MD6N-65-30S [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MD6N-65-30S |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总3页 (文件大小:129K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MD6N-65
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[2] WIRING CONDUIT
0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
LIGHTNING SURGE PROTECTOR FOR
Confirm selectable combinations of approval and wiring
conduit types in the table.
STANDARD SIGNAL LINE & PULSE USE
(conduit mount, weather-proof; 65 V DC line voltage)
Functions & Features
[3] BODY MATERIAL
B: Brass
• Designed specifically for 4 – 20 mA DC and pulse signal
line including both 4-wire and 2-wire transmitters
• Direct mount in a wiring conduit of outdoor
enclosures
S: Stainless steel
• Absorbs surges only without affecting instrumentation
signal
GENERAL SPECIFICATIONS
Degree of protection: IP65
Wiring conduit: See ‘Ordering information.’
Electrical connection: Leadwires
Leadwire diameters
Cable side & grounding: AWG20
Protected equipment side: AWG22
Body material: Nickel-plated brass or stainless steel 316
INSTALLATION
Operating temperature:
No Safety approval: -40 to +85°C (-40 to +185°F)
FM approval:
-40 to +80°C (-40 to +176°F) (T6)
ATEX approval:
MODEL: MD6N–65–[1][2][3]
■ SELECTABLE WIRING CONDUITS SPECIFIC TO EACH APPROVAL
-40 to +80°C (-40 to +176°F) (T5)
-40 to +75°C (-40 to +167°F) (T6)
Mounting: Screwed into an electrical conduit of outdoor
enclosures
‘N’ marked combinations are not selectable.
APPROVAL
0
3
4
WIRING CONDUIT
Weight: 330 g (0.73 lb)
0
1
2
Y
Y
Y
N
Y
N
N
Y
Y
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 70 V min.
ORDERING INFORMATION
• Code number: MD6N–65–[1][2][3]
Specify a code from below for each of [1] through [3].
(e.g. MD6N-65-00B)
Line to ground: ±160 V min.
Max. surge voltage
Line to line: 100 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through the surge
protector. Protected equipment must be able to withstand
this voltage for a very short time period.)
Response time:
For the safety approval code 4, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8284).
[1] SAFETY APPROVAL
0: None
Line to line: ≤ 4 nsec.
Line to ground: ≤ 20 nsec.
3: FM explosion-proof
Leakage current:
4: ATEX flameproof
Line to line: ≤ 5 μA @ 70 V DC
Line to ground: ≤ 5 μA @ ±160 V DC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Max. load current: 100 mA
Confirm selectable combinations of approval and wiring
conduit types in the table.
MD6N-65 SPECIFICATIONS
ES-8281 Rev.3 Page 1/3
http://www.m-system.co.jp/
MODEL: MD6N-65
Internal series resistance: Approx. 22 Ω including return
Max. line voltage
Without safety approval: 70 V DC
With safety approval: 66 V DC
Capacitance @ 1 kHz:
Line to line: ≤ 2500 pF
Line to ground: ≤ 100 pF
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex d EN 60079-1
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
FM: Explosion-proof and Dust-ignition proof
Class I, Div. 1, Groups A, B, C and D
Class II, Div. 1, Groups E, F and G
Class III, Div. 1
T6
(Class 3615)
ATEX: FIameproof
II 2G, Ex d IIC, T5 and T6
(EN 60079-1)
CONNECTION EXAMPLES
Field
Central Station
(Protected Equipment Enclosure)
Conduit Mount
Type SPD
Protected Equipment
Current Loop Supply
MDP-65-1
+
–
yellow
red
+
–
+
–
From Field
+
S
S
S
S
S+
S–
P+
P–
Cable
IN
–
blue
black
To Central Station
G
(Protected Equiment)
green
G
G
G
Connect the Conduit Mount Type SPD’s green leadwire to the ground terminal inside the protected equipment enclosure to
ground through the enclosure’s outside ground terminal.
If the enclosure does not have an inside ground terminal, connect the green leadwire directly to the outside ground wire
pulled inside the enclosure. Keep the ground wire as short as possible.
MD6N-65 SPECIFICATIONS
ES-8281 Rev.3 Page 2/3
http://www.m-system.co.jp/
MODEL: MD6N-65
EXTERNAL DIMENSIONS unit: mm (inch)
2–G 1/2, 1/2 NPT or M20x1.5
27 (1.06)
approx. 250 (9.8)
52 (2.05)
approx. 250 (9.8)
10 (.39)
{17 (.67)}
[22 (.87)]**
10 (.39)
{17 (.67)}
[22 (.87)]**
*
*
*
{
[
} for M20x1.5 with ATEX flameproof approval
] for 1/2 NPT
**
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
leadwires
22Ω
+
red
yellow
+
Equipment
Side
Discharge
Elements
Cable
Side
1
*
ZD
black
blue
–
–
green
To Equipment
Ground
2
*
G
*1. The zenor diode has polarity. Zero-cross signal cannot be connected.
*2. Use only when the signal line requires functional grounding.
This is NOT for surge protection.
Specifications are subject to change without notice.
MD6N-65 SPECIFICATIONS
ES-8281 Rev.3 Page 3/3
http://www.m-system.co.jp/