MDW5ALW [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDW5ALW |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总5页 (文件大小:126K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDW5ALW
DC Power
Lightning Surge Protectors for
Electronics Equipment M-RESTER
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
LIGHTNING SURGE PROTECTOR FOR
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
LonWorks
(life monitor)
APPLICABLE NETWORK
LonWorks FTT-10A network
Functions & Features
• Designed specifically for the network
• Life monitor function helps you to decide when you should
replace the surge protector
This unit is not applicable to LonWorks Link Power network.
GENERAL SPECIFICATIONS
Construction: Plug-in
• LED and alarm contact output indicate the degradation
and life span of the surge protection circuits
• Easy maintenance thanks to discharge elements installed
on the element module
Degree of protection: IP20 (If the solderless terminals are
covered with insulation tubes.)
Surge protection type: Two-port SPD
Connection
• No interruption of signal even unplugging head element
• DIN rail mounting
• Transmission, power & grounding: M3 screw terminals
(torque 0.8 N·m)
45 (1.78)
• Alarm output: Euro Type Connector Terminal
(torque 0.6 N·m)
Applicable wire size
Line, communication: See the 'External Dimensions.'
97 (3.82)
Alarm output: 0.2 to 2.5 mm2, stripped length 7 mm
Screw terminal
• Transmission, power & grounding: Nickel-plated steel
• Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Indicators
89 (3.5)
mm (inch)
• ALM: Green/Amber/Red tricolor LED
OFF when no surge is detected.
HEAD ELEMENT
MODEL: MDW5ALW–E
Green ON when surge is detected more than once.
Amber ON when element life is about to expire.
(Prepare to replace)
BASE
Red ON when element life is expired or deteriorated
or internal battery is drained. (Replace)
• PWR: Green LED
MODEL: MDW5ALW–B–[1]
ORDERING INFORMATION
Order the both pieces of this surge protector (the head
element and the base), respectively required for the use.
Order the pieces by separate only for replacement.
• Head element
ON when power is supplyed.
OFF when the base power circuit is in error.
Degradation judged: When the leakage current at the
voltage limiter exceeds approx. 100 μA
Life time judged: When the number of discharges of the
discharge element reaches the expected life span.
Alarm contact: Relay N.C contact
Code number: MDW5ALW-E
• Base
Code number: MDW5ALW-B-[1]
Specify a code from below for [1].
(e.g. MDW5ALW-B-R)
• Element error: ON when life span of the discharge
element has expired, the voltage limiter is degraded,
battery drain or element is removed.
• Base error: ON with power circuit error or power supply
failure
[1] POWER INPUT
AC Power
Rated load: 250 V AC @ 1 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
M2: 100 – 240 V AC (Operational voltage range 90 – 264 V,
47 – 66 Hz)
Maximum switching voltage: 264 V AC or 125 V DC
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 1/5
http://www.m-system.co.jp/
MODEL: MDW5ALW
Maximum switching power: 250 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Battery: Lithium battery built in the element, used for life
time judgement. No recharge or replacement available.
Battery life: ≥ 10 years
INSTALLATION
Power consumption
•AC: Approx. 2 VA at 100 V
Approx. 3 VA at 200 V
Approx. 4 VA at 240 V
•DC: ≤ 2 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 160 g (0.35 lb)
PERFORMANCE
Max. continuous operating voltage (Uc):
Line to line: ±1.5 V
Line to earth: ±100 V
SHLD to earth: ±160 V
Voltage protection level (Up):
@ 4 kV (1.2/50 μsec.)
Line to line: ±30 V
Line to earth: ±370 V
SHLD to earth: ±800 V
Response time:
Line to line: ≤ 4 nsec.
Line or SHLD to earth: ≤ 20 nsec.
Leakage current
(@ max. continuous operating voltage)
Line to line: ≤ 50 μA
Line to earth: ≤ 20 μA
SHLD to earth: ≤ 5 μA
Max. discharge current (Imax): 10 kA (8/20 μsec.), 1.0 kA
(10/350 μsec.)
Nominal current (I ): 100 mA
N
Insulation resistance: ≥ 100 MΩ with 500 V DC
(surge protector circuit to alarm contact to power)
Dielectric strength: 2000 V AC @ 1 minute
(surge protector circuit to alarm contact to power)
Internal series resistance: ≤ 3.8 Ω (including return)
≤ 4.2 Ω (for only base, including return)
AC durability: 1 Arms (60 Hz 1 sec.) 5 times
Capacitance @ 1 MHz:
Line to line: Approx. 100 pF
Line to earth: Approx. 100 pF
SHLD to earth: Approx. 100 pF
Surge protection: IEC 61643-21 Categories C1, C2
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 2/5
http://www.m-system.co.jp/
MODEL: MDW5ALW
EXTERNAL VIEW
Alarm Contact Terminal
Power LED
1
2
3
4
5
Alarm LED
6
7
8
9 10 11
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7.4 (.29)
5–M3 TERMINAL SCREW
89 (3.5)
17.5 (.69)
5.3 (.21)
Alarm Contact Terminal
BASE
1
2
3
4
5
DIN RAIL
35mm wide
6 (.27)
HEAD ELEMENT
6
7
8
9
10 11
9.8 (.39)
45 (1.77)
41 (1.61)
55 (2.17)
3.3 (.13)
5.3 (.21)
6–M3 TERMINAL SCREW
• When mounting, no extra space is needed between units.
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 3/5
http://www.m-system.co.jp/
MODEL: MDW5ALW
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ CONNECTION DIAGRAM
HEAD ELEMENT
Discharge
Element
Discharge
Element
Voltage
Limiter
Leakage
Current
Detector
Alarm
LED
Voltage
Limiter
Battery 3V
Comparation
Circuit
Counter
PROTECTED
Protected Device
SIDE
*1
SURGE SIDE
BASE
+
–
1
2
3
4
5
6
7
Series Resistance
*2
*3
NET A, B
U
V
Communication
8
SHLD
*3
Surge Protector for
Power Supply Line
9
G
U(+)
G
5V
10
11
u
v
U
V
To
POWER
POWER
V(–)
12V
Power LED
A1
A2
G
ALARM OUTPUT
Voltage Monitoring
Cross Wiring
Grounding
*1. Be sure to use twisted-pair cables.
*2. No polarity.
*3. With shielded twisted-pair cables, connect the shield of the cable to the ‘3’ terminal of the M-Rester for floating, and with the ‘4’ terminal for grounding.
Follow instructions provided with the protected device whether ‘8’ and ‘9’ terminals should be connected or not.
However, if the shield terminal of the protected device is not isolated from NET A / B, DO NOT connect ‘8’ and ‘9’ terminals to the protected device.
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 4/5
http://www.m-system.co.jp/
MODEL: MDW5ALW
■ NETWORK CONFIGURATION
P ꢃepꢁ/ꢁC ꢂiꢃet
M-RESTER
SurgeꢁSide
ProtectedꢁSide
NetꢄorꢅꢁC ꢂpe
NetꢄorꢅꢁC ꢂpe
CrossoverꢁWire
G
G
G
Protected
Devices
(Nodes)
Grouꢃdiꢃg
P ꢃepꢁ/ꢁC ꢂiꢃet
M-RESTER
SurgeꢁSide
ProtectedꢁSide
NetꢄorꢅꢁC ꢂpe
CrossoverꢁWire
G
G
G
Protected
Devices
(Nodes)
•TꢀeꢁM-RESTERꢁisꢁ aapic ꢂpeꢁtoꢁꢃetꢄorꢅsꢁꢄꢀicꢀꢁcoꢃsistꢁoꢃplꢁoꢆꢁꢇTT-ꢈ10A
ꢁꢁNotꢁ aapic ꢂpeꢁtoꢁtꢀeꢁoꢃesꢁcoꢃꢃectedꢁtoꢁLiꢃꢅꢁPoꢄerꢁꢃetꢄorꢅA
•ꢁTꢀeꢁm ximumꢁꢃumꢂerꢁoꢆꢁꢃodesꢁcoꢃꢃect ꢂpeꢁtoꢁtꢀeꢁꢃetꢄorꢅꢁsegmeꢃtꢁisꢁreducedꢁꢂlꢁoꢃe
ꢁꢁꢄꢀeꢃꢁoꢃeꢁuꢃitꢁoꢆꢁM-RESTERꢁisꢁ ddedA
•ꢁWꢀeꢃꢁtꢀeꢁdist ꢃceꢁꢂetꢄeeꢃꢁꢃodesꢁ reꢁrep tiveplꢁpoꢃgꢁ(eAgAꢁgrouaedꢁ ꢃdꢁsea r tedꢁꢂlꢁc ꢂiꢃets),
ꢁꢁiꢃst ppꢁtꢀeꢁM-RESTERꢁꢂlꢁe cꢀꢁgrouaꢁoꢆꢁdevicesAꢁꢁIꢃsertꢁtꢀeꢁM-RESTERꢁ tꢁtꢀeꢁsurgeꢁsideꢁoꢆꢁtꢀeꢁꢃetꢄorꢅA
•ꢁꢇorꢁdet ipedꢁiꢃꢆorm tioꢃꢁoꢃꢁtꢀeꢁꢃetꢄorꢅ,ꢁreꢆerꢁtoꢁLONWORKSꢁꢇTT-ꢈ10ꢁꢇreeꢁToaopoglꢁTr ꢃsceiverꢁ
ꢁꢁUser’sꢁGuideꢁarovidedꢁꢂlꢁEcꢀepoꢃA
Specifications are subject to change without notice.
MDW5ALW SPECIFICATIONS
ES-8218 Rev.4 Page 5/5
http://www.m-system.co.jp/