R3-NL1-L3 [MSYSTEM]
Remote I/O R3 Series LonWorks INTERFACE MODULE;型号: | R3-NL1-L3 |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series LonWorks INTERFACE MODULE |
文件: | 总5页 (文件大小:152K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-NL1
Remote I/O R3 Series
RELATED PRODUCTS
• XIF File (Device Interface File)
XIF file is used to define a LonWorks device when
programmed on LonMaker.
LonWorks INTERFACE MODULE
(analog I/O 16 points, discrete I/O 48 points)
27.5 (1.08)
GENERAL SPECIFICATIONS
Connection
LonWorks: Euro type connector terminal
130
(5.12)
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
Internal bus: Via the Installation Base
(model: R3-BSx)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
109
(4.29)
mm (inch)
Screw terminal: Nickel-plated steel
Isolation: LonWorks to internal bus or internal power to
power input to RUN contact output to FG
Input error data setting: Input value setting at input module
error with side DIP SW
MODEL: R3–NL1–[1][2]
ORDERING INFORMATION
• Code number: R3-NL1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NL1-R/Q)
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN indicator: Bi-color (green/red) LED; Green ON in
communications with another device online or changing the
output data (turns off after 25 seconds of no
communication); Red ON when receiving data (function
selected with DIP SW)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
N: No power supply
ERR indicator: Bi-color (green/red) LED; Green ON or
blinking at communication error; Red ON at transmitting
data (Function selected with DIP SW)
AC Power
K3: 100 – 120 V AC
■ RUN CONTACT OUTPUT
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
L3: 200 – 240 V AC
RUN contact: Turns on while the green RUN LED is ON
(LonWorks in normal communication)
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
DC Power
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
R: 24 V DC
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When
7
driving an inductive load, external contact protection and
noise quenching recommended.
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
LonWorks COMMUNICATION
Neuron Chip: FT3120 (NeuronID printed in numbers and bar
code [peel-off code 39 format])
Transceiver: FT-X1 (equivalent to FTT10A)
Transmission speed: 78 kbps
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Twisted-pair cable
/C02: Polyurethane coating
Distance, free topology: 500 meters
Max. 64 nodes/channel
/C03: Rubber coating
LNS: Ver. 3.0 Service Pack 8 or higher
Network variable type
R3-NL1 SPECIFICATIONS
ES-8427 Rev.10 Page 1/5
http://www.m-system.co.jp/
MODEL: R3-NL1
Analog: SNVT_lev_percent or SNVT_temp (selectable)
Discrete: SNVT_switch
ONLINE indicator: Red LED
ON: Off-line or no network information (decommissioned)
Blinking in approx. 0.5 Hz: On-line
(ready to communicate network variables)
Blinking in approx. 5 Hz for 30 sec.: Wink message received
SERVICE indicator: Green LED
OFF: Normal operations
Blinking in approx. 0.5 Hz: No network information
ON: Internal program error
SERVICE switch: Used to identify the node in LonWorks
network configuration
RESET switch: Resetting the Neuron Chip
Numbers of data (*factory setting)
Analog Input
Analog Output
16
0
12
4
8 (*)
8 (*)
4
12
0
16
Discrete Input
Discrete Output
0
48
0
48
INSTALLATION
Power consumption
•AC: Approx. 20 VA
•DC: Approx. 12 W
Current consumption (no power supply): 100 mA
Output current (power supply): 250 mA continuous at 20 V
DC; 400 mA for 10 minutes
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (LonWorks or
internal bus or internal power to power input to RUN contact
output to FG)
R3-NL1 SPECIFICATIONS
ES-8427 Rev.10 Page 2/5
http://www.m-system.co.jp/
MODEL: R3-NL1
EXTERNAL VIEW
FRONT VIEW
SIDE VIEW
ONLINE LED
SERVICE LED
SERVICE SW
RESET SW
RUN LED
ERR LED
DIP SW
SW3
ON
SW2
SW1
1
2
3
4
5
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Configuration Jack
Euro Type
Connector Terminal
1
2
3
4
5
6
ON
ON
COMMUNICATION CABLE CONNECTIONS
HOST PC
R3-NLx
R3-NLx
LONWORKS
LONWORKS
LONWORKS
Terminator
TRANSMISSION DATA DESCRIPTIONS
The DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area).
