MD7TC-FG2 [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MD7TC-FG2 |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总6页 (文件大小:151K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MD7TC
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
(CENELEC intrinsic safety (ATEX) not available)
LIGHTNING SURGE PROTECTOR FOR
THERMOCOUPLE USE
(ultra-slim)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Functions & Features
• High discharge current capacity 20 kA (8 / 20 μs), 1 kA
(10 / 350 μs)
/C02: Polyurethane coating
• Ultra-thin 7-mm-wide module can be mounted
in high density
GENERAL SPECIFICATIONS
Construction: Slim-sized front terminal structure
Degree of protection: IP20
• Excellent protection employing multi-stage SPD circuits
• DIN rail mounting and grounding
• Shield terminal provided
Connection: Euro terminal block (torque 0.3 N·m)
Applicable wire size: 0.2 – 2.5 mm2, stripped length 8 mm
Grounding: DIN Rail
7 (.28)
Housing material: Flame-resistant resin (black)
INSTALLATION
Operating temperature: -25 to +85°C (-13 to +185°F)
(See Safety Parameters for use in a hazardous location.)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)
Oxide film on the surface of an aluminium DIN rail may
lower the electric conductivity between this module and the
ground. Use a steel or copper rail.
95
(3.74)
98
(3.86)
mm (inch)
Weight: 70 g (2.5 oz)
MODEL: MD7TC–[1][2][3]
ORDERING INFORMATION
• Code number: MD7TC-[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. MD7TC-FF0/Q)
For the safety approval code 2, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8057).
• Specify the specification for option code /Q
(e.g. /C01)
[1] SHIELD TERMINAL (line / earth)
FF: Floating / Floating
FG: Floating / Grounding
GF: Grounding / Floating
GG: Grounding / Grounding
[2] SAFETY APPROVAL
0: None
2: CENELEC intrinsic safety (ATEX)
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 1/6
http://www.m-system.co.jp/
MODEL: MD7TC
PERFORMANCE
MODEL NO.
MD7TC-FF
MD7TC-FG
±±60V
MD7TC-GF
MD7TC-GG
±7.5V
Max. continuous operating voltage (Uc) Line to Line
7.5V
25V
Line to Earth
Line to SHLD
SHLD to Earth
±±60V
±7.5V
±25V
±±60V
short
±±60V
±ꢀ00V
short
Voltage protection level (Up)
@4kV (±.2 / 50 µs)
Line to Line
Line to Earth
Line to SHLD
SHLD to Earth
Line to Line
±ꢀ00V
±ꢀ00V
short
±25V
±±200V
±ꢀ00V
short
Leakage current @Uc
Response time
≤ 5µA
≤ 5µA
Other sections
Line to Line
≤ 4 nsec.
Other sections
≤ 20 nsec.
Max. discharge current (Imax)
20kA (ꢀ / 20 µs), ±.0kA (±0 / 350 µs)
±00mA
N
Nominal current (I )
Internal series resistance
Surge protection
4.7Ω ±±0% per line
IEC 6±643-2± Categories C±, C2, D±
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex ia EN 60079-11
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
CENELEC: Intrinsic safety (ATEX)
II 1G, Ex ia IIC; T4 and T5
EN 60079-0
EN 60079-11
SAFETY PARAMETERS
■ CENELEC / ATEX IS DATA
Ui (Vmax)
16V
any
Ii (Imax)
Ci
Li
35 nF
0 µH
Temp. Class
Range
Parameter
1.3W
-25 to +40°C
-25 to +60°C
-25 to +80°C
-25 to +40°C
Pi
T4
T5
1.2W
1.0W
1.0W
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 2/6
http://www.m-system.co.jp/
MODEL: MD7TC
DESCRIPTIONS
■ SELECTING SHIELD TERMINAL TYPE
• The surge protector has a dedicated shield terminal effective for easy shield wiring and surge protection.
• Review the shield method (grounding, non-grounding, connecting to SG, etc.) required by the protected device or system.
• There is no electrical effect to the shield by installing the surge protector, but an appropriate shield terminal type must be
selected to suit user applications.
• Refer to the flow chart below to choose.
Cable
With Shield
Without Shield
Shield to Signal
Isolated
Shield to Signal
Not Isolated
Signal to Earth
Isolated
Signal to Earth
Not Isolated
Shield
Not Grounded
Shield
Grounded
Shield
Not Grounded
Shield
Grounded
FF
FG
GF
GG
FF
GG
CONNECTION EXAMPLES
Sheath or
Protected Side
Metal Enclosure
Surge Side
Surge Side
Protected Side
Protected Device
M-RESTER
M-RESTER
+
–
+
–
1
2
7
4
5
8
4
5
8
1
2
7
Compensating
Leadwire
Compensating
Leadwire
Compensating
Leadwire
T/C
INPUT
FG
*4
SG
(SHLD)
DIN RAIL
ADAPTOR
DIN RAIL
ADAPTOR
*3
Crossover Wire
*1
*1
DIN RAIL
DIN RAIL
*2
*2
*1. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Use a steel or copper rail.
*2. Be sure to ground the DIN rail. Recommended grounding resistance ≤100Ω
*3. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.
Ground only the surge protector when the protected device has no ground terminal.
*4. Shield wiring method is an example. Proceed according to the system requirements.
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 3/6
http://www.m-system.co.jp/
MODEL: MD7TC
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
8–M3 EURO
TERMINAL
WIRE INSERTION ANGLE: approx. 20°
8
6
5
4
8
DIN RAIL
ADAPTOR
6
5
DIN RAIL
4
(35 mm wide)
1
2
3
7
1
2
3
7
[1.5 (.06)]
98 (3.86)
7
(.28)
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 4/6
http://www.m-system.co.jp/
MODEL: MD7TC
SCHEMATIC CIRCUITRY
SHIELD TERMINAL
MODEL NO.
SCHEMATIC CIRCUITRY
APPLICATIONS
•Line to SHLD: •MD7TC-FFx
Floating
•Earth to SHLD:
Floating
•Standard type
Surge Side
Protected Side
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
floating against the earth.
(single-end grounding)
Series Resistance
+
–
4
1
+
–
DISCHARGE
ELEMENT
5
6
8
2
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
•Line to SHLD: •MD7TC-FGx
Floating
•Earth to SHLD:
Grounding
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
grounded. (single- or both-
end grounding)
Surge Side
Protected Side
Series Resistance
+
–
4
1
+
–
DISCHARGE
ELEMENT
5
6
8
2
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
•Line to SHLD: •MD7TC-GFx
Grounding
•Earth to SHLD:
Floating
•To protect a device having
isolation between Signal
and Earth.
•When SHLD wire should be
connected to SG terminal
of the protected device.
(SHLD is not grounded to
the earth.)
Surge Side
Protected Side
Series Resistance
+
–
4
1
+
–
DISCHARGE
ELEMENT
5
6
8
2
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
•Line to SHLD: •MD7TC-GGx
Grounding
•Earth to SHLD:
Grounding
•To protect a device which
does not have a good
dielectric strength between
Signal and Earth.
Surge Side
Protected Side
Series Resistance
+
–
4
1
+
–
DISCHARGE
ELEMENT
5
6
8
2
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Sections enclosed with broken line may differ depending upon the models.
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 5/6
http://www.m-system.co.jp/
MODEL: MD7TC
Specifications are subject to change without notice.
MD7TC SPECIFICATIONS
ES-8053 Rev.9 Page 6/6
http://www.m-system.co.jp/
相关型号:
MD8001LEADFREE
Small Signal Bipolar Transistor, 0.03A I(C), 40V V(BR)CEO, 2-Element, NPN, Silicon, TO-78, HERMETIC SEALED, METAL PACKAGE-6
CENTRAL