MATP-600MA [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MATP-600MA |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总3页 (文件大小:136K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MATP
Line: M5 screw terminal (torque: 2.5 N·m)
Lightning Surge Protectors for
Electronics Equipment M-RESTER
Alarm output: Tension clamp
Applicable wire size
Line: See the drawing below.
Alarm output: 0.13 to 1.5 mm
Screw terminal
SURGE PROTECTOR FOR PHOTOVOLTAIC SYSTEM
Functions & Features
2, stripped length 8 mm
• Surge protection for photovoltaic array and power
conditioner.
Line: Nickel-plated steel
Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Alarm output: Trips when the thermal breaker operates.
(N.C. contact)
•High discharge current capacity 20 kA or 40 kA (8/20 μs)
• Degraded head element is automatically separated from
the power lines by the incorporated thermal breaker, and
the LED lamp (turns off) and the relay contact alerts the
failure status.
Rated load:
250 V AC @50 mA (resistive load)
• Breakdown of the surge protector remotely detected with
the alarm output
24 V DC @50 mA (resistive load)
Safety function: Thermal breaker incorporated
Monitor LED: Green LED turns on during normal conditions
between 150 and 600 V DC, and turns off during failure
condition, power off and the thermal breaker operating.
• Applicable Solderless Terminal Size
diameter d
d : M5 use
B ≤ 13.0 mm
F ≥ 7.0 mm
(F ≥ 8.2 mm for sharing terminals)
T ≤ 1.8 mm
F
MODEL: MATP–600[1][2]
INSTALLATION
ORDERING INFORMATION
• Code number: MATP-600[1][2]
Specify a code from below for each [1] and [2].
(e.g.MATP-600MA)
Operating temperature: -25 to +80°C (-13 to +176°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail
Weight
MATP-600Mx: 200 g (0.44 lb)
MATP-600Hx: 250 g (0.55 lb)
OPERATIONAL VOLTAGE
600: 600 V DC
PERFORMANCE
[1] MAXIMUM DISCHARGE CURRENT
M: 20kA (8/20 μsec.)
Max. continuous operating voltage (Uc): 600 V DC
Discharge voltage: (Line to earth) 600 V DC
Maximum surge voltage: 2.5 kV
Maximum (Imax) and Nominal (In) discharge current: (8/ 20
μs)
H: 40kA (8/20 μsec.)
[2] ALARM OUTPUT
A: With
• MATP-600Mx: 20 kA (Imax), 10 kA (In)
• MATP-600Hx: 40 kA (Imax), 20 kA (In)
Response time: ≤ 4 nsec
Y: Without
Leakage current: ≤ 1 mA
GENERAL SPECIFICATIONS
Construction: Standalone; terminal access at the front
Degree of protection: IP20 (If the solderless terminals are
covered with insulation tubes.)
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to
alarm output)
Dielectric strength: 2000 V AC @ 1 minute (line to alarm
output)
Surge protection type: Voltage limiting type one-port SPD
Connection
Surge protection: IEC 61643-1 Class II
MATP SPECIFICATIONS
ES-8150 Rev.4 Page 1/3
http://www.m-system.co.jp/
MODEL: MATP
CONNECTION EXAMPLES
■ CONNECTION DIAGRAM
10m min.
Switch Gear
Common Enclosure
Distribution Board
DC
Blocking Diode
L+
Photovoltaic
Array
L–
AC
*1
L−
L+
L−
L+
SPD
SPD
*2, *3
*2, *3
*1. When the wiring distance is longer than 10 m between the power conditioner and the surge protector in the switch gear, install near the power
conditioner.
*2. Cable length between the branch point and the earthing: 0.5 m or less recommended
*3. When the solar panel manufacturer requires earthing at negative line of DC side, do NOT use the earth terminal of the SPD but use the
L- terminal. If also, earthing at positive line is necessary, earth the L+ terminal.
■ CIRCUIT BREAKER POSITION
If you want to use circuit breaker as SPD maintenance switch, insert a wiring MCCB for DC on SPD power side (diagram below).
Even when the output current of solar cell array is low, use 20 AT or more for wiring MCCB.
Switch Gear
Wiring MCCB
Blocking Diode
L+
Solar Cell
Array
L–
L−
L+
L+
Solar Cell
Array
SPD
L–
L+
Solar Cell
Array
L–
MATP SPECIFICATIONS
ES-8150 Rev.4 Page 2/3
http://www.m-system.co.jp/
MODEL: MATP
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
80 (3.15)
60 (2.36)
50 (1.97)
15 (.59) 15 (.59)
5–M5 SCREW
TERMINAL COVER
L–
L+
DIN RAIL
35mm wide
SPECIFICATION
MONITOR LED
[3.4 (.13)]
ALARM OUTPUT
TERMINAL
*
15 (.59)
45°
(WIRE INSERTION ANGLE)
12.5 (.49)
A0 A1 NC
*
Only for 'Alarm output' code 'A.'
SCHEMATIC CIRCUITRY
–
L
+
L
Monitor LED
Display
Circuit
ѳ
ѳ
ѳ
ѳ
A0 A1 NC
ѳ
: Thermal breaker
Note: Terminals A0 & A1 are available for ‘Alarm output’ code ‘A.’
Specifications are subject to change without notice.
MATP SPECIFICATIONS
ES-8150 Rev.4 Page 3/3
http://www.m-system.co.jp/