R3-AR4W [MSYSTEM]

Remote I/O R3 Series RTD INPUT ALARM MODULE;
R3-AR4W
型号: R3-AR4W
厂家: M-SYSTEM    M-SYSTEM
描述:

Remote I/O R3 Series RTD INPUT ALARM MODULE

输入元件
文件: 总4页 (文件大小:134K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: R3-AR4  
Input: M3 separable screw terminal (torque 0.5 N·m)  
Internal power: Via the Installation Base (model: R3-BSx)  
Screw terminal: Nickel-plated steel  
Remote I/O R3 Series  
RTD INPUT ALARM MODULE  
(4 points, isolated)  
Isolation: Input 1 to input 2 to input 3 to input 4 to internal  
bus or internal power  
Sensor type: Selectable with the side DIP SW  
Temperature unit: °C, °F or absolute temperature selectable  
with the side DIP SW  
27.5 [1.08]  
Conversion rate: Selectable with the side DIP SW  
Burnout detection: Upscale or downscale selectable with the  
side DIP SW  
130  
[5.12]  
Linearization: Standard  
RUN indicator: Bi-color (red/green) LED;  
Red when the bus A operates normally;  
Green when the bus B operates normally;  
Amber when both buses operate normally.  
ERR indicator: Bi-color (red/green) LED;  
Red with burnout; Green in normal operating conditions.  
109  
[4.29]  
mm [inch]  
MODEL: R3-AR4[1][2]  
ORDERING INFORMATION  
• Code number: R3-AR4[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-AR4W/CE/Q)  
INPUT SPECIFICATIONS  
Maximum leadwire resistance: 100 Ω per wire  
Sensing current: ≤ 1 mA  
Temperature range  
• Specify the specification for option code /Q  
(e.g. /C01)  
USABLE RANGE  
RTD  
°C  
°F  
Pt 100 (JIS ’97, IEC)  
Pt 100 (JIS ’89)  
JPt 100 (JIS ’89)  
Pt 50Ω (JIS ’81)  
Ni 100  
-200 to +850  
-200 to +660  
-200 to +510  
-200 to +649  
-80 to +250  
-50 to +250  
-200 to +850  
-50 to +200  
-50 to +150  
-328 to +1562  
-328 to +1220  
-328 to +950  
-328 to +1200  
-112 to +482  
-58 to +482  
-328 to +1562  
-58 to +392  
-58 to +302  
NO. OF CHANNELS  
4: 4  
Cu 10 @ 25°C  
Pt 1000  
[1] COMMUNICATION MODE  
S: Single  
Ni 508.4Ω  
W: Dual  
Cu 50  
Max. (upscale) or min. (downscale) value of the usable range  
when a burnout is detected.  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
INSTALLATION  
/CE: CE marking  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R3-BSx)  
Weight: 200 g (0.44 lb)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
GENERAL SPECIFICATIONS  
Connection  
Internal bus: Via the Installation Base (model: R3-BSx)  
R3-AR4 SPECIFICATIONS  
ES-8433 Rev.7 Page 1/4  
https://www.m-system.co.jp/  
MODEL: R3-AR4  
This setting is common to all four points.  
PERFORMANCE  
Conversion accuracy: ±1.0°C (±1.8°F) except ±3.0°C  
ALARM HOLD TIME  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is held for the preset time even if it is  
reset in shorter time.  
(±5.4°F) for Cu 10 @ 25°C  
Conversion rate: 250 msec. or 1 sec. selectable  
Data allocation: 1  
This setting is common to all four points.  
Current consumption: 70 mA  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Burnout response time: ≤ 2 sec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input  
2 to input 3 to input 4 to internal bus or internal power)  
2000 V AC @ 1 minute (power input to FG; isolated on the  
power supply module)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
ALARM SETTING  
The following parameters are programmable using the PC  
Configurator Software (model: R3CON).  
■ALARM TRIP POINT  
(-200.0 to +850.0°C or -328 to +1562°F;  
factory set to A1: 400.0°C, A2: 300.0°C, A3: 200.0°C,  
A4: 100.0°C)  
Four alarm setpoints are selectable per each input.  
ALARM TYPE  
(High or Low; factory set to A1: High, A2: High, A3: Low,  
A4: Low)  
High or Low alarm is selectable for each alarm trip point.  
High alarm: An alarm is set when the input signal goes  
above the setpoint.  
Low alarm: An alarm is set when the input signal goes below  
the setpoint.  
DEADBAND (HYSTERESIS)  
(0.0 to 1000.0°C or 0 to 1800°F; factory set to 10.0°C or  
100°F)  
Deadband (deviation between the points where the alarm is  
set and reset) is selectable for each alarm trip point.  
ALARM ON DELAY TIME  
(0.0 to 99.0 seconds; factory set to 1.0)  
The alarm output is set when the preset time elapses after  
the input has entered in the alarm range.  
This setting is common to all four points.  
POWER ON DELAY TIME  
(0.0 to 99.0 sec.; factory set to 5.0)  
The alarm output start functioning in the preset time after  
the power has been turned on.  
R3-AR4 SPECIFICATIONS  
ES-8433 Rev.7 Page 2/4  
https://www.m-system.co.jp/  
MODEL: R3-AR4  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
RUN LED  
ERR LED  
Functions  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
SW3  
ON  
SW2  
SW1  
Conv.  
Rate  
Temp.  
Unit  
Burnout  
RTD  
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
Input 2 (SW1)  
or  
Input 4 (SW2)  
Input 1 (SW1)  
or  
Input 3 (SW2)  
ON  
ON  
OUTPUT DATA DESCRIPTIONS  
Four alarm setpoints are selectable per each input. One (1) word (16 bit) data is transmitterd to the PLC or the host device via  
the R3 network module.  
15  
0
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Input 1  
Input 2  
Input 3  
Input 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
Alarm 1  
Alarm 2  
Alarm 3  
Alarm 4  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
27.5 [1.08]  
109 [4.29]  
POSITIONING  
GUIDE  
1
11  
2
20–M3  
SCREW  
12  
3
13  
4
14  
5
15  
6
16  
7
17  
8
18  
9
19  
10  
20  
TERMINAL  
COVER  
R3-AR4 SPECIFICATIONS  
ES-8433 Rev.7 Page 3/4  
https://www.m-system.co.jp/  
MODEL: R3-AR4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
RUN LED ERR LED DIP SW  
Input Circuit  
RTD  
INTERNAL BUS A  
Communication  
Circuit  
A
1
INTERNAL BUS B *  
INPUT 1  
B
B
2
11  
12  
3
Control  
Circuit  
INTERNAL POWER  
Input Circuit  
Input Circuit  
Input Circuit  
RTD  
RTD  
RTD  
A
B
B
5
INPUT 2  
INPUT 3  
INPUT 4  
4
10  
15  
20  
13  
14  
6
A
B
B
7
16  
17  
8
A
B
B
9
18  
19  
*For dual redundant communication.  
• Unused Input Channels  
Close across the unused input terminals with a resistor as  
shown below and set the DIP switch for Pt 100 input.  
INPUT 1  
1
INPUT 2  
3
INPUT 3  
6
INPUT 4  
8
100Ω  
2
4
7
9
11  
13  
16  
18  
Unused channels left open are equal to the burnout,  
which turns the red ERR LED on and sets a burnout flag at the  
PLC or the host device.  
Connecting the resistor means approx. 0°C. An alarm setpoint  
must be set to a value that does not trip an unwanted alarm.  
Unused channels can be specified and set so on the PC  
Configurator Software (model: R3CON) without needing to  
connect resistors at the field terminals.  
Specifications are subject to change without notice.  
R3-AR4 SPECIFICATIONS  
ES-8433 Rev.7 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

R3-AR4W/CE

Remote I/O R3 Series RTD INPUT ALARM MODULE
MSYSTEM

R3-AR4W/Q

Remote I/O R3 Series RTD INPUT ALARM MODULE
MSYSTEM

R3-AS4

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4S

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4S/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4S/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS4W/Q

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8S

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM

R3-AS8S/CE

Remote I/O R3 Series DC CURRENT INPUT ALARM MODULE
MSYSTEM