change without notice.
R5-SV SPECIFICATIONS
ES-6116 Rev.8 Page 3/3
http://www.m-system.co.jp/
相关型号: