R3-RS4W/CE [MSYSTEM]
Remote I/O R3 Series RTD INPUT MODULE;型号: | R3-RS4W/CE |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series RTD INPUT MODULE 输入元件 |
文件: | 总4页 (文件大小:132K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-RS4
Remote I/O R3 Series
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
RTD INPUT MODULE
(4 points, isolated)
27.5 [1.08]
Isolation: Input 1 to input 2 to input 3 to input 4 to internal
bus or internal power
Sensor type: Selectable with the side DIP SW
Temperature unit: °C, °F or absolute temperature selectable
with the side DIP SW
130
[5.12]
Conversion rate: Selectable with the side DIP SW
Burnout detection: Upscale or downscale selectable with the
side DIP SW
109
[4.29]
mm [inch]
Linearization: Standard
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with burnout; Green in normal operating conditions.
MODEL: R3-RS4[1][2]
ORDERING INFORMATION
• Code number: R3-RS4[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-RS4W/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
INPUT SPECIFICATIONS
Maximum leadwire resistance: 100 Ω per wire
Sensing current: ≤ 1 mA
Temperature range
NO. OF CHANNELS
4: 4
°C
RTD
USABLE RANGE
CONFORMANCE RANGE
Pt 100 (JIS ’97, IEC)
Pt 100 (JIS ’89)
-240 to +900
-240 to +900
-236 to +560
-200 to +850
-200 to +660
-200 to +510
[1] COMMUNICATION MODE
JPt 100 (JIS ’89)
S: Single
Pt 50Ω (JIS ’81)
Ni 100
-236 to +700
-100 to +252
-212 to +312
-200 to +649
-80 to +250
-50 to +250
W: Dual
Cu 10 @ 25°C
Pt 1000
Ni 508.4Ω
Cu 50
-240 to +900
-100 to +332
-100 to +200
-200 to +850
-50 to +200
-50 to +150
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Ni 1000
-56 to +152
-56 to +152
/CE: CE marking
°F
RTD
Other Options
USABLE RANGE
CONFORMANCE RANGE
blank: none
Pt 100 (JIS ’97, IEC)
Pt 100 (JIS ’89)
-400 to +1652
-400 to +1652
-393 to +1040
-328 to +1562
-328 to +1220
-328 to +950
/Q: Option other than the above (specify the specification)
JPt 100 (JIS ’89)
Pt 50Ω (JIS ’81)
Ni 100
-393 to +1292
-148 to +486
-350 to +594
-328 to +1200
-112 to +482
-58 to +482
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Cu 10 @ 25°C
Pt 1000
Ni 508.4Ω
Cu 50
-400 to +1652
-148 to +630
-148 to +392
-328 to +1562
-58 to +392
-58 to +302
/C02: Polyurethane coating
/C03: Rubber coating
Ni 1000
-69 to +306
-69 to +306
EX-FACTORY SETTING
Max. (upscale) or min. (downscale) value of the usable range when
a burnout is detected.
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8364)
R3-RS4 SPECIFICATIONS
ES-8364 Rev.13 Page 1/4
https://www.m-system.co.jp/
MODEL: R3-RS4
INSTALLATION
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy: ±1.0°C (±1.8°F) except ±3.0°C
(±5.4°F) for Cu 10 @ 25°C
Conversion rate: 250 msec. or 1 sec. selectable
Data range
°C, absolute temperature: Engineering unit value × 10
(integer)
°F: Engineering unit value (integer)
Data allocation: 4
Current consumption: 70 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Burnout response time: ≤ 2 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
■ FRONT VIEW
■ SIDE VIEW
RUN LED
ERR LED
Functions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SW3
ON
SW2
SW1
Conv.
Rate
Temp.
Unit
Burnout
RTD
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)
or
Input 4 (SW2)
Input 1 (SW1)
or
Input 3 (SW2)
ON
ON
R3-RS4 SPECIFICATIONS
ES-8364 Rev.13 Page 2/4
https://www.m-system.co.jp/
MODEL: R3-RS4
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
11
2
20–M3
SCREW
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TERMINAL
COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Input Circuit
RTD
INTERNAL BUS A
Communication
Circuit
A
1
INTERNAL BUS B*
INPUT 1
B
B
2
11
12
3
Control
Circuit
INTERNAL POWER
Input Circuit
Input Circuit
Input Circuit
RTD
RTD
RTD
A
B
B
5
INPUT 2
INPUT 3
INPUT 4
4
10
15
20
13
14
6
A
B
B
7
16
17
8
A
B
B
9
18
19
*For dual redundant communication.
• Unused Input Channels
Close across the unused input terminals with a resistor as shown
below and set the DIP switch for Pt 100 input.
INPUT 1
1
INPUT 2
3
INPUT 3
6
INPUT 4
8
100Ω
2
4
7
9
11
13
16
18
Unused channels left open are equal to the burnout, which turns
the red ERR LED on and sets a burnout flag at the PLC or the
host device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to connect
resistors at the field terminals.
R3-RS4 SPECIFICATIONS
ES-8364 Rev.13 Page 3/4
https://www.m-system.co.jp/
MODEL: R3-RS4
Specifications are subject to change without notice.
R3-RS4 SPECIFICATIONS
ES-8364 Rev.13 Page 4/4
https://www.m-system.co.jp/