M2XU-0V2-P/N [MSYSTEM]
Super-mini Signal Conditioners Mini-M Series;型号: | M2XU-0V2-P/N |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners Mini-M Series |
文件: | 总6页 (文件大小:130K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M2XU
Super-mini Signal Conditioners Mini-M Series
[1] INPUT
0: User-calibrated (Factory default: 4 – 20 mA DC)
UNIVERSAL TRANSMITTER
(PC programmable)
If the unit is to be factory-calibrated to a specific
input type, please select from the following:
Current
Functions & Features
• Accepts direct inputs from various sensors and provides a
standard process signal
Z1: Range 0 – 50 mA DC (Input resistance 100 Ω)
Voltage
• I/O types and calibration ranges are fully programmable
via a PC
S1: Range -1 – +1 V DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
Thermocouple
• Linearization up to 100 points can be programmed
for DC and potentiometer inputs
T1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)
T2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
T3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)
T4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
T5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
T6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)
T7: R (Usable range -50 to +1760°C, -58 to +3200°F)
T8: S (Usable range -50 to +1760°C, -58 to +3200°F)
T9: C (WRe 5-26) (Usable range 0 to 2315°C, 32 to 4199°F)
TN: N (Usable range -270 to +1300°C, -454 to +2372°F)
TU: U (Usable range -200 to +400°C, -328 to +752°F)
TL: L (Usable range -200 to +900°C, -328 to +1652°F)
TP: P (Platinel II) (Usable range 0 to 1395°C, 32 to 2543°F)
T0: Specify (Please provide an emf table.)
RTD
• Isolation between input – output – power
Typical Applications
• Signal conversion between control room and field
instrumentation with isolation
• Ideal for use as a fast solution, multifunctional spare part
23 (.91)
Model
76
(2.99)
124
(4.88)
(2- or 3-wire)
mm (inch)
R1: JPt 100 (JIS'89)
(Usable range: -200 to +500°C, -328 to +932°F)
R3: Pt 100 (JIS'89)
MODEL: M2XU–[1][2]–[3][4]
(Usable range: -200 to +850°C, -328 to +1562°F)
R4: Pt 100 (JIS'97, IEC)
ORDERING INFORMATION
• Code number: M2XU-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M2XU-00-R/CE/Q)
(Usable range: -200 to +850°C, -328 to +1562°F)
R5: Pt 50 Ω (JIS'81)
(Usable range: -200 to +649 °C, -328 to +1200°F)
R6: Ni 508.4 Ω
• Specify the specification for option code /Q
(e.g. /C01/S01)
(Usable range: -50 to +200°C, -58 to +392°F)
R7: Pt 1000
(Usable range: -200 to +200°C, -328 to +392°F)
R8: Ni 100 (Usable range: -50 to +200°C, -58 to +392°F)
R9: Cu 10 @25°C
Non-specified orders will be shipped at default factory
settings (M2XU-00: 4 – 20 mA input/4 – 20 mA output).
However, the power suffix code must be specified.
If you specify full code numbers without specific calibration
ranges, default settings will be used.
(Usable range: -50 to +200°C, -58 to +392°F)
R0: Specify (Please provide a resistance table.)
Potentiometer
M: Total resistance 100 Ω – 10 kΩ
Note: Consult M-System for 2-wire RTD
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 1/6
http://www.m-system.co.jp/
MODEL: M2XU
[2] OUTPUT
GENERAL SPECIFICATIONS
0: User-calibrated (Factory default: 4 – 20 mA DC)
Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
If the unit is to be factory-calibrated to a specific
output type, please select from the following:
Current
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
(Negative current output is not provided.)
