R3-TC2V [MSYSTEM]
Remote I/O R3 Series TEMPERATURE CONTROL MODULE;型号: | R3-TC2V |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series TEMPERATURE CONTROL MODULE |
文件: | 总7页 (文件大小:183K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-TC2
P: 12 V pulse (Load resistance 600 Ω max.)
Remote I/O R3 Series
Open-collector 2 points
TEMPERATURE CONTROL MODULE
Functions & Features
COMMUNICATION MODE
S: Single
• Two PID controllers
• Universal input x 2 points, control output x 4 points,
discrete input x 2 points, clamp-on current sensor input x 2
points
[2] OPTIONS
blank: none
• 2 universal inputs configurable to T/C, RTD, DC current or
voltage independently
/Q: With options (specify the specification)
• Discrete inputs usable to switch PID bank or operation
mode
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Control outputs configurable to MV, PV or alarm
• Clamp-on current sensor input enables to detect heater
wire break or over current
/C02: Polyurethane coating
/C03: Rubber coating
• Auto tuning function
• Minimum construction with an installation base (model: R3
-BS02), interface module and temperature controller
module
RELATED PRODUCTS
• Modbus Interface Module (model: R3-NM3)
(Not compatible with other Network modules)
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
• Configurable with PC configurator (model: R3CON)
• Mixed installation with other I/O modules
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
27.5 (1.08)
130
(5.12)
• Clamp-on current sensor (model: CLSE)
(Used for detecting the heater wire break)
109
(4.29)
GENERAL SPECIFICATIONS
Connection
mm (inch)
Internal bus: Via the Installation Base (model: R3-BSx)
Input, control output: M3 separable screw terminal (torque
0.5 N·m)
MODEL: R3-TC2[1]S[2]
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
ORDERING INFORMATION
• Code number: R3-TC2[1]S[2]
Specify a code from below for each [1] and [2].
(e.g. R3-TC2AS/Q)
Isolation: Pv1 to Pv2 to CT1 or CT2 to Di1 or Di2 to MV1 or
MV2 to Do1 or Do2 to internal bus or internal power
CT Input waveform
RMS sensing: Up to 15 % of 3rd harmonic content
RUN indicator: Bi-color (red/green) LED;
Red when the internal bus operates normally.
ERR indicator: Bi-color (red/green) LED; Red at device error;
Green in normal operating conditions.
• Specify the specification for option code /Q
(e.g. /C01)
CONTROL LOOP
2: 2 loops
Loop status indicator (RUN1): Red LED; turns on when loop
1 operating
Loop status indicator (AUTO1): Red LED; turns on during
auto mode, turns off during manual mode at loop 1
Loop status indicator (ERR1): Red LED; turns on during error
at loop 1
[1] CONTROL OUTPUT
A: 0 – 20 mA DC (Load resistance 500 Ω max.)
Open-collector 2 points
V: 0 – 10 V DC (Load resistance 2 kΩ max.)
Open-collector 2 points
Loop status indicator (ALM1): Red LED; turns on when alarm
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 1/7
http://www.m-system.co.jp/
MODEL: R3-TC2
trip on loop 1
Allowable leadwire resistance: 20 Ω per wire
Loop status indicator (RUN2): Red LED; turns on when loop
2 operating
• Potentiometer
Excitation: ≤ 0.33 mA
Loop status indicator (AUTO2): Red LED; turns on during
auto mode, turns off during manual mode at loop 2
Loop status indicator (ERR2): Red LED; turns on during error
at loop 2
Allowable leadwire resistance: 20 Ω per wire
■ Clamp-on current sensor (CT1, CT2)
(Sensor model No.: AC input)
CLSE-R5: 0 – 5 A
Loop status indicator (ALM2): Red LED; turns on when alarm
trip on loop 2
CLSE-05: 0 – 50 A
CLSE-10: 0 – 100 A
Control mode: Standard PID, heating and cooling control
(ON/OFF, PID)
CLSE-20: 0 – 200 A
CLSE-40: 0 – 400 A
Proportional band (P): 0.1 to 999.9 (temperature unit)
Integral time (I): 0.0 to 9999.9 sec.
Derivative time (D): 0.0 to 9999.9 sec.
Auto-tuning: Limit cycle method
CLSE-60: 0 – 600 A
Frequency: 50 / 60 Hz (45 - 65 Hz)
Operational range: 0 – 120 % of rating
Overload capacity:
Alarm: Deviation high & low, absolute high & low, etc.
Sampling cycle: 100 msec.
CLSE-R5: 10 A continuous
CLSE-05: 60 A continuous
CLSE-10: 120 A continuous
CLSE-20: 240 A continuous
CLSE-40: 480 A continuous
CLSE-60: 720 A continuous
Be sure that the input voltage is of 480 V or less.
■ Discrete Input (Di1, Di2)
Contact rating: 3.3 V @1 mA
Detection levels:
Control cycle: 0.1 to 99.9 sec.
MV output range: -5 - +105 %
Parameters: Stored in E2PROM; write/erase cycle endurance:
less than 100 000
Parameter setting: With PC configurator software (model:
R3CON)
User-configurable items: With PC configurator software
(model: R3CON)
· Input type
≤ 15 kΩ / 0.5 V at close
· Input range
≥ 350 kΩ / 2.5 V at open
· Output range
· Cold junction compensation; CJC sensor attached to input
terminal. CJC can be enabled or disabled per each universal
input.
OUTPUT SPECIFICATIONS
Four control outputs are configurable to Mv, Ao or Do.
■ Control Output (Mv1, Mv2)
Specify the type of output with the code number.
• DC Current: 0 – 20 mA DC
Operational range: 0 – 23 mA DC
Load resistance: ≤ 500 Ω
INPUT SPECIFICATIONS
■ Universal input 1, 2 (Pv1, Pv2)
For type and range configuration, refer to the instruction
manual.
• DC Voltage: 0 – 10 V DC
DC Current:
Operational range: 0 - 11.5 V DC
Load resistance: ≥ 2 kΩ
Input range: 0 - 20 mA DC
Input resistance: 49.9 Ω resistor incorporated
• DC voltage input
■ Voltage Pulse
Maximum frequency: 1 Hz
Input resistance: ≥ 10 kΩ (-1000 to +1000 mV DC)
Input resistance: ≥ 1 MΩ (-10 to + 10 V DC)
• Thermocouple
Minimum pulse width: 1 msec.
Hi level: 12 V ±15 %
Lo level: ≤ 0.5 V
Input resistance: ≥ 10 kΩ
Load resistance: 600 Ω min.
■ Control Output (Do1, Do2)
• Open collector
Input range: Refer to the table 1
Burnout sensing: ≤ 4 μA
Conformance range: Refer to the table 1
• RTD (2-wire or 3-wire)
Maximum frequency: 1 Hz
Minimum pulse width: 1 msec.
Output rating: 50 V DC 100 mA (resistive load)
Saturation voltage: 0.5 V DC
Excitation: ≤ 0.33 mA
Allowable leadwire resistance: 20 Ω per wire
• Resistance
Excitation: ≤ 0.33 mA
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 2/7
http://www.m-system.co.jp/
MODEL: R3-TC2
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Accuracy
• Pv1 or Pv2: Refer to "Input type, range & conversion
accuracy" section.
• CT1 or CT2: ±2 % (sensor error margin not included)
• MV1 or MV2: ±0.5 % (added to the input accuracy)
Data allocation: 8
Current consumption: ≤ 120 mA
Cold junction compensation error:
±2.0°C at 0 – 50°C (±3.6°F at 32 – 122°F)
Temp. coefficient
• Pv1 or Pv2: ±0.03 %/°C (± 0.02 %/°F)
• CT1 or CT2: ±0.03 %/°C (± 0.02 %/°F)
Response time
• CT1 or CT2: ≤ 2 sec. (0 – 90 %)
• Mv1 or Mv2: ≤ 1 sec. (0 – 90 %, DC output)
Burnout response: ≤ 10 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute (Pv1 to Pv2 to
CT1 or CT2 to Di1 or Di2 to MV1 or MV2 to Do1 or Do2 to
internal bus or internal power)
1500 V AC @1 minute (internal power to FG)
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 3/7
http://www.m-system.co.jp/
MODEL: R3-TC2
INPUT TYPE, RANGE & CONVERSION ACCURACY
Table 1
1
*
INPUT TYPE
INPUT RANGE
0 – 20mA DC
ACCURACY
DC Current
DC Voltage
±20ꢀA
When the 100% is ≤ 50mV
-1000 – +1000mV DC
±10ꢀV
±±0ꢀV
±ꢁ0ꢀV
±ꢂ0ꢀV
When the 100% is ≤ 200mV
When the 100% is ≤ 500mV
When the 100% is > 500mV
-10 – +10V DC
0 – ±000Ω
±0ꢃ1%
±0ꢃ1Ω
±0ꢃ1Ω
°F
Potentiometer
Resistor
0 – ±000Ω
°C
THERMOCOUPLE
1
1
*
*
INPUT RANGE
0 – 17ꢁ0
ACCURACY CONFORMANCE RANGE INPUT RANGE
ACCURACY
±1ꢃꢂ0
±0ꢃ±5
±0ꢃ3ꢁ
±0ꢃ±5
±0ꢃ±5
±1ꢃ35
±0ꢃ90
±0ꢃ90
±0ꢃ±5
±0ꢃ5±
±0ꢃ3ꢁ
±0ꢃ±5
±0ꢃ±5
°F
CONFORMANCE RANGE
32 – 3200
(PR)
±1ꢃ00
±0ꢃ25
±0ꢃ20
±0ꢃ25
±0ꢃ25
±0ꢃ75
±0ꢃ50
±0ꢃ50
±0ꢃ25
±0ꢃ30
±0ꢃ20
±0ꢃ25
±0ꢃ25
°C
0 – 17ꢁ0
-150 – +1370
-170 – +1000
-1ꢂ0 – +1200
-170 – +±00
±00 – 17ꢁ0
200 – 17ꢁ0
0 – 17ꢁ0
32 – 3200
-±5± – +2±9ꢂ
-±5± – +1ꢂ32
-3±ꢁ – +2192
-±5± – +752
212 – 330ꢂ
-5ꢂ – +3200
-5ꢂ – +3200
32 – ±199
K (CA)
-270 – +1370
-270 – +1000
-210 – +1200
-270 – +±00
100 – 1ꢂ20
-50 – +17ꢁ0
-50 – +17ꢁ0
0 – 2315
-23ꢂ – +2±9ꢂ
-27± – +1ꢂ32
-292 – +2192
-27± – +752
752 – 3200
392 – 3200
32 – 3200
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-2ꢁ)
0 – 2315
32 – ±199
N
-270 – +1300
-200 – +ꢁ00
-200 – +900
0 – 1395
-130 – +1300
-200 – +ꢁ00
-200 – +900
0 – 1395
-±5± – +2372
-32ꢂ – +1112
-32ꢂ – +1ꢁ52
32 – 25±3
-202 – +2372
-32ꢂ – +1112
-32ꢂ – +1ꢁ52
32 – 25±3
U
L
P (Platinel ll)
RTD
1
1
*
ACCURACY*
INPUT RANGE
ACCURACY
±0ꢃ20
INPUT RANGE
Pt 100 (JIS ’97, IEC)
Pt 500
-200 – +ꢂ50
-200 – +ꢂ50
-200 – +ꢂ50
-200 – +ꢁ±9
-200 – +510
-50 – +200
-50 – +250
-32ꢂ – +15ꢁ2
-32ꢂ – +15ꢁ2
-32ꢂ – +15ꢁ2
-32ꢂ – +1200
-32ꢂ – +950
-5ꢂ – +392
±0ꢃ3ꢁ
±0ꢃ72
±0ꢃ72
±0ꢃ72
±0ꢃ3ꢁ
±0ꢃ72
±0ꢃ90
±0ꢃ±0
Pt 1000
±0ꢃ±0
Pt 50Ω (JIS ’ꢂ1)
JPt 100 (JIS ’ꢂ9)
Ni 50ꢂꢃ±Ω
±0ꢃ±0
±0ꢃ20
±0ꢃ±0
Cu 10 @25°C
±0ꢃ50
-5ꢂ – +±ꢂ2
*1ꢃ DC input: Value indicated above or ±0ꢃ1% oꢄ span, ꢅhichever is greater
Thermocouple: CJC error margin (2ꢃ0 °C, 3ꢃꢁ °F) added value indicated above or ±0ꢃ1% oꢄ span, ꢅhichever is greater
RTD, Resistor: Value indicated above or ±0ꢃ1% oꢄ span, ꢅhichever is greater
EXTERNAL VIEW
RUN LED
RUN1
AUTO1
ERR1
ALM1
RUN2
AUTO2
ERR2
Loop Status Indicator
ERR LED
ALM2
1
11
2
12
3
13
4
14
5
15
CJC SENSOR(2)
6
16
7
17
8
18
9
19
10
20
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 4/7
http://www.m-system.co.jp/
MODEL: R3-TC2
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
CJC SENSOR (2)
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL COVER
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 5/7
http://www.m-system.co.jp/
MODEL: R3-TC2
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Indicator LEDs
...
Isolation
1
Communication
INTERNAL BUS
Circuit
2
A/D
Converter
Pv1
Control
Circuit
UNIVERSAL INPUT
3
4
INTERNAL POWER
Isolation
Isolation
Isolation
5
6
7
8
9
+
+
–
CT 1
CT 2
A/D
Converter
Mv1
Output
Circuit
Mv2
10
Isolation
11
12
13
14
18
19
20
+
+
–
Do1
Output
Circuit
A/D
Converter
Pv2
Do2
UNIVERSAL INPUT
Isolation
15
16
17
Di 1
Input
Circuit
Di 2
■ UNIVERSAL INPUT CONNECTION (Pv2) e.g.
■ UNIVERSAL INPUT CONNECTION (Pv1) e.g.
■ CT 1 / CT 2 CONNECTION e.g.
•Clamp-on current Sensor
Power Side
•DC Voltage (-10 – +10V DC)
•DC Current (0 – 20mA DC)
•DC Voltage (-10 – +10V DC)
•DC Current (0 – 20mA DC)
k
1
2
11
12
5
+
–
+
–
INPUT
INPUT
l
k
6
l
7
•DC Voltage (-1000 – +1000mV DC)
•DC Voltage (-1000 – +1000mV DC)
Load Side
2
4
12
14
–
+
–
+
INPUT
INPUT
■ DISCRETE INPUT CONNECTION e.g.
•Thermocouple
-
•Thermocouple
-
–
Di 1
15
–
–
+
+
Di2
16
2
3
4
12
13
14
CJC
CJC
SENSOR
SENSOR
17
+
+
comp. leadwire
comp. leadwire
■ CONTROL OUTPUT 1 & 2 CONNECTION e.g.
•RTD/Resistor (3-wire)
•RTD/Resistor (3-wire)
8
9
+
+
–
2
3
4
12
13
14
A
B
B
A
B
B
Mv1
Mv2
10
•RTD/Resistor (2-wire)
•RTD/Resistor (2-wire)
■ CONTROL OUTPUT 3 & 4 CONNECTION e.g.
Do1
2
3
12
13
A
B
A
B
+
–
18
19
20
Do2
+
–
•Potentiometer
•Potentiometer
max.
+
max.
+
2
3
4
12
13
14
–
–
min.
min.
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 6/7
http://www.m-system.co.jp/
MODEL: R3-TC2
SYSTEM CONFIGURATION EXAMPLES
■ 1 loop heating ON/OFF control and heater wire break detection
1. Installation example:
• Base (model: R3–BS)
• Interface Module (model: R3–NM3)
• Temperature Control Module (model: R3–TC2)
• Clamp-on Current Sensor (model: CLSE)
• Oven
• Heater
• Relay
• Temperature sensor
2. Proccess until start operating:
UNIVERSAL INPUT 2 (Pv2)
CT INPUT 1
R3–BS
R3–NM3
R3–TC2
Turn ON power supply
Set input sensor type and range
Set CT input to wire break detection
Select control mode (ON/OFF Control)
Specify target temperature (SP)
Select operation mode (auto)
Start operation
CONTROL OUTPUT 3 (Do1)
Temp. Sensor
Relay Power
Ry
Heater Power
Heater
Relay
CLSE
Oven
■ 1 loop heating and cooling control (PID)
1. Installation example:
• Base (model: R3–BS)
• Power Supply Module (R3–PS1)
• Interface Module (model: R3–NM3)
• Temperature Control Module (model: R3–TC2)
• DC Voltage Input Module (model: R3–SV4)
(Other R3 modules also available)
• Object to heat/cool
• Temperature sensor
R3–BS
2. Proccess until start operating:
UNIVERSAL INPUT 1 (Pv1)
R3–PS1
R3–NM3
R3–TC2
R3–SV4
Turn ON power supply
Set input sensor type and range
Select control mode (PID)
Control output 1 (Mv1)
Control output 2 (Mv2)
Cold water
Temp. Sensor
Set deadband
Specify target temperature (SP)
Select operation mode (auto)
Start operation
Object to
heat/cool
Hot water
Note: The examples above are for single loop, however, dual loop control is also availabe using only one R3-TC2.
Specifications are subject to change without notice.
R3-TC2 SPECIFICATIONS
ES-8468 Rev.3 Page 7/7
http://www.m-system.co.jp/