R3-TS8S/Q [MSYSTEM]
Remote I/O R3 Series THERMOCOUPLE INPUT MODULE;型号: | R3-TS8S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series THERMOCOUPLE INPUT MODULE 输入元件 |
文件: | 总5页 (文件大小:141K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-TS8
Remote I/O R3 Series
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
THERMOCOUPLE INPUT MODULE
(8 points, isolated)
27.5 [1.08]
Isolation: Input 1 to input 2 to input 3 to input 4 to input 5 to
input 6 to input 7 to input 8 to internal bus or internal power
Sensor type: Selectable with the side DIP SW
(Independent types selectable per group of 4 channels.)
Temperature unit: °C, °F or absolute temperature selectable
with the side DIP SW
130
[5.12]
Conversion rate: Selectable with the side DIP SW
Burnout detection: Upscale or downscale selectable with the
side DIP SW
109
[4.29]
mm [inch]
Linearization: Standard
Cold junction compensation: CJC sensor attached to the
input terminals
MODEL: R3-TS8[1][2]
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with burnout; Green in normal operating conditions.
ORDERING INFORMATION
• Code number: R3-TS8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-TS8W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
NO. OF CHANNELS
8: 8
[1] COMMUNICATION MODE
S: Single
W: Dual
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8363)
R3-TS8 SPECIFICATIONS
ES-8363 Rev.13 Page 1/5
https://www.m-system.co.jp/
MODEL: R3-TS8
Cold junction compensation error:
INPUT SPECIFICATIONS
Input resistance: 30 kΩ min.
Burnout sensing: 0.1 μA
±1.0°C max. (at 25°C ±10°C)
±1.8°F max. (at 77°F ±18°F)
(±1.5°C or ±2.7°F for R, S, PR)
Temperature range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Burnout response time: ≤ 2 sec.
°C
T/C
K (CA)
E (CRC)
J (IC)
USABLE
RANGE
CONFORMANCE
RANGE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to input 5 to input 6 to input 7 to
input 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
-272 to +1472
-272 to +1120
-260 to +1300
-150 to +1370
-170 to +1000
-180 to +1200
T (CC)
B (RH)
R
-272 to +500
24 to 1920
-100 to +1860
-170 to +400
400 to 1760
200 to 1760
S
-100 to +1860
-52 to +2416
-272 to +1400
0 to 1760
0 to 2315
-130 to +1300
C (WRe 5-26)
N
STANDARDS & APPROVALS
EU conformity:
U
L
-252 to +700
-252 to +1000
-52 to +1496
-52 to +1860
-200 to +600
-200 to +900
0 to 1395
EMC Directive
P (Platinel II)
(PR)
EMI EN 61000-6-4
0 to 1760
EMS EN 61000-6-2
RoHS Directive
°F
T/C
USABLE
RANGE
CONFORMANCE
RANGE
K (CA)
E (CRC)
J (IC)
-458 to +2682
-458 to +2048
-436 to +2372
-238 to +2498
-274 to +1832
-292 to +2192
T (CC)
B (RH)
R
-458 to +932
75 to 3488
-148 to +3380
-274 to +752
752 to 3200
392 to 3200
S
-148 to +3380
-62 to +4381
-458 to +2552
32 to 3200
32 to 4199
-202 to +2372
C (WRe 5-26)
N
U
L
-422 to +1292
-422 to +1832
-62 to +2725
-62 to +3380
-328 to +1112
-328 to +1652
32 to 2543
32 to 3200
P (Platinel II)
(PR)
Max. (upscale) or min. (downscale) value of the usable
range when a burnout is detected.
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 250 g (0.55 lb)
PERFORMANCE
Conversion accuracy: ±1.0°C (±1.8°F) except ±2.0°C
(±3.6°F) for B, R, S, C, PR
Conversion rate: 250 msec. or 1 sec. selectable
Data range
°C, absolute temperature: Engineering unit value × 10
(integer)
°F: Engineering unit value (integer)
Data allocation: 8
Current consumption: 100 mA
R3-TS8 SPECIFICATIONS
ES-8363 Rev.13 Page 2/5
https://www.m-system.co.jp/
MODEL: R3-TS8
EXTERNAL VIEW
■ SIDE VIEW
■ FRONT VIEW
RUN LED
ERR LED
1
2
15
16
17
18
19
20
21
22
23
24
25
26
27
28
3
4
5
SW1
SW2
SW3
6
T/C
Burnout
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
Input 1-4 (SW1)
or
Input 5-8 (SW2)
Temp.
Unit
Conv.
8
9
Rate
10
11
12
13
14
ON
ON
ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
15
2
16
3
17
4
18
5
19
6
28–M3
SCREW
20
7
21
8
22
9
23
10
24
11
25
12
26
13
27
14
28
TERMINAL
COVER
R3-TS8 SPECIFICATIONS
ES-8363 Rev.13 Page 3/5
https://www.m-system.co.jp/
MODEL: R3-TS8
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Input Circuit
INTERNAL BUS A
+
+
+
+
+
+
+
+
Communication
Circuit
+
–
1
T/C
INTERNAL BUS B*
comp. wire
INPUT 1
–
–
–
Control
Circuit
2
3
CJC
SENSOR
INTERNAL POWER
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
+
4
13
14
27
28
T/C
comp. wire
–
INPUT 2
5
6
CJC
SENSOR
+
7
T/C
comp. wire
–
INPUT 3
8
CJC
SENSOR
• Unused Input Channels
Close across the unused input terminals as shown below.
9
INPUT 1
1
INPUT 2
4
INPUT 3
7
INPUT 4
10
+
10
T/C
comp. wire
Short
CJC
–
INPUT 4
–
2
3
5
6
8
9
11
12
11
SENSOR
CJC
SENSOR
12
INPUT 5
15
INPUT 6
18
INPUT 7
21
INPUT 8
24
+
15
T/C
comp. wire
Short
–
INPUT 5
16
17
19
20
22
23
25
26
–
CJC
SENSOR
16
CJC
SENSOR
17
Unused channels left open are equal to the burnout, which
turns the red ERR LED on and sets a burnout flag at the
PLC or the host device.
When you choose B (RH) thermocouple, shortcircuiting
across the terminal may not be effective to cancel the
burnout flag. Be sure to use the PC Configurator Software
(model: R3CON).
Unused channels can be specified and set so on the PC
Configurator Software without needing to short at the field
terminals.
+
18
T/C
comp. wire
–
INPUT 6
–
19
CJC
SENSOR
20
+
21
T/C
comp. wire
–
INPUT 7
–
22
CJC
SENSOR
23
+
24
T/C
comp. wire
–
INPUT 8
–
25
CJC
SENSOR
26
*For dual redundant communication.
R3-TS8 SPECIFICATIONS
ES-8363 Rev.13 Page 4/5
https://www.m-system.co.jp/
MODEL: R3-TS8
Specifications are subject to change without notice.
R3-TS8 SPECIFICATIONS
ES-8363 Rev.13 Page 5/5
https://www.m-system.co.jp/