Manual zero adjustments: -5 to +5 %
(factory setting: 0 %)
Z1: Range 0 – 20 mA DC
Voltage
V1: Range -2.5 – +2.5 V DC
V2: Range -10 – +10 V DC
Manual span adjustments: 95 to 105 %
(factory setting: 100 %)
[3] POWER INPUT
AC Power
Programming: PC programmable features include:
· T/C and RTD type and temp. range
· Input and output ranges
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)
· Zero and span adjustments
DC Power
· Simulated output
R: 24 V DC
· User's linearization table (max. 100 points, specified within
-15 – +115 % for both input and output)
· User’s TC/RTD table
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(110 V ±10 % for UL)
Burnout (T/C, RTD and Pot.): Upscale standard; downscale
or no burnout options are PC programmable
Linearization (T/C, RTD input): Standard tables stored in
memory
[4] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N: Without CE or UL
Cold junction compensation (T/C): CJC sensor (included) to
be attached to the input terminals
Status indicator LED: Blinking patterns indicate different
operating status of the transmitter.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
/CE: CE marking
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
/S01: Stainless steel (UL not available)
RELATED PRODUCTS
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 2/6
http://www.m-system.co.jp/
MODEL: M2XU
•Potentiometer: 100 Ω – 10 kΩ
INPUT SPECIFICATIONS
■ DC Current: Shunt resistor attached to the input terminals
(0.5 W)
Minimum span:
(Range) 0 – 100 Ω : 2.5 Ω
0 – 300 Ω : 3.0 Ω
Operational range: 0 – 70 mA DC with 100 Ω, 0.5 W
Input range: 0 – 50 mA DC
0 – 1000 Ω : 10 Ω
0 – 10 kΩ : 10 Ω
Minimum span: 2 mA
Excitation: ≤ 0.5 V DC at 1000 Ω
If not specified, the input range is 0 – 1000 Ω.
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is 4 – 20 mA DC.
■ DC Voltage
OUTPUT SPECIFICATIONS
■ DC Current
Operational range: -11.5 – +11.5 V DC
Input range: -10 – +10 V DC
Operational range: 0 – 24 mA DC
Output range: 0 – 20 mA DC
Minimum span: 10 mV for S1; 100 mV for S2
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
S1: 0 – 100 mV DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
S2: 1 – 5 V DC
Load resistance: Output drive 15 V max.
(e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
■ Thermocouple
For T/C types K, E, T, B, R, S, N or U, the accuracy in the
temperature ranges near the lower limit may be out of the
described value. Consult M-System for more detail.
Input resistance: 1 MΩ min.
Code V1 (narrow spans)
Operational range: -3 – +3 V DC
Output range: -2.5 – +2.5 V DC
Minimum span: 250 mV
Burnout sensing: 45 nA ±10 %
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
T1 PR: 0 – 1600°C
Code V2 (wide spans)
Operational range: -11.5 – +11.5 V DC
Output range: -10 – +10 V DC
Minimum span: 1 V
T2 K: 0 – 1000°C
T3 E: 0 – 500°C
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
T4 J: 0 – 500°C
T5 T: 0 – 300°C
T6 B: 0 – 1800°C
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V1: 0 – 1 V DC
T7 R: 0 – 1600°C
T8 S: 0 – 1600°C
T9 C: 0 – 2000°C
TN N: 0 – 1000°C
V2: 1 – 5 V DC
TU U: 0 – 300°C
TL L: 0 – 500°C
INSTALLATION
TP P: 0 – 1200°C
Power Consumption
■ RTD
•AC: Approx. 6 VA
Maximum leadwire resistance: 200 Ω per wire (3 -wire)
Sensing current: ≤ 1.0 mA
•DC: Approx. 3 W
Operating temperature: -30 to +60°C (-22 to +140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 120 g (0.26 lb)
If not specified, the input range is shown below.
R1: JPt 100 0 – 100°C
R3: Pt 100 0 – 100°C
R4: Pt 100 0 – 100°C
R5: Pt 50 Ω 0 – 200°C
R6: Ni 508.4 Ω 0 – 100°C
R7: Pt 1000 0 – 100°C
R8: Ni 100 0 – 100°C
R9: Cu 10 0 – 100°C
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 3/6
http://www.m-system.co.jp/
MODEL: M2XU
Line voltage effect: ±0.1 % over voltage range
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Accuracy: Input accuracy + output accuracy
Input accuracy (% of input range)
Inversely proportional to span.
(DC) -1 – +1 V : ±0.02
-10 – +10 V : ±0.02
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Type -10 – +10 V, Input Range 1 – 5 V,
Output Type 0 – 20 mA, Output Range 0 – 10 mA
Max. Input Range (20 V) ÷ Span (4 V) × 0.02 % = 0.1 %
Max. Output Range (20 mA) ÷ Span (10 mA) × 0.02 % =
0.04 %
0 – 50 mA : ±0.02
Except the input resistor error.
(T/C) (PR) : ±0.08
K (CA) : ±0.02
E (CRC) : ±0.02
J (IC) : ±0.04
Overall accuracy = 0.1 + 0.04 = ±0.14 %
T (CC) : ±0.06
B (RH) : ±0.12
STANDARDS & APPROVALS
EU conformity:
R : ±0.08
S : ±0.08
EMC Directive
C (WRe 5 - 26) : ±0.04
EMI EN 61000-6-4
N : ±0.04
EMS EN 61000-6-2
U : ±0.04
Low Voltage Directive
L : ±0.04
EN 61010-1
P (Platinel II) : ±0.04
Installation Category II
(RTD) JPt 100 (JIS ’89) : ±0.04
Pt 100 (JIS ’89) : ±0.03
Pt 100 (JIS ’97, IEC) : ±0.03
Pt 50 Ω (JIS ’81) : ±0.04
Ni 508.4 Ω : ±0.05
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
EN 50581
Pt 1000 : ±0.08
Approval:
Ni 100 : ±0.14
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
Cu 10 : ±0.6
(Pot.) 0 – 100 Ω : ±0.08
0 – 300 Ω : ±0.04
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
0 – 1000 Ω : ±0.04
0 – 10 kΩ : ±0.04
Output accuracy: ±0.02 % of output range
Inversely proportional to span.
Cold junction compensation error:
±0.4°C or ±0.7°F (at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient
(at -5 to +55°C [23 to 131°F] of I/O range)
Input: ±0.016 %/°C (±0.009 %/°F) with current
±0.004 %/°C (±0.002 %/°F) with voltage
±0.004 %/°C (±0.002 %/°F) with T/C
±0.004 %/°C (±0.002 %/°F) with RTD
±0.004 %/°C (±0.002 %/°F) with Pot.
Output: ±0.013 %/°C (±0.007 %/°F)
Response time:
≤ 0.5 sec.(0 – 90 %) with current
≤ 0.5 sec.(0 – 90 %) with voltage
≤ 1.5 sec.(0 – 90 %) with T/C
≤ 0.9 sec.(0 – 90 %) with RTD
≤ 0.9 sec. (0 – 90 %) with Pot.
Burnout response: ≤ 10 sec.
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 4/6
http://www.m-system.co.jp/
MODEL: M2XU
EXTERNAL VIEW
■ FRONT VIEW (with cover open)
■ RIGHT SIDE VIEW
Configurator Jack
Status Indicator LED
Zero/Span Selector
Input Range Selector
Position H: code S2, Z1
Position L : other
Top: SPAN
Middle: OFF
Bottom: ZERO
UP/DOWN Switches
The front cover cannot be opened to 180 deg.
when flush with neighboring units.
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS unit: mm (inch)
6 (.23)
DIN RAIL
35mm wide
4
1
5
8
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
12
9
8–M3
SCREW
14 13
21.5 (.85) 7.3 (.29)
86.7 (3.41)
116.7 (4.59)
15 (.59)
[4 (.16)]
23 (.91)
• When mounting, no extra space is needed between units.
TERMINAL ASSIGNMENTS unit: mm (inch)
Use the input resistor (model: REM2) for a DC current input,
and the CJC sensor (model: CJM) for a thermocouple input,
both included in the package.
INPUT RESISTOR
(model: REM2)
CJC SENSOR
(model: CJM)
black
red
1
4
1
5
4
5
8
8
12
9
12
9
14 13
14 13
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 5/6
http://www.m-system.co.jp/
MODEL: M2XU
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
DC
T/C
ext. wire
RTD
POT.
INPUT RANGE
SELECTOR
ZERO/SPAN
SELECTOR
Isolation
+
max.
+
+
+
–
Digital
Computation
Output
Driver
1
9
+
A
B
B
3
2
1
–
*
–
R
Low Drift
Amplifier
& Burnout
OUTPUT
POWER
4
12
13
14
–
CJC
SENSOR
(model: CJM)
UP/DOWN
SWITCHES
–
red
5
U(+)
V(–)
min.
black
8
JACK
CONFIGURATOR
Base Socket
*Input shunt resistor attached for current input.
Specifications are subject to change without notice.
M2XU SPECIFICATIONS
ES-5008 Rev.18 Page 6/6
http://www.m-system.co.jp/
相关型号: