M2XUM-00-M2 [MSYSTEM]
Super-mini Signal Conditioners Mini-M Series;型号: | M2XUM-00-M2 |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners Mini-M Series |
文件: | 总7页 (文件大小:183K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M2XUM
Current
Super-mini Signal Conditioners Mini-M Series
Z1: Range 0 – 50 mA DC (Input resistance 100 Ω)
Voltage
UNIVERSAL TRANSMITTER
(PC programmable; Modbus-RTU communication)
Functions & Features
S1: Range -1 – +1 V DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
Thermocouple
• Accepts direct inputs from various sensors and provides a
standard process signal
T1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)
T2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
T3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)
T4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
T5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
T6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)
T7: R (Usable range -50 to +1760°C, -58 to +3200°F)
T8: S (Usable range -50 to +1760°C, -58 to +3200°F)
T9: C (WRe 5-26) (Usable range 0 to 2315°C, 32 to 4199°F)
TN: N (Usable range -270 to +1300°C, -454 to +2372°F)
TU: U (Usable range -200 to +400°C, -328 to +752°F)
TL: L (Usable range -200 to +900°C, -328 to +1652°F)
TP: P (Platinel II) (Usable range 0 to 1395°C, 32 to 2543°F)
T0: Specify (Please provide an emf table.)
RTD
• I/O types and calibration ranges are fully programmable
via a PC
• Linearization up to 100 points can be programmed for DC
and potentiometer inputs
• Isolation between input – output – RS-485 – power
Typical Applications
• Signal conversion between control room and field
instrumentation with isolation
• Ideal for use as a fast solution, multifunctional spare part
29.5 (1.16)
(2- or 3-wire)
Model
76
(2.99)
R1: JPt 100 (JIS'89)
(Usable range: -200 to +500°C, -328 to +932°F)
R3: Pt 100 (JIS'89)
(Usable range: -200 to +850°C, -328 to +1562°F)
R4: Pt 100 (JIS'97, IEC)
124
(4.88)
mm (inch)
(Usable range: -200 to +850°C, -328 to +1562°F)
R5: Pt 50 Ω (JIS'81)
(Usable range: -200 to +649 °C, -328 to +1200°F)
R6: Ni 508.4 Ω
MODEL: M2XUM–[1][2]–[3][4]
(Usable range: -50 to +200°C, -58 to +392°F)
R7: Pt 1000
ORDERING INFORMATION
• Code number: M2XUM-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M2XUM-00-M2/CE/Q)
(Usable range: -200 to +200°C, -328 to +392°F)
R8: Ni 100 (Usable range: -50 to +200°C, -58 to +392°F)
R9: Cu 10 @25°C
• Specify the specification for option code /Q
(e.g. /C01/S01)
(Usable range: -50 to +200°C, -58 to +392°F)
R0: Specify (Please provide a resistance table.)
Potentiometer
Non-specified orders will be shipped at default factory
settings (M2XUM-00: 4 – 20 mA input/4 – 20 mA output).
However, the power suffix code must be specified.
If you specify full code numbers without specific calibration
ranges, default settings will be used.
M: Total resistance 100 Ω – 10 kΩ
Note: Consult M-System for 2-wire RTD
[2] OUTPUT
0: User-calibrated (Factory default: 4 – 20 mA DC)
Note: Must be used with its socket. NOT installable to a
multi-unit installation base. (e.g. model: M2BS-16)
If the unit is to be factory-calibrated to a specific
output type, please select from the following:
Current
[1] INPUT
0: User-calibrated (Factory default: 4 – 20 mA DC)
Z1: Range 0 – 20 mA DC
Voltage
If the unit is to be factory-calibrated to a specific
input type, please select from the following:
V1: Range -2.5 – +2.5 V DC
V2: Range -10 – +10 V DC
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 1/7
http://www.m-system.co.jp/
MODEL: M2XUM
· Zero and span adjustments
[3] POWER INPUT
AC Power
· Simulated output
· User's linearization table (max. 100 points, specified within
-15 – +115 % for both input and output)
· User’s TC/RTD table
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
Burnout (T/C, RTD and Pot.): Upscale standard; downscale
or no burnout options are PC programmable
Linearization (T/C, RTD input): Standard tables stored in
memory
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
Cold junction compensation (T/C): CJC sensor (included) to
be attached to the input terminals
[4] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N: Without CE
Status indicator LED: Blinking patterns indicate different
operating status of the transmitter.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
/CE: CE marking
Other Options
blank: none
MODBUS COMMUNICATION
Standard: Conforms to TIA/EIA-485-A
Transmission distance: 500 meters max.
Baud rate: 38.4 kbps max.
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
/C02: Polyurethane coating
Transmission media: Shielded twisted-pair cable
(CPEV-S 0.9 dia.)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
INPUT SPECIFICATIONS
■ DC Current: Shunt resistor attached to the input terminals
RELATED PRODUCTS
(0.5 W)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Operational range: 0 – 70 mA DC with 100 Ω, 0.5 W
Input range: 0 – 50 mA DC
Minimum span: 2 mA
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is 4 – 20 mA DC.
■ DC Voltage
Operational range: -11.5 – +11.5 V DC
Input range: -10 – +10 V DC
GENERAL SPECIFICATIONS
Construction: Plug-in
Minimum span: 10 mV for S1; 100 mV for S2
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
S1: 0 – 100 mV DC
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to RS-485 to power
Overrange output: Approx. -15 to +115 %
(Negative current output is not provided.)
Manual zero adjustments: -5 to +5 %
(factory setting: 0 %)
S2: 1 – 5 V DC
■ Thermocouple
For T/C types K, E, T, B, R, S, N or U, the accuracy in the
temperature ranges near the lower limit may be out of the
described value. Consult M-System for more detail.
Input resistance: 1 MΩ min.
Manual span adjustments: 95 to 105 %
(factory setting: 100 %)
Burnout sensing: 45 nA ±10 %
Programming: PC programmable features include:
· T/C and RTD type and temp. range
· Input and output ranges
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 2/7
http://www.m-system.co.jp/
MODEL: M2XUM
If not specified, the input range is shown below.
T1 PR: 0 – 1600°C
Operational range: -11.5 – +11.5 V DC
Output range: -10 – +10 V DC
Minimum span: 1 V
T2 K: 0 – 1000°C
T3 E: 0 – 500°C
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
T4 J: 0 – 500°C
T5 T: 0 – 300°C
T6 B: 0 – 1800°C
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V1: 0 – 1 V DC
T7 R: 0 – 1600°C
T8 S: 0 – 1600°C
T9 C: 0 – 2000°C
TN N: 0 – 1000°C
V2: 1 – 5 V DC
TU U: 0 – 300°C
TL L: 0 – 500°C
INSTALLATION
Power Consumption
TP P: 0 – 1200°C
■ RTD
•AC: Approx. 6 VA
Maximum leadwire resistance: 200 Ω per wire (3 -wire)
Sensing current: ≤ 1.0 mA
If not specified, the input range is shown below.
R1: JPt 100 0 – 100°C
R3: Pt 100 0 – 100°C
R4: Pt 100 0 – 100°C
R5: Pt 50 Ω 0 – 200°C
R6: Ni 508.4 Ω 0 – 100°C
R7: Pt 1000 0 – 100°C
R8: Ni 100 0 – 100°C
R9: Cu 10 0 – 100°C
•DC: Approx. 3 W
Operating temperature: -30 to +60°C (-22 to +140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 120 g (0.26 lb)
PERFORMANCE
Accuracy: Input accuracy + output accuracy
Input accuracy (% of input range)
Inversely proportional to span.
(DC) -1 – +1 V : ±0.02
-10 – +10 V : ±0.02
0 – 50 mA : ±0.02
Except the input resistor error.
(T/C) (PR) : ±0.08
•Potentiometer: 100 Ω – 10 kΩ
Minimum span:
(Range) 0 – 100 Ω : 2.5 Ω
0 – 300 Ω : 3.0 Ω
0 – 1000 Ω : 10 Ω
K (CA) : ±0.02
0 – 10 kΩ : 10 Ω
E (CRC) : ±0.02
Excitation: ≤ 0.5 V DC at 1000 Ω
If not specified, the input range is 0 – 1000 Ω.
J (IC) : ±0.04
T (CC) : ±0.06
B (RH) : ±0.12
OUTPUT SPECIFICATIONS
■ DC Current
R : ±0.08
S : ±0.08
Operational range: 0 – 24 mA DC
Output range: 0 – 20 mA DC
Minimum span: 1 mA
C (WRe 5 - 26) : ±0.04
N : ±0.04
U : ±0.04
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
L : ±0.04
P (Platinel II) : ±0.04
(RTD) JPt 100 (JIS ’89) : ±0.04
Pt 100 (JIS ’89) : ±0.03
Pt 100 (JIS ’97, IEC) : ±0.03
Pt 50 Ω (JIS ’81) : ±0.04
Ni 508.4 Ω : ±0.05
Pt 1000 : ±0.08
Load resistance: Output drive 15 V max.
(e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
Code V1 (narrow spans)
Operational range: -3 – +3 V DC
Output range: -2.5 – +2.5 V DC
Minimum span: 250 mV
Ni 100 : ±0.14
Cu 10 : ±0.6
(Pot.) 0 – 100 Ω : ±0.08
Code V2 (wide spans)
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 3/7
http://www.m-system.co.jp/
MODEL: M2XUM
0 – 300 Ω : ±0.04
0 – 1000 Ω : ±0.04
0 – 10 kΩ : ±0.04
Output accuracy: ±0.02 % of output range
Inversely proportional to span.
Cold junction compensation error:
±0.4°C or ±0.7°F (at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient
(at -5 to +55°C [23 to 131°F] of I/O range)
Input: ±0.016 %/°C (±0.009 %/°F) with current
±0.004 %/°C (±0.002 %/°F) with voltage
±0.004 %/°C (±0.002 %/°F) with T/C
±0.004 %/°C (±0.002 %/°F) with RTD
±0.004 %/°C (±0.002 %/°F) with Pot.
Output: ±0.013 %/°C (±0.007 %/°F)
Response time:
≤ 0.5 sec.(0 – 90 %) with current
≤ 0.5 sec.(0 – 90 %) with voltage
≤ 1.5 sec.(0 – 90 %) with T/C
≤ 0.9 sec.(0 – 90 %) with RTD
≤ 0.9 sec. (0 – 90 %) with Pot.
Burnout response: ≤ 10 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to RS-485 to power to ground)
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Type -10 – +10 V, Input Range 1 – 5 V,
Output Type 0 – 20 mA, Output Range 0 – 10 mA
Max. Input Range (20 V) ÷ Span (4 V) × 0.02 % = 0.1 %
Max. Output Range (20 mA) ÷ Span (10 mA) × 0.02 % =
0.04 %
Overall accuracy = 0.1 + 0.04 = ±0.14 %
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
EN 50581
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 4/7
http://www.m-system.co.jp/
MODEL: M2XUM
EXTERNAL VIEW
■ FRONT VIEW (with cover open)
■ RIGHT SIDE VIEW
Address Setting Rotary SW
Configurator Jack
Input Range Selector
Position H: code S2, Z1
Position L : other
Status Indicator LED
Zero/Span Selector
Top: SPAN
Middle: OFF
Bottom: ZERO
Modbus Term. Resistor
: OFF
UP/DOWN Switches
: ON
The front cover cannot be opened to 180 deg.
when flush with neighboring units.
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS unit: mm (inch)
6 (.23)
DIN RAIL
35mm wide
3
2
5
1
4
6
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
9
8
7
11–M3
SCREW
11 10
21.5 (.85) 7.3 (.29)
86.7 (3.41)
116.7 (4.59)
22 (.87)
[4 (.16)]
29.5 (1.16)
• When mounting, no extra space is needed between units.
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 5/7
http://www.m-system.co.jp/
MODEL: M2XUM
TERMINAL ASSIGNMENTS unit: mm (inch)
Use the input resistor (model: REM2) for a DC current input,
and the CJC sensor (model: CJM) for a thermocouple input,
both included in the package.
INPUT RESISTOR
(model: REM2)
CJC SENSOR
(model: CJM)
black
2
red
3
2
5
1
4
3
6
5
4
1
6
9
8
7
9
8
7
11 10
11 10
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
ADDRESS STATUS
DC
T/C
ext. wire
RTD
POT.
INPUT RANGE
SELECTOR
ZERO/SPAN
SELECTOR
Isolation
+
max.
+
+
+
–
Digital
Computation
Output
Driver
1
7
8
+
A
B
B
3
2
1
–
*
–
R
Low Drift
Amplifier
& Burnout
OUTPUT
2
–
CJC
SENSOR
(model: CJM)
UP/DOWN
SWITCHES
–
red
4
3
DA
DB
DG
U(+)
V(–)
Isolation
min.
**
COMM.
INTERFACE
black
RS-485
Interface
5
6
JACK
CONFIGURATOR
9
10
11
POWER
Base Socket
* Input shunt resistor attached for current input.
**When the module is at the end of RS-485 transmission line, turn on the Modbus
terminating resistor located behind the front cover, off when it is not.
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 6/7
http://www.m-system.co.jp/
MODEL: M2XUM
SYSTEM CONFIGURATION EXAMPLES
■ RS-232-C/RS-485
■ Ethernet/RS-485
RS-232-C
Ethernet
RS-232-C/RS-485 Converter
(Model: R2K-1 or LK1)
ETHERNET
Ethernet Communication Adaptor
(model: 72EM2-M4)
RS-485
RUN
SEND
FIELD
CNFG
RS-485
RS-485
Mo
del
Mo
Mo
Mo
Mo
del
Mode
l
del
del
del
Universal Transmitters
(model: M2XUM)
Universal Transmitters
(model: M2XUM)
MODBUS COMMUNICATION PARAMETERS
Refer to the instruction manual for the details about Modbus communication.
■ COMMUNICATION PARAMETERS
PARAMETER
Data Mode
Baud Rate
Parity
SPECIFICATIONS
DEFAULT
MODIFICATION
RTU
RTU
Not modifiable
9600/19200/38400 bps
38400 bps
JXCON Software
None/Odd/Even
Odd
8
JXCON Software
Bit Length
Stop Bit
8
1
Not modifiable
1
Not modifiable
Node Address
1 to 247
1
Hardware Rotary SW for 1 through 15,
JXCON Software for 16 through 247 (Rotary SW set to 0).
Floating Point Data
Physical Layer
Normal/Swapped
RS-485
Normal
RS-485
JXCON Software
Not modifiable
Specifications are subject to change without notice.
M2XUM SPECIFICATIONS
ES-5009 Rev.19 Page 7/7
http://www.m-system.co.jp/
相关型号: