R3-AV8S/Q [MSYSTEM]
Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE;型号: | R3-AV8S/Q |
厂家: | M-SYSTEM |
描述: | Remote I/O R3 Series DC VOLTAGE INPUT ALARM MODULE 输入元件 |
文件: | 总4页 (文件大小:138K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R3-AV8
Remote I/O R3 Series
CAUTION
■UNUSED INPUT CHANNELS
Set the unused channels to the ranges other than 1 - 5 V.
Otherwise, set them as "Unused" with PC Configurator
software: R3CON. Unused channels left open with 1 – 5 V
setting are equal to the input lower than -15 %, which sets a
data abnormality at the PLC or the host device.
Open circuit with the input range set to ±10 V means 50 %
of the full-scale. An alarm setpoint must be set to a value
that does not trip an unwanted alarm.
DC VOLTAGE INPUT ALARM MODULE
(8 points, isolated)
27.5 [1.08]
130
[5.12]
GENERAL SPECIFICATIONS
Connection
109
[4.29]
Internal bus: Via the Installation Base (model: R3-BSx)
Input: M3 separable screw terminal (torque 0.5 N·m)
Internal power: Via the Installation Base (model: R3-BSx)
Screw terminal: Nickel-plated steel
mm [inch]
MODEL: R3–AV8[1][2]
Isolation: Input 1 to input 2 to input 3 to input 4 to input 5 to
input 6 to input 7 to input 8 to internal bus or internal power
Input range: Selectable with the side DIP SW (per 4
channels)
ORDERING INFORMATION
• Code number: R3-AV8[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-AV8W/CE/Q)
Conversion rate: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD converter response
failure);
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
8: 8
Green in normal operating conditions.
[1] COMMUNICATION MODE
S: Single
W: Dual
INPUT SPECIFICATIONS
■ Narrow Span: -1 – +1 V, 0 – 1 V DC
Input resistance: 100 kΩ min.
■ Wide Span: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
Input resistance: 1 MΩ min.
/CE: CE marking
Other Options
blank: none
INSTALLATION
/Q: Option other than the above (specify the specification)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 250 g (0.55 lb)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
R3-AV8 SPECIFICATIONS
ES-8436 Rev.7 Page 1/4
https://www.m-system.co.jp/
MODEL: R3-AV8
The alarm output start functioning in the preset time after
the power has been turned on.
PERFORMANCE
Conversion accuracy: Refer to the table at the end of this
This setting is common to all 8 points.
■ALARM HOLD TIME
section.
Conversion rate: 160 / 80 / 40 / 20 msec. selectable
Data range: 0 – 10000 of the input range
Data allocation: 4
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is
reset in shorter time.
Current consumption: 100 mA
This setting is common to all 8 points.
Temp. coefficient: ±0.015 % /°C (±0.008 %/°F)
(±0.03 % /°C [±0.02 %/°F] with 0 – 5 V or 1 – 5 V range)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @ 1 minute (input 1 to input
2 to input 3 to input 4 to input 5 to input 6 to input 7 to
input 8 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module)
Conversion accuracy
RATE
160 msec. 80 msec. 40 msec. 20 msec.
RANGE
All ranges
0.1ꢀ
0.2ꢀ
0.4ꢀ
0.8ꢀ
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
ALARM SETTING
The following parameters are programmable using the PC
Configurator Software (model: R3CON).
■ALARM TRIP POINT (-15.00 to +115.00 %;
factory set to A1: 80.00, A2: 60.00, A3: 40.00, A4: 20.00)
Four alarm setpoints are selectable per each input.
■ALARM TYPE
(High or Low; factory set to A1: High, A2: High, A3: Low,
A4: Low)
High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes
above the setpoint.
Low alarm: An alarm is set when the input signal goes below
the setpoint.
■DEADBAND (HYSTERESIS)
(0.00 to 100.00 %; factory set to 5.00)
Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.
■ALARM ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all 8 points.
■POWER ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 5.0)
R3-AV8 SPECIFICATIONS
ES-8436 Rev.7 Page 2/4
https://www.m-system.co.jp/
MODEL: R3-AV8
EXTERNAL VIEW
■ SIDE VIEW
■ FRONT VIEW
RUN LED
ERR LED
1
2
15
16
17
18
19
20
21
22
23
24
25
26
27
28
3
4
Functions
Range
5
SW1
SW2
SW3
ON
6
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
Conv.
Rate
Input 1-4 (SW1)
or
Input 5-8 (SW2)
8
9
10
11
12
13
14
ON
ON
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. Two (2) word (16 bits × 2) data is transmitterd to the PLC or the host device
via the R3 network module.
15
0
15
0
0
+1
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
27.5 [1.08]
109 [4.29]
POSITIONING
GUIDE
1
15
2
16
3
17
4
18
5
19
6
28–M3
SCREW
20
7
21
8
22
9
23
10
24
11
25
12
26
13
27
14
28
TERMINAL
COVER
R3-AV8 SPECIFICATIONS
ES-8436 Rev.7 Page 3/4
https://www.m-system.co.jp/
MODEL: R3-AV8
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RUN LED ERR LED DIP SW
Input Circuit
INTERNAL BUS A
Communication
Circuit
1
2
+
+
–
+
+
–
+
+
–
+
+
–
+
+
–
+
+
–
+
+
–
+
+
–
INTERNAL BUS B*
WIDE SPAN
NARROW SPAN
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
Control
Circuit
3
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
Input Circuit
INTERNAL POWER
4
WIDE SPAN
NARROW SPAN
5
13
14
27
28
6
7
WIDE SPAN
NARROW SPAN
8
9
10
11
12
15
16
17
18
19
20
21
22
23
24
25
26
WIDE SPAN
NARROW SPAN
WIDE SPAN
NARROW SPAN
WIDE SPAN
NARROW SPAN
WIDE SPAN
NARROW SPAN
WIDE SPAN
NARROW SPAN
*For dual redundant communication.
Note: Connect either wide or narrow span terminals for each channel.
Specifications are subject to change without notice.
R3-AV8 SPECIFICATIONS
ES-8436 Rev.7 Page 4/4
https://www.m-system.co.jp/