R3-WT1B16S/Q [MSYSTEM]
Remote I/O R3 Series MULTI POWER INPUT MODULE;型号: | R3-WT1B16S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series MULTI POWER INPUT MODULE 输入元件 |
文件: | 总5页 (文件大小:184K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-WT1B
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
MULTI POWER INPUT MODULE
(clamp-on current sensor type CLSB use)
/C02: Polyurethane coating
/C03: Rubber coating
52.5 (2.07)
RELATED PRODUCTS
• PC configurator software (model: R3CON)
The R3CON is used to set up the software setting of this
module. Downloadable at M-System's web site.
• Clamp-on current sensor (model: CLSB-05)
• Clamp-on current sensor (model: CLSB-10)
Note: The clamp-on current sensor, not included in the
product package of the R3 module, must be ordered
separately. Refer to the data sheet for the sensor for more
information such as applicable wire diameter.
130
(5.12)
109
(4.29)
mm (inch)
MODEL: R3-WT1B[1][2][3][4]
GENERAL SPECIFICATIONS
Connection
ORDERING INFORMATION
• Code number: R3-WT1B[1][2][3][4]
Specify a code from below for each of [1] through [4].
(e.g. R3-WT1B11W/Q)
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3.5 screw terminals (torque 0.8 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
Isolation: Sensor core to sensor output or current input or
internal bus or internal power to voltage input
DIP switch settings:
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF SYSTEMS
1B: 1, Sensor type CLSB
• Computation methods
• Count Reset (Disable/Enable)
• Others
[1] CONFIGURATION
1: 3-phase / 3-wire
Refer to the instruction manual for details.
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input abnormality;
2: Single-phase / 2-wire
3: Single-phase / 3-wire
[2] INPUT (unbalanced load)
1: 110 V AC / 50 A
Green in normal operating conditions.
Power ON timer: Starts conversion in 10 seconds after the
power is turned on.
2: 110 V AC / 100 A
5: 220 V AC / 50 A
6: 220 V AC / 100 A
Low-end cutout: Converted data forced to 0 % for 2 % or
less input. (Selectable by using R3CON)
Computation
A: 100 V / 200 V AC / 50 A (single-phase/3-wire)
B: 100 V / 200 V AC / 100 A (single-phase/3-wire)
Active power, reactive power: Time division
multiplication
[3] COMMUNICATION MODE
S: Single
Power factor: Calculated with active power (P)
and reactive power (Q)
W: Dual
P
2
P + Q
2
√
[4] OPTIONS
blank: none
Frequency: One-shot
/Q: With options (specify the specification)
R3-WT1B SPECIFICATIONS
ES-8417 Rev.5 Page 1/5
http://www.m-system.co.jp/
MODEL: R3-WT1B
INPUT SPECIFICATIONS
Frequency: 50 or 60 Hz
PERFORMANCE
Accuracy
• Voltage Input
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz) (Except the
sensor’s accuracy.)
Operational range: 0 – 120 % of rating
Overload capacity: 150 % of rating for 10 sec., 120 %
continuous
Active / reactive power: ±2 % (Add sensor’s accuracy for
overall performance)
• Current Input
Power factor: ±4 % (Add sensor’s accuracy for overall
performance)
Range
CLSB-05: 0 – 50 A AC
Frequency: ±1 %
CLSB-10: 0 – 100 A AC
Active / reactive energy: ±2 % (Add sensor’s accuracy for
overall performance)
Operational range: 0 – 115 % of rating
Be sure that the input voltage is of 440 V or less.
■ Power Factor Input Range:
-1 – lag 0 – 1 – lead 0 – -1
Magnetic field (ext. origin) effect: ± 0.5 % (400 A/m)
Conversion rate: 100 msec.
Conversion data: 16 bits / 32 bits
Data range: -1000 – 0 – 1000 – 0 – -1000 with SW2-1 set to
OFF
Data allocation: 4, 8 or 16 selectable
Current consumption: 150 mA
A device which employs different measuring methods may
show different outputs from that of M-System's.
■ Frequency Input Range: 45 – 65 Hz
Data range: 4500 – 6500
Response time: ≤ 2 sec. (0 – 100 % ±1 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (voltage input to
current input or internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
■ACTIVE / REACTIVE POWER INPUT RANGE
•Single-phase/2-wire
INPUT
USABLE RANGE VT BURDEN (VA)
110V / 50A
110V / 100A
220V / 50A
220V / 100A
5500W
0.2/phase
11000W
11000W
0.4/phase
22000W
•Single-phase/3-wire
INPUT
USABLE RANGE VT BURDEN (VA)
200V / 50A
200V / 100A
10000W
0.2/phase
20000W
•3-phase/3-wire
INPUT
USABLE RANGE
VT BURDEN (VA)
0.2/phase
lead
110V / 50A
9526W /
9526 var
19050 var
19050 var
38100 var
lag
lead
lag
110V / 100A 19050W /
220V / 50A 19050W /
220V / 100A 38100W /
lead
lag
0.4/phase
lead
lag
Reactive power data in Lead: Positive, Lag: Negative
Note: Invalid in single-phase systems.
