MSP5C2-17E-0R [MSYSTEM]
Final Control Elements MINI-TOP ELECTRONIC ACTUATOR;型号: | MSP5C2-17E-0R |
厂家: | M-SYSTEM |
描述: | Final Control Elements MINI-TOP ELECTRONIC ACTUATOR |
文件: | 总5页 (文件大小:183K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MSP5C2
Final Control Elements
[3] OUTPUT STEM TYPE
6: M6 female thread, 0.75 pitch
8: M8 female thread, 1.0 pitch
1: M10 female thread, 1.25 pitch
D: M6 female thread, 1.0 pitch
E: M8 female thread, 1.25 pitch
F: M10 female thread, 1.5 pitch
MINI-TOP ELECTRONIC ACTUATOR
(linear type; CC-Link)
Functions & Features
• Small-size control valve actuator
• Direct connection to CC-Link capable PLC and other
devices on the same network
• Easy wired
CE MARKING
• Uploading device information via CC-Link for maintenance
purpose
0: Without
• 1/1000 high resolution
POWER INPUT
DC Power
• Easy adjustment: electronic limiter at the valve open &
closed positions
R: 24 V DC
• Overload protection
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Seal-spring incorporated for both directions; usable with
three-way valves
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
Typical Applications
• For CP control valve in paper manufacturing
• Fuel mixing control for combustion control system
• Air conditioning for buildings and factories
GENERAL SPECIFICATIONS
Degree of protection: IP66
Operation at a communication error: Extend, retract or stop
Electrical connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Transmission cable: Conforms to CC-Link Ver 1.10
Housing material: Diecast aluminum
(Cast aluminum for the terminal box; steel for the cover)
Drive: Stepping motor
Insulation class: E
Position detection: Potentiometer
Deadband: 0.1 – 1.9 % adjustable (factory set to 1.5 %)
Restarting timer: 0 – 10 sec. adjustable
(factory set to 1.5 sec.)
MODEL: MSP5C2–[1][2][3]–0R
Isolation: Housing or FE1 to communication to power
Zero adjustment: 0 – 25 %
ORDERING INFORMATION
• Code number: MSP5C2-[1][2][3]-0R
Specify a code from below for each of [1] through [3].
(e.g. MSP5C2-131-0R)
Span adjustment: 50 - 100 %
Protective functions: Overload protection
Status indicator LED: Red light blinks in 2 sec. intervals in
normal operations; blinks in 0.5 sec. intervals when a
foreign object is detected mechanically caught inside.
Manual operating handle: Not available
[1] STROKE
1: 5 to 10 mm (.20” to .39”)
3: 10 to 20 mm (.39” to .79”)
CC-Link COMMUNICATION
Protocol: CC-Link V1.10
Device type: Remote device station
Station No. setting: Rotary switch; 1 – 64
Required node: 1
[2] OPERATION TIME, THRUST
3: 5 sec. / 10 mm, 150 N
4: 9 sec. / 10 mm, 300 N
Baud rate setting: Rotary switch
L RUN indicator: Red LED
7: 18 sec. / 10 mm, 700 N
L ERR. indicator: Red LED
MSP5C2 SPECIFICATIONS
ES-4860 Rev.2 Page 1/5
http://www.m-system.co.jp/
MODEL: MSP5C2
INSTALLATION
Current consumption
•DC: Approx. 0.5 A
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: 0.5 G (4.9 m/s ) max.
2
Mounting position: All directions
Do not mount the actuator with its output stem or wiring
conduit on the upside if the actuator is to be exposed to
dripping water.
Weight: 1.8 kg (4.0 lb)
PERFORMANCE
Resolution: 1/1000 or 0.015 mm, whichever is greater, with
0.1 % deadband setting
Insulation resistance: ≥ 100 MΩ with 100 V DC
Dielectric strength: 100 V AC @ 1 minute
(housing or FE1 to communication to power)
MSP5C2 SPECIFICATIONS
ES-4860 Rev.2 Page 2/5
http://www.m-system.co.jp/
MODEL: MSP5C2
COMMUNICATIONS
■MASTER to SLAVE
DATA TYPE ADDRESS FUNCTION
DETAIL
RY0
RY1
RY2
RY3
RY4
RY5
RY6
RY7
RY8
RY9
RYA
RYB
RYC
RYD
RYE
RYF
RWw0
Forced Closed Position Input *1
Forced Open Position Input *1
0 : Disable 1 : Position = 0%
0 : Disable 1 : Position = 100%
Bit
Enable Target Position Input
0 : Disable 1 : Enable
Reset Motor Deadlock Alarm
Clear Motor Starting Counter
Clear Motor Reversing Counter
Motor deadlock alarm is cancelled when ‘1’ is set.
Motor starting counter is reset to 0 when ‘1’ is set.
Motor reversing counter is reset to 0 when ‘1’ is set.
Clear Accumulated Running Distance Accumulated running distance is reset to 0 when ‘1’ is set.
Target Position Input
Signed, 0.01% increments (e.g. 100 = 1.00%)
Valid only when Enable Target Position Input is enabled.
Word
RWw1
RWw2
RWw3
*1. Valid regardless of the RY8 (Enable Target Position Input) status. Stopped when ‘1’ is set both at RY0 and RY1.
■SLAVE to MASTER
DATA TYPE ADDRESS FUNCTION
DETAIL
RX0
RX1
RX2
RX3
RX4
RX5
RX6
Bit
RX7
RX8
Motor Deadlock Alarm
Target Position Input Error
System Error
0 : Normal 1 : Overload or other deadlock alarm
0 : Normal 1 : Out of range from -0.5 to +100.5%
0 : Normal 1 : Memory or other system error
0 : Remote (CC-Link) 1 : Manual
RX9
RXA
RXB
RXC
RXD
RXE
RXF
RWr0
RWr1
RWr2
RWr3
Control Status
Position Output
Signed, 0.01% increments (e.g. 100 = 1.00%)
1 count per every 100 starting actions
Word
Motor Starting Counter *2
Motor Reversing Counter *2
Accumulated Running Distance (%)
1 count per every 100 reversing actions
1 count per running 100% distance every time
2
*
*2. When the count reaches 65535, the value is held until it is reset.
MSP5C2 SPECIFICATIONS
ES-4860 Rev.2 Page 3/5
http://www.m-system.co.jp/
MODEL: MSP5C2
EXTERNAL DIMENSIONS unit: mm (inch)
42 (1.65)
118 (4.65)
[73 (2.87)]
4–M5 10 (.39) deep
[45(1.77)]
Bottom View
[22 (.86)]
96 (3.78)
Terminal Box
M3
Terminal Box Cover
5.9 (.23)
*
4ーG 1/2 (Cable soket)
(See the stem size table)
YOKE SURFACE
M
0
12-0.25
0
36–0.1 dia.
66 (2.60) dia.
*
Max. 40 (1.57) for the stroke 5 – 10 m
OUTPUT STEM HOLE SIZE M
CODE
DIA.
M 6
M 8
M10
M 6
M 8
M10
PITCH DEPTH
6
8
0.75
1.0
1
1.25
1.0
15
D
E
F
1.25
1.5
MSP5C2 SPECIFICATIONS
ES-4860 Rev.2 Page 4/5
http://www.m-system.co.jp/
MODEL: MSP5C2
SCHEMATIC CIRCUITRY
DIP SW
INDICATOR LED
Isolation
STEPPING MOTOR
DA
Comm.
Circuit
Motor
Driver
M
DG
DB
To other CC-Link Devices
CPU
Monitoring
SLD
FE
Z
S
Position
Detector
POT
+
–
24V
GND
FE1
Power
Circuit
Specifications are subject to change without notice.
MSP5C2 SPECIFICATIONS
ES-4860 Rev.2 Page 5/5