Data are assigned in turn from Slot 1, in order of Functional Blocks (Input or GetValue/R3Di first, followed by Output or
SetValue/R3Do).
The 1st output must be the 1st transmitted data in the slot next to the one with the last input data.
[Example 1]
Data Area
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
Module 7
Module 8
Module 9
Module 10
4
4
4
1
1
1
1
1
1
1
GetValue [0 – 3]
GetValue [4 – 7]
SetValue [0]
SetValue [1]
SetValue [2]
SetValue [3]
SetValue [4]
SetValue [5]
SetValue [6]
SetValue [7]
[Example 2]
Data Area
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
1
4
4
1
4
4
GetValue [0]
GetValue [1 – 4]
GetValue [5 – 7] The 4th data, Slot 3 is invalid.
SetValue [0]
SetValue [1 – 4]
SetValue [5 – 7] The 4th data, Slot 6 is invalid.
When the data consist of only inputs or outputs, data for the total of 16 Functional Blocks (GetValue [0 – 15] or R3Di [0 – 2], or
SetValue [0 – 15] or R3Do [0 – 2]) are assigned to each module position from Slot 1.
R3-NL1 SPECIFICATIONS
ES-8427 Rev.10 Page 3/5
http://www.m-system.co.jp/
MODEL: R3-NL1
I/O COMBINATIONS
A dedicated Device File for each I/O device depending upon I/O combinations is required using an integration tool such as Lon
Maker.
On-line download is available for Device Image files at M-System's homepage.
Functional Blocks usable for respective files are not identical to all. Refer to the manual.
■ANALOG INPUT / OUTPUT
NO. of DATA
DEVICE IMAGE
(APB FILE)
USABLE FUNCTIONAL BLOCKS
INPUT OUTPUT
16
12
8
0
4
R3NL1_1_101.APB NodeObjet, GetValue [0 ... 15] (Can be defined from 0 to 15)
R3NL1_2_101.APB NodeObjet, GetValue [0 ... 11], SetValue [0 ... 3]
R3NL1_3_101.APB NodeObjet, GetValue [0 ... 7], SetValue [0 ... 7]
R3NL1_4_101.APB NodeObjet, GetValue [0 ... 3], SetValue [0 ... 11]
R3NL1_5_101.APB NodeObjet, SetValue [0 ... 15]
8
4
12
16
0
■DISCRETE INPUT / OUTPUT
NO. of DATA
DEVICE IMAGE
(APB FILE)
USABLE FUNCTIONAL BLOCKS
INPUT OUTPUT
0
48
0
R3NL1_6_101.APB NodeObjet, R3Do [0 ... 2] (One (1) block can handle 16 contacts.)
R3NL1_7_101.APB NodeObjet, R3Di [0 ... 2]
48
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
1
2
3
4
5
6–M3
SCREW
1
4
2
5
3
6
TERMINAL
COVER
R3-NL1 SPECIFICATIONS
ES-8427 Rev.10 Page 4/5
http://www.m-system.co.jp/
MODEL: R3-NL1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Caution: FG terminal is NOT a protective conductor terminal.
ONLINE/SERVICE LED RUN/ERR LED
LONWORKS
Control
Circuit
Communication
Circuit
1
2
3
4
5
INTERNAL BUS
Transceiver
FT-X1
Neuron
Chip
FT3120
DIP SW
SERVICE SW
RESET SW
INTERNAL POWER
1
4
2
3
6
RUN +
RUN CONTACT OUTPUT
5
RUN –
*
U (+)
*
POWER INPUT
V (–)
*
FG
JACK
*Not provided with ‘No Power Supply’ type module.
CONFIGURATION JACK
Specifications are subject to change without notice.
R3-NL1 SPECIFICATIONS
ES-8427 Rev.10 Page 5/5
http://www.m-system.co.jp/