M80YS-66-R [MSYSTEM]
Super-mini Signal Conditioners M80 Series;型号: | M80YS-66-R |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners M80 Series |
文件: | 总2页 (文件大小:100K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M80YS
Super-mini Signal Conditioners M80 Series
RELATED PRODUCTS
• Installation Base (model: M80BSx)
This unit must be mounted on a dedicated base.
OUTPUT ISOLATOR
Functions & Features
• Converts DC input into isolated standardized process
signal
GENERAL SPECIFICATIONS
Construction: Plug-in
• Isolates between analog output channels of a PLC
• Achieves space-saving and easy maintenance with Multi-
channel Installation Base
Housing material: Flame-resistant resin (gray)
Power supply: Via the Installation Base terminals
(model: M80BSx)
Isolation: Input to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
14.0 (.55)
INPUT SPECIFICATIONS
■ DC Voltage
39.2
(1.54)
Input resistance: 1 MΩ min. (10 kΩ min. in power failure)
INSTALLATION
51.8 (2.04)
Current consumption: Approx. 50 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 5 to 95 %RH (non-condensing)
Mounting: Multi-channnel Installation Base (model: M80BSx)
Weight: 20 g (0.71 oz)
mm (inch)
MODEL: M80YS-6[1]-R
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
ORDERING INFORMATION
• Code number: M80YS-6[1]-R
Specify a code from below for [1].
(e.g. M80YS-66-R)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 15 msec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute (input to output
to power to ground)
INPUT
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
STANDARDS & APPROVALS
EU conformity:
[1] OUTPUT
Current
EMC Directive
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
D: 0 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
4: 0 - 10 V DC (Load resistance 5000 Ω min.)
5: 0 – 5 V DC (Load resistance 2500 Ω min.)
6: 1 – 5 V DC (Load resistance 2500 Ω min.)
4W: -10 – +10 V DC (Load resistance 5000 Ω min.)
EN 50581
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
M80YS SPECIFICATIONS
ES-5397 Rev.0 Page 1/2
http://www.m-system.co.jp/
MODEL: M80YS
EXTERNAL DIMENSIONS unit: mm (inch)
14.0 (.55)
50.5 (1.99)
1.3 (.05)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
Isolation
Low Drift
Amplifier
Output
Driver
+
–
A
B
+
–
9
10
4
1
2
3
5
7
6
8
ꢀ
ꢀ
INPUT
OUTPUT
POWER
C
ꢀ
ꢀ
ꢀ
ꢀ
+
–
Installation Base
Note: Use shielded cables for I/O wiring.
Specifications are subject to change without notice.
M80YS SPECIFICATIONS
ES-5397 Rev.0 Page 2/2
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明