M6DPA-D5-R/UL [MSYSTEM]
Euro Terminal Ultra-Slim Signal Conditioners M6D Series;型号: | M6DPA-D5-R/UL |
厂家: | M-SYSTEM |
描述: | Euro Terminal Ultra-Slim Signal Conditioners M6D Series |
文件: | 总4页 (文件大小:124K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M6DPA
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
Euro Terminal Ultra-Slim Signal Conditioners M6D Series
4W: -10 – +10 V DC (Load resistance 20 kΩ min.)
5W: -5 – +5 V DC (Load resistance 10 kΩ min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
FREQUENCY TRANSMITTER
Functions & Features
• 5.9-mm wide ultra-slim design
• Low profile allows the M6D module mounted in a 120-mm
deep panel
POWER INPUT
DC Power
R: 24 V DC
• Converts the output from a pulse-type transducer into a
standard process signal
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• High-density mounting
• Power indicator LED
[3] OPTIONS (multiple selections)
Standards & Approvals
blank: CE marking
5.9 (.23)
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
94
(3.70)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
102
(4.02)
/C02: Polyurethane coating
mm (inch)
GENERAL SPECIFICATIONS
Connection
Input and output: Euro terminal (torque 0.3 N·m)
Power input: Via the Installation Base (model: M6DBS)
or Euro terminal (torque 0.3 N·m)
MODEL: M6DPA–[1][2]–R[3]
ORDERING INFORMATION
• Code number: M6DPA-[1][2]-R[3]
Specify a code from below for each [1] through [3].
(e.g. M6DPA-CA-R/UL/Q)
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: -2 to +2 % (front)
• Frequency range (e.g. 0 – 1 kHz)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01)
(Output code 4W, 5W: Adjustable at 0V.)
Span adjustment: 98 to 102 % (front)
Chattering protection: Filter provided for mechanical
contact input
Power LED: Green light turns on when the power is supplied.
[1] INPUT
A1: Open collector
INPUT SPECIFICATIONS
■ Open Collector
A2: Mechanical contact
C: 5 V pulse (sensitivity 2 V)
D: 24 V pulse (sensitivity 10 V)
Frequency range: 0 – 0.01 Hz through 100 kHz
Pulse width time requirement: ≥ 4 µsec. for both H and L
levels
Sensing voltage/current: 2.5 V DC @1 mA (approx.)
Detecting levels: ≤ 750 Ω/0.75 V for ON;
≥ 3 kΩ/1.6 V for OFF
[2] OUTPUT
Current
A: 4 – 20 mA DC (Load resistance 550 Ω max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
■ Mechanical Contact
Frequency range: 0 – 0.01 Hz through 30 Hz
Pulse width time requirement: ≥ 10 msec. for both ON and
OFF
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
M6DPA SPECIFICATIONS
ES-7830 Rev.8 Page 1/4
http://www.m-system.co.jp/
MODEL: M6DPA
Sensing voltage/current: 2.5 V DC @1 mA (approx.)
Detecting levels: ≤ 750 Ω/0.75 V for ON;
≥ 3 kΩ/1.6 V for OFF
Approval:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
■ Voltage Pulse
Frequency range: 0 – 0.01 Hz through 100 kHz
Pulse width time requirement: ≥ 4 µsec. for both H and L
levels
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
Waveform: Square or sine
Input impedance: ≥ 10 kΩ
Max. voltage between input terminals: ±50 V
Detecting H level
5 V pulse: ≥ 3 V
24 V pulse: ≥ 14 V
Detecting L level
5 V pulse: ≤ 1 V
24 V pulse: ≤ 6 V
OUTPUT SPECIFICATIONS
■ DC Current: 2 – 20 mA DC (and 0 – 1 mA DC)
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 11 V max.
■ DC Voltage: 0 – 10 V DC
Minimum span: 1 V
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 1 V
INSTALLATION
Power consumption: Approx. 0.5 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6DBS) or DIN rail
Weight: 60 g (2.1 oz)
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: Max. 0.5 sec. + 1 pulse cycle (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
M6DPA SPECIFICATIONS
ES-7830 Rev.8 Page 2/4
http://www.m-system.co.jp/
MODEL: M6DPA
EXTERNAL VIEW
(With the cover open)
Power LED
Zero Adj.
Span Adj.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
WIRE INSERTION ANGLE: approx. 7°
8–M3
EURO TERMINAL
DIN RAIL HOOK
5
6
7
8
DIN RAIL
35mm wide
1
2
3
4
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
[0.5 (.02)]
5.9 (.23)
102 (4.02)
• When mounting, no extra space is needed between units.
M6DPA SPECIFICATIONS
ES-7830 Rev.8 Page 3/4
http://www.m-system.co.jp/
MODEL: M6DPA
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
Isolation
Waveform
Shaper
Digital
Computation
Voltage
Amplifier
Output
Driver
+
–
1
2
3
4
5
6
+
–
INPUT
OUTPUT
POWER LED
7
8
+
–
POWER
POWER
Input Connection Examples
■ Open Collector or Mechanical Contact
2.5 V
■ Voltage Pulse
2.4 kΩ
+
–
1
2
+
–
1
2
Specifications are subject to change without notice.
M6DPA SPECIFICATIONS
ES-7830 Rev.8 Page 4/4
http://www.m-system.co.jp/