R5-MS1S/Q [MSYSTEM]
Remote I/O R5 Series POTENTIOMETER INPUT MODULE;型号: | R5-MS1S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R5 Series POTENTIOMETER INPUT MODULE 输入元件 |
文件: | 总3页 (文件大小:112K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R5-MS
Zero/Span adj. mode selector: Rotary switch; run mode and
adj. mode selectable
Remote I/O R5 Series
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
POTENTIOMETER INPUT MODULE
18 (.71)
2
3
4
1
5
0
8
7 6
9
INPUT SPECIFICATIONS
Total resistance: 100 Ω – 10 kΩ
Minimum span: 50 % of the total resistance range
Excitation: 0.5 V DC
90
(3.54)
96.5
(3.80)
mm (inch)
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 100 g (3.53 oz)
MODEL: R5-MS[1][2][3]
ORDERING INFORMATION
• Code number: R5-MS[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. R5-MS2W/Q)
PERFORMANCE
Conversion accuracy: ±0.1 %
• Specify the specification for option code /Q
(e.g. /C01)
Data range: 0 – 10000 of the input range
Data allocation: 1 (2 for 2-channel type)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Resolution: 1/10000 of the total resistance range
(Reduced by the actual range determined zero/ span
positions. Minimum 50 % of the total resistance range must
be maintained.)
[1] NO. OF CHANNELS
1: 1 channel
2: 2 channels
[2] COMMUNICATION MODE
S: Single
Response time: ≤ 0.1 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to internal bus or internal power)
W: Dual
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
STANDARDS & APPROVALS
EU conformity:
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
/C02: Polyurethane coating
/C03: Rubber coating
EN 50581
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R5-BS)
Input: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
Internal power: Via the base (model: R5-BS)
Isolation: Input 1 to input 2 to internal bus or internal power
R5-MS SPECIFICATIONS
ES-6146 Rev.6 Page 1/3
http://www.m-system.co.jp/
MODEL: R5-MS
FUNCTIONS
• Zero/Span Adjustment Modes
Run Mode
Normal operating mode
Input 0 % Adjustment Mode
Apply the actual 0% input and press SET.
Input 100 % Adjustment Mode
Apply the actual 100 % input and press SET.
• How to Operate
1) Start up in Monitor Mode (SW position = 0) and wait for 2
or 3 seconds.
2) Switch to another mode and go through the adjustments.
3) Reset the switch to the position ‘0’ so that the new
setting is stored in the internal memory.
• Cautions on the LEDs
1) Mode switching from Run to another mode becomes
effective when SET button is touched and the LED for the
respective mode starts blinking after the rotary switch
setting has been changed.
2) Mode switching back to Monitor becomes effective
automatically in a few seconds after the switch is reset to
‘0’ and is confirmed with the LED stopping blinking.
EXTERNAL VIEW
RUN
RUN LED
Zero/Span Adj.
Mode Selector
SET
SET Button
4
1
5
2
6
3
Euro Type
Connector Terminals
R5-MS SPECIFICATIONS
ES-6146 Rev.6 Page 2/3
http://www.m-system.co.jp/
MODEL: R5-MS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
LOCKING CLAMP
18 (.71)
6.5
90 (3.54)
(.26)
4
1
5
2
6
3
POSITIONING GUIDE
*
*Euro type connector terminals (4, 5 and 6) provided only with 2-ch. option.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
POTENTIOMETER
RUN LED
max.
Excitation Volt.
Generator
+
1
2
3
3
2
1
Isolation
INTERNAL BUS A
Communication
Circuit
INPUT 1
INTERNAL BUS B*
–
min.
Control
Circuit
POTENTIOMETER
max.
INTERNAL POWER
Excitation Volt.
Generator
+
4
5
6
3
2
1
Isolation
INPUT 2
–
min.
SET
BUTTON
ROTARY SW
*For dual redundant communication.
Note: The section enclosed by broken line is with 2-ch. option.
Specifications are subject to change without notice.
R5-MS SPECIFICATIONS
ES-6146 Rev.6 Page 3/3
http://www.m-system.co.jp/