Choose VT ratio so that the calibration range calculated by
the following equation is within the usable range in the
above table.
Measuring Wattage [W]
Calibration Range [W] =
(VT Ratio) × (Current Rating)
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 300 g (0.66 lb)
R3-WT1B SPECIFICATIONS
ES-8417 Rev.5 Page 2/5
http://www.m-system.co.jp/
MODEL: R3-WT1B
EXTERNAL VIEW
■ FRONT VIEW
RUN LED
■ SIDE VIEW
1
2
3
4
5
6
7
8
9
10
ERR LED
SW3
SW2
SW1
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
ON
ON
ON
TRANSMISSION DATA DESCRIPTIONS
n = I/O address on the installation base
Factory setting = 1 kWh and 1 kvarh per bit.
ADDRESS
CONTENTS
2
n
Active power *
Reactive power * 2
Data address depends upon the data allocation mode as
n + 1
n + 2
n + 3
2
indicated below:
4 (n thr. n+3)
Power factor *
Frequency * 2
8 (n thr. n+7)
3
3
n + 4
n + 5
n + 6
n + 7
Incoming active energy (lower bits)
Incoming active energy (upper bits)
Outgoing active energy (lower bits)
Outgoing active energy (upper bits)
*
*
16 (n thr. n+15)
*1. Fixed at 16 for the R3-NPx.
*2. 16-bit data
*3. 32-bit data
3
n + 8
n + 9
n +10
n +11
LAG reactive energy (lower bits)
LAG reactive energy (upper bits)
LEAD reactive energy (lower bits)
LEAD reactive energy (upper bits)
*
3
*
n +12
n +13
n +14
n +15
0
0
0
0
R3CON type ID WT1B***
Network module 4, 8, 16
data allocation
mode example *1
I/O DATA DESCRIPTIONS
■ 16-BIT DATA
16-bit binary data. Minus values are represented in 2’s complements.
15
0
■ 32-BIT DATA
32-bit binary data. Minus values are represented in 2’s complements.
31
upper digits
16 15
lower digits
0
R3-WT1B SPECIFICATIONS
ES-8417 Rev.5 Page 3/5
http://www.m-system.co.jp/
MODEL: R3-WT1B
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
52.5 (2.07)
109 (4.29)
POSITIONING
GUIDE
1
2
3
4
5
6
7
8
9
10
10–M3.5
SCREW
TERMINAL
COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ 3-PHASE/3-WIRE
RUN LED ERR LED DIP SW
SOURCE
1
2
3
Input Circuit
VT
FUSE
INTERNAL BUS A
U
u
P1
P2
P3
Communication
Circuit
1
2
3
4
INTERNAL BUS B*
VOLTAGE
INPUT
V
V
v
v
Control
Circuit
U
u
INTERNAL POWER
LOAD
SOURCE
9
1
2
3
10
k
l
1S
1L
3S
3L
5
6
7
8
CLAMP-ON SENSOR
CURRENT
INPUT
Input
Circuit
k
CLAMP-ON SENSOR
l
LOAD
*For dual redundant communication.
■ SINGLE-PHASE/2-WIRE
RUN LED ERR LED DIP SW
SOURCE
1
2
Input Circuit
VT
FUSE
INTERNAL BUS A
U
V
u
v
P1
P2
Communication
Circuit
1
2
3
4
VOLTAGE
INPUT
INTERNAL BUS B*
LOAD
Control
Circuit
INTERNAL POWER
SOURCE
1
2
Input Circuit
9
k
l
1S
1L
Input
Circuit
5
6
7
8
CURRENT
INPUT
10
CLAMP-ON SENSOR
LOAD
*For dual redundant communication.
R3-WT1B SPECIFICATIONS
ES-8417 Rev.5 Page 4/5
http://www.m-system.co.jp/
MODEL: R3-WT1B
■ SINGLE-PHASE/3-WIRE
RUN LED ERR LED DIP SW
SOURCE
1
N
2
Input Circuit
VT
FUSE
INTERNAL BUS A
U
u
P1
P0
P2
Communication
Circuit
1
2
3
4
INTERNAL BUS B*
VOLTAGE
INPUT
V
V
v
v
Control
Circuit
U
u
INTERNAL POWER
LOAD
SOURCE
9
1
N 2
10
Input Circuit
k
1S
1L
2S
2L
5
6
7
8
CLAMP-ON SENSOR
CURRENT
INPUT
Input
Circuit
l
k
CLAMP-ON SENSOR
l
LOAD
*For dual redundant communication.
Specifications are subject to change without notice.
R3-WT1B SPECIFICATIONS
ES-8417 Rev.5 Page 5/5
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明