M6SXAR-4-R [MSYSTEM]
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series;型号: | M6SXAR-4-R |
厂家: | M-SYSTEM |
描述: | Tension-Clamp Ultra-Slim Signal Conditioners M6S Series |
文件: | 总4页 (文件大小:157K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M6SXAR
(Usable range: -50 to +250°C, -58 to +482°F)
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
0: Specify (Please provide a resistance table.)
(Configurator software is used to change the input type and
range. Input code 7: Pt 1000 cannot be switched to/from
other input types while its temperature range can be
changed.)
RTD ALARM
(PC programmable)
Functions & Features
• Maintenance-free tension clamp connection
• 5.9-mm wide ultra-slim design
• Low profile allows the M6S module mounted in a 120-mm
deep panel
OUTPUT
Relay; SPDT or transfer contact
• PC programmable
• Linearization and upscale and downscale burnout
protection
POWER INPUT
DC Power
• High-density mounting
R: 24 V DC
• Power and status indicator LEDs
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
5.9 (.23)
blank: none
/Q: With options (specify the specification)
94
(3.70)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
102
(4.02)
mm (inch)
RELATED PRODUCTS
• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
MODEL: M6SXAR–[1]–R[2]
ORDERING INFORMATION
• Code number: M6SXAR-[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. M6SXAR-4-R/Q)
GENERAL SPECIFICATIONS
Connection
• Temperature range (e.g. 0 – 100°C)
• Specify the specification for option code /Q
(e.g. /C01)
Input and output: Tension clamp
Power input: Via the Installation Base (model: M6SBS)
or Tension clamp
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm
2
[1] INPUT RTD
1: JPt 100 (JIS'89)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
(Usable range: -200 to +500°C, -328 to +932°F)
3: Pt 100 (JIS'89)
Burnout: Upscale standard; downscale or no burnout
optional by programming
(Usable range: -200 to +650°C, -328 to +1202°F)
4: Pt 100 (JIS'97, IEC)
In case of upscale standard, the alarm operates as if the
input signal has exceeded over the range.
Linearization: Standard
(Usable range: -200 to +850°C, -328 to +1562°F)
5: Pt 50 Ω (JIS'81)
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Blinking patterns indicate
different operating status of the transmitter.
Alarm monitor LED: Red LED turns on when the alarm is
tripped.
(Usable range: -200 to +649 °C, -328 to +1200°F)
7: Pt 1000
(Usable range: -200 to +850°C, -328 to +1562°F)
9: Cu 10 @25°C
M6SXAR SPECIFICATIONS
ES-7993 Rev.4 Page 1/4
http://www.m-system.co.jp/
MODEL: M6SXAR
Programming: Downloaded from PC
Input type and range
INSTALLATION
Power consumption: Approx. 0.5 W
Input fine adjustments
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6SBS) or DIN rail
Weight: 65 g (2.3 oz)
User’s RTD table (max. 300 points)
Burnout (Upscale, downscale or no burnout)
Alarm setpoint (input %)
Trip action (High or Low)
Relay coil (energized or de-energized)
Power ON delay time (0 to 999 sec.)
Alarm ON delay time (0 to 999 sec.)
Hysteresis (deadband) (input %)
Alarm test, and others
PERFORMANCE in percentage of span
Setpoint accuracy (trip point accuracy)
Pt and JPt: Whichever greater ±0.1 % of input range or
±0.15°C
Cu10: ±1°C
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: ≤ 1 sec. (0 – 100 % at 90 % setpoint)
Burnout response time: ≤ 1 sec.
Factory default setting
Alarm setpoint: 80%
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Trip action: High
Relay coil at alarm: Energized
Power ON delay time: 5 seconds
Alarm ON delay time: 0 seconds
Hysteresis (deadband): 1.0%
Burnout: Upscale
CALCULATION EXAMPLES OF SETPOINT ACCURACY
[Example] Input type Pt 100, Input range 0 – 100°C
Setpoint accuracy *1 (0.15°C *2) ÷ Span (100°C) × 100 %
*1. Calculate the accuracy in °C
INPUT SPECIFICATIONS
Input: 2- or 3-wire RTD
*2. 100 °C × 0.1 % = 0.1 °C ≤ 0.15 °C. 0.15 °C is used as
input accuracy value.
Maximum leadwire resistance: 10 Ω per wire
Sensing current: ≤ 1.5 mA (≤ 0.15 mA for Pt 1000)
Minimum span: 20°C or 36°F
Resistance range:
STANDARDS & APPROVALS
EU conformity:
0 - 500 Ω (Input code: 1, 3, 4, 5, 9)
0 - 5 kΩ (Input code: 7)
EMC Directive
If not specified, the input range is 0 - 100°C.
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
OUTPUT SPECIFICATIONS
■ Relay Output
Measurement Category II (output)
Pollution Degree 2
Relay rating:
250 V AC @2 A (cos ø = 1)
Input or power to output: Reinforced insulation (300 V)
RoHS Directive
30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @100 mA
EN 50581
Mechanical life: 5 × 10 cycles (rate 180/min.)
6
Alarm Trip Operation Terminal No. in parentheses
• Setting Example
Hi alarm (coil energized at alarm) or
Lo alarm (coil de-energized at alarm)
(3–2)ON
Output
(3–4)ON
Input
(%)
0
50
100
Setpoint
Trip operation in power failure: Terminals 3 – 4 turn ON.
M6SXAR SPECIFICATIONS
ES-7993 Rev.4 Page 2/4
http://www.m-system.co.jp/
MODEL: M6SXAR
EXTERNAL VIEW
(With the cover open)
Power LED
Alarm Monitor LED
Status Indicator LED
Configurator Jack
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCREWDRIVER
*
INSERTION ANGLE
: approx. 35°
WIRE INSERTION ANGLE
: approx.35°
TEST PROBE
max. 2 (.08) dia.
5
6
7
8
DIN RAIL HOOK
DIN RAIL
35mm wide
1
2
3
4
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
[0.5 (.02)]
5.9 (.23)
102 (4.02)
• When mounting, no extra space is needed between units.
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm
M6SXAR SPECIFICATIONS
ES-7993 Rev.4 Page 3/4
http://www.m-system.co.jp/
MODEL: M6SXAR
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS ALARM
IND. LED MONITOR LED
RTD
2-wire
A
3-wire
A
NC
4
2
3
Digital
Computation
Ry
6
1
OUTPUT
NO
B
Low Drift
Amplifier
COM
POWER LED
B
B
5
+
–
7
8
POWER
POWER
CONFIGURATOR
JACK
■ Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
LOAD
LOAD
U
Diode, Varistor or
CR Circuit
Varistor or CR Circuit
Specifications are subject to change without notice.
M6SXAR SPECIFICATIONS
ES-7993 Rev.4 Page 4/4
http://www.m-system.co.jp/