MD6T-24-40S [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MD6T-24-40S |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总3页 (文件大小:118K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MD6T-24
which the surge protector is used.
Lightning Surge Protectors for
Electronics Equipment M-RESTER
GENERAL SPECIFICATIONS
Degree of protection: IP65
LIGHTNING SURGE PROTECTOR FOR
Wiring conduit: See ‘Ordering information.’
Connection
STANDARD SIGNAL LINE & PULSE USE
(conduit mount, weather-proof, 24 V DC line voltage)
Functions & Features
Cable side: Euro type terminal block (Applicable wire size:
0.14 – 1.5 mm (AWG26 – 16) for both stranded and solid
2
• Designed specifically for 4 – 20 mA DC and
pulse signal line including both 4-wire and 2-wire
transmitters
wires; stripped length 6 mm)
Equipment side: Leadwires (leadwire diameter AWG20 for
grounding; AWG22 for the protected equipment)
Body material: Nickel-plated brass or stainless steel 316
• Direct mount in a wiring conduit of outdoor enclosures
• Absorbs surges only without affecting instrumentation
signal
INSTALLATION
Operating temperature:
No Safety approval: -40 to +85°C (-40 to +185°F)
ATEX approval:
-40 to +80°C (-40 to +176°F) (T5)
-40 to +75°C (-40 to +167°F) (T6)
Mounting: Screwed into an electrical conduit of outdoor
enclosures
Weight: 500 g (1.1 lb)
PERFORMANCE
MODEL: MD6T–24–[1][2][3]
Discharge voltage (peak voltage)
Line to line: 30 V min.
ORDERING INFORMATION
• Code number: MD6T–24–[1][2][3]
Specify a code from below for each of [1] through [3].
(e.g. MD6T-24-00B)
Line to ground: ±160 V min.
Max. surge voltage
Line to line: 40 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through the surge
protector. Protected equipment must be able to withstand
this voltage for a very short time period.)
Response time:
For the safety approval code 4, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8284).
[1] SAFETY APPROVAL
0: None
Line to line: ≤ 4 nsec.
Line to ground: ≤ 20 nsec.
4: ATEX flameproof
Leakage current:
Line to line: ≤ 5 μA @ 30 V DC
Line to ground: ≤ 5 μA @ ±160 V DC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Max. load current: 100 mA
[2] WIRING CONDUIT
0: G 1/2 (Not selectable for ATEX flameproof approval)
1: 1/2 NPT
Internal series resistance: Approx. 22 Ω including return
Max. line voltage
2: M20 × 1.5
Without safety approval: 30 V DC
With safety approval: 28 V DC
Capacitance @ 1 kHz:
[3] BODY MATERIAL
B: Brass
S: Stainless steel
Line to line: ≤ 2500 pF
Line to ground: ≤ 100 pF
CAUTION
The packing of the cable gland must be separate from the
body. Choose an appropriate one for the environment in
MD6T-24 SPECIFICATIONS
ES-8283 Rev.9 Page 1/3
http://www.m-system.co.jp/
MODEL: MD6T-24
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex d EN 60079-1
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
ATEX: FIameproof
II 2G, Ex d IIC, T5 and T6
(EN 60079-1)
CONNECTION EXAMPLES
Field
Central Station
(Protected Equipment Enclosure)
Conduit Mount Type SPD
Protected Equipment
Current Loop Supply
MDP-24-1
+
yellow
+
From Field
+
–
S
S
1
2
S+
S–
P+
P–
Cable
–
IN
blue
–
To Central Station
green
G
(Protected Equiment)
G
G
G
Connect the MD6T’s green leadwire to the ground terminal inside the protected equipment enclosure to ground through the
enclosure’s outside ground terminal.
If the enclosure does not have an inside ground terminal, connect the green leadwire directly to the outside ground wire
pulled inside the enclosure. Keep the ground wire as short as possible.
MD6T-24 SPECIFICATIONS
ES-8283 Rev.9 Page 2/3
http://www.m-system.co.jp/
MODEL: MD6T-24
EXTERNAL DIMENSIONS unit: mm (inch)
■ WITHOUT SAFETY APPROVAL
G 1/2, 1/2 NPT or M20x1.5
G 1/2, 1/2 NPT or M20x1.5
69 (2.72)
35 (1.38)
79 (3.11) [91 (3.58)]
*
approx. 250 (9.8)
*
[ ] for 1/2 NPT
■ WITH SAFETY APPROVAL
1/2 NPT or M20x1.5
1/2 NPT or M20x1.5
69 (2.72)
41 (1.61)
86 (3.39) [91 (3.58)]
*
approx. 250 (9.8)
*
[ ] for 1/2 NPT
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
leadwires
22Ω
yellow
+
+
1
Equipment
Side
Discharge
Elements
Cable
Side
1
*
ZD
–
–
2
blue
G
To Equipment
Ground
2
*
green
*1. The zenor diode has polarity. Zero-cross signal cannot be connected.
*2. Use only when the signal line require functional grounding.
This is NOT for surge protection.
Specifications are subject to change without notice.
MD6T-24 SPECIFICATIONS
ES-8283 Rev.9 Page 3/3
http://www.m-system.co.jp/