MDP-100T/A33 [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDP-100T/A33 |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总4页 (文件大小:119K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDP-100T
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Construction: Plug-in
Surge protection type: Voltage limiting type one-port SPD
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
LIGHTNING SURGE PROTECTOR FOR
AC/DC POWER SUPPLY USE (1A)
(photovoltaic system, instrument shelter)
Functions & Features
Housing material: Flame-resistant resin (black)
INSTALLATION
• Designed for AC and specifically for DC power supplies up
to 1 A
Operating temperature: -20 to +80°C (-4 to +176°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
• Beneficial for protecting instruments from
counter electromotive force by inductors and of course
normal lightning surges entering from power supply lines
• 1 A fuse incorporated in element circuit
Weight:
90 g (0.20 lb), standard
115 g (0.25 lb), with DIN rail mounting adapter
23.5 (.93)
PERFORMANCE
Max. line voltage (Uc): 120 V AC (peak voltage 170V)
Discharge voltage:
Lot.NO
N1430B
100
(3.94)
Line to line: 190 V
JPAN
MADEIN
Line to earth: 410 V
M•STER
MODEL
Voltage protection level (Up):
Line to line: 400 V
80 (3.15)
mm (inch)
Line to earth: 800 V
Response time: ≤ 0.1 μsec.
Leakage current:
Line to line: ≤ 0.15 mA @ 150 V DC
Line to earth: ≤ 0.15 mA @ 300 V DC
Max. discharge current (Imax): 1000 A (8/ 20 μsec.)
MODEL: MDP–100T[1]
ORDERING INFORMATION
• Code number: MDP-100T[1]
Specify a code from below for [1].
(e.g. MDP-100T/A33/Q)
Nominal current (I ): 1.0 A
N
Dielectric strength of the base module:
1500 V AC @ 1 minute (G terminal to other terminals)
Internal series resistance: ≤ 0.4 Ω (including return)
Surge protection: IEC 61643-1 Class III
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
MDP-100T SPECIFICATIONS
ES-8226 Rev.2 Page 1/4
http://www.m-system.co.jp/
MODEL: MDP-100T
CONNECTION EXAMPLES
CONTROL ROOM
FIELD
M-RESTER
1A
M-RESTER
1A
S1
S2
P1
P2
S1
S2
P1
P2
Discharge
Element
Discharge
Element
R
1A
1A
Relay,
Coil, etc.
G
G
The M-RESTER must be connected with its terminals S1 and S2 faced on power source side
in order that the fuses would be blown in case of shortcircuit of the discharge element.
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
MDP-100T SPECIFICATIONS
ES-8226 Rev.2 Page 2/4
http://www.m-system.co.jp/
MODEL: MDP-100T
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ STANDARD
80 (3.15)
53 (2.09)
2–5 (.20) dia.
MTG HOLE
23.5 (.93)
27 (1.06)
HEAD ELEMENT
P1
P2
BASE
4–M4 TERMINAL SCREW
S1
S2
GROUND TERMINAL (G)
(used as mounting bracket)
■ WITH DIN RAIL MOUNTING ADAPTER
8.5
(.33)
[3.3 (.13)]
80 (3.15)
53 (2.09)
27 (1.06)
23.5 (.93)
DIN RAIL
35mm wide
P1 P2
4–M4 TERMINAL SCREW
S1 S2
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MOUNTING REQUIREMENTS unit: mm (inch)
2–M4 SCREW
25 (.97) min.
MDP-100T SPECIFICATIONS
ES-8226 Rev.2 Page 3/4
http://www.m-system.co.jp/
MODEL: MDP-100T
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
1A
S1
S2
P1
P2
ELEMENT
Discharge
Elements
POWER
SUPPLY
TO EQUIPMENT
1A
BASE
G
GROUND TERMINAL
(used as mounting attachment)
Note: When the head element is removed, the line will be open.
Specifications are subject to change without notice.
MDP-100T SPECIFICATIONS
ES-8226 Rev.2 Page 4/4
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明