M2EAXDY-5R/Q [MSYSTEM]
Super-mini Signal Conditioners with Display Mini-M M2E Series;型号: | M2EAXDY-5R/Q |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners with Display Mini-M M2E Series |
文件: | 总7页 (文件大小:180K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M2EAXDY
5: 2 points; SPDT or transfer contact
Super-mini Signal Conditioners with
Display Mini-M M2E Series
[2] POWER INPUT
AC Power
TWO-WIRE TRANSMITTER ALARM
(PC programmable, dual or quad alarm trip)
Functions & Features
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
• Quad or dual trip
R: 24 V DC
• Settable with front button
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
• ON delay time selectable
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Enclosed relays
• Relays can be powered by 200 V AC and 100 V DC
• Segment linearization and square root extraction
configurable
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
Typical Applications
• Annunciator
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Various alarm applications
/C02: Polyurethane coating
/C03: Rubber coating
29.5
(1.16)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
EX-FACTORY SETTING
83
(3.27)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-5169)
Default setting will be used if not otherwise specified.
Up
Mo
de
Do
wn
124
Se
t
(4.88)
RELATED PRODUCTS
• M2EA configurator software (model: M2EACFG)
mm (inch)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual (EM-5151) for the M2EA configurator for
applicable cable types.
MODEL: M2EAXDY–[1]-[2][3]
ORDERING INFORMATION
• Code number: M2EAXDY-[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. M2EAXDY-2-M2/Q)
GENERAL SPECIFICATIONS
Construction: Plug-in
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (gray)
Isolation: input to L1 or L4 alarm output to L2 or L3 alarm
output to power
INPUT – Field-selectable
Current
4 – 20 mA DC (Input resistance 250 Ω)
(Selectable within 0 – 20 mA DC)
(for output code 5, L3 alarm output and L4 alarm output is
not available)
Configuration: Program with front buttons or Via PC.
Programmable features include: Refer to the parameter list.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
[1] OUTPUT
2: 4 points; N.O. or make contact
3: 4 points; N.C. or break contact
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 1/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
Maximum switching power: 480 VA or 150 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 5 × 10 cycles
DISPLAY
Display functions: Displays and sets measured range,
7
engineering unit
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)
Number of pixels: 68 × 95 (horizontal × vertical)
Character color: Yellow (reversing display of the current
value and the alarm setting value when alarm is tripped)
Display life: Approx. 60000 hours
Alarm Trip Operation Terminal No. in parentheses
• Example Quad N.O. contacts (LL, L, H, HH)
ON OFF
ON OFF
L1 (3–6)
L2 (5–7)
L3 (5–8)
L4 (3–9)
(Expected time for the Display brightness to be reduced to
50 % when the Display is used continuously with brightness
setting 2 in 25 ℃)
OFF ON
OFF ON
Display type: OEL display
Input
%
Display digit: Negative 5 digits, positive 6 digits (-99999 to
999999)
0
50
100
LL
L
H
HH
Decimal point position: Selectable
Trip operation in power failure
Output code 2 : All relays turn OFF.
Output code 3 : All relays turn ON.
SUPPLY OUTPUT
Output code 5 : Terminals 3 – 9, 5 – 8 turn ON.
■ SUPPLY OUTPUT (across the terminals 1 – 2)
Output voltage: 24 – 28 V DC with no load
19 V DC minimum at 20 mA
LINEARIZATION
■ Linearization Types
Current rating: ≤ 22 mA DC
Permissible load resistance:
Linear: Proportional to the input
Square root: The input is square root extracted.
User's table: Segment linearization
LR (Ω) ≤ (19 – Min. Operational Voltage)V ÷ 0.02 A
• Shortcircuit Protection
Current limited: 35 mA max.
Calibration points: Max. 128 points; the input % and
linearized value in scaling are specified in pairs.
Selectable range: -7.5 to +107.5 % as input %; -99999 to
+999999 as linearized values
Protected time duration: No limit
INPUT SPECIFICATIONS
■ DC Current
■ Low-end Cutout:Low-end cutout (Low Cut) point
selectable within the range of 0 to 100 %.
Input resistance: Incorporated (250 Ω)
Input range: 0 - 20 mA DC
With linear or segment linearization,
the output signal is forcibly set to 0 % for the input lower
than the low-cut point. With the square root extraction, the
output signal is linear to the input when the latter is lower
than the low-cut point.
Minimum span: 1 mA DC
The measurement available for -7.5 - +107.5% of input
setting range.
• Linear or User Table
• Square Root
OUTPUT SPECIFICATIONS
■ Quad Alarm
Relay rating: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Low-end cutout
point
Low-end cutout
point
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
0
0
input percent
input percent
0.2%
0.2%
Mechanical life: 5 × 10
7
cycles
■ DUAL ALARM
Relay rating: 100 V AC @ 4 A (cos ø = 1)
120 V AC @ 4 A (cos ø = 1)
INSTALLATION
Power Consumption
•AC:
240 V AC @ 2 A (cos ø = 1)
30 V DC @ 4 A (resistive load)
≤ 7 VA at 100 V
Maximum switching voltage: 250 V AC or 125 V DC
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 2/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
≤ 10 VA at 200 V
≤ 12 VA at 264 V
•DC: ≤ 4 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 10 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 200 g (0.44 lb)
PERFORMANCE
Accuracy (display accuracy, setting accuracy): differs
depending on the linearization type.
Linear: ±(0.08 % of FS + 1 digit)
Square root extraction (1 % or more of input): ±(0.15 % of
FS + 1 digit)
Segment linearization:
±(0.08 % of FS + 1 digit) [gain ≤ 1]
±(0.08 % x gain of FS + 1 digit) [gain > 1]
See CALCULATION EXAMPLES OF OVERALL ACCURACY.
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time (Filter time constant: 0 sec.): ≤ 0.5 sec.
(0 – 100 % at 90 % setpoint)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to L1 or L4
alarm output to L2 or L3 alarm output to power to ground)
(for output code 5, L3 alarm output and L4 alarm output is
not available)
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Range: 0 – 20 mA, Input Setting: 4 – 20 mA
(when the linearization type is linear)
• Accuracy = Input Range Span (20 mA) ÷ Input Span
Setting (16 mA) × 0.08 % = ±0.1 % + 1 digit
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
L1 or L4 alarm output to L2 or L3 alarm output:
Basic insulation (300 V)
RoHS Directive
EN 50581
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 3/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
EXTERNAL VIEW
Display
PERCENT
50.00
%
L4
L3
L2
L1
80.00
70.00
30.00
20.00
▲
▲
▼
▼
Up Button
Mode Button
Set Button
Down Button
Up
Mode
Configurator Jack
Down
Set
COMPONENT
Display
FUNCTION
Indicates present values, setting values and abnormal information. Two types of present values at upper
and lower are displayed by setting.
Mode button
Set button
Used to shift from measuring mode to each setting mode. Destination to shift is changed by the time press-
ing and holding the button. Used to return from each setting mode to measuring mode. (press and hold for
2 sec. or more)
Used to change setting value of setting parameter. When at setting changeable state, used to enter (save)
the setting value. Used to move on through digits of setting value for input scaling at setting changeable
state.
Used to release latching alarm in measuring mode (hold down more than 2 seconds).
Up button
Used to shift through setting parameter, and to increase or select setting value.
Used to shift through setting parameter, and to decrease or select setting value.
Down button
Con!gurator Jack
Used to con!gure with M2EA con!gurator software (model: M2EACFG). At the same time, set the lockout
setting of the unit to ‘lock’.
Refer to the operating manual (EM-5169-B) for detailed procedures.
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 4/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
PARAMETER LIST
MODE
ITEM SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Basic setting
01
12
13
14
15
16
Lockout setting
Lock / Unlock
—
mA
mA
—
Lock
0 % input setting
100 % input setting
0 % input scaling
100 % input scaling
Input decimal point
0.00 – 19.00
4.00
1.00 – 20.00
20.00
-99999 – 999999
-99999 – 999999
No decimal point
The number of decimal places : 1 – 5
0.00
—
100.00
—
2 places of decimals
17
24
Unit (INP Scaling)
Low cut
Choose from 68 types
Enable / Disable
0.00 – 100.00
*
—
—
%
Disable
0.00
25
Low cut point
%
—
—
—
—
—
—
—
30
31
32
33
34
40
41
L1 alarm enable
L1 alarm setpoint
L1 trip action
Enable
Enable / Disable
-99999 – 999999
High / Low
20.00
Low
L1 deadband
0 – 999999
0.01
L1 coil at alarm
L2 alarm enable
L2 alarm setpoint
Energized / De-energized
Enable / Disable
Energized
Enable
-99999 – 999999
80.00 (2 points alarm)
30.00 (4 points alarm)
42
L2 trip action
High / Low
—
High (2 points alarm)
Low (4 points alarm)
43
44
50
51
52
53
54
60
61
62
63
64
70
71
72
89
79
80
81
01
91
L2 deadband
0 – 999999
—
—
0.01
L2 coil at alarm
L3 alarm enable
L3 alarm setpoint
L3 trip action
Energized / De-energized
Enable / Disable
-99999 – 999999
High / Low
Energized
—
Enable
—
70.00
—
High
L3 deadband
0 – 999999
—
0.01
L3 coil at alarm
L4 alarm enable
L4 alarm setpoint
L4 trip action
Energized / De-energized
Enable / Disable
-99999 – 999999
High / Low
—
Energized
—
Enable
—
80.00
—
High
L4 deadband
0 – 999999
—
0.01
L4 coil at alarm
Alarm ON-delay time
Power ON-delay time
Latching alarm
Alarm test
Energized / De-energized
0 – 999
—
Energized
sec.
sec.
—
0
0 – 999
5
Enable / Disable
—
Disable
—
Cancel
Option
Filter time constant
Input Zero !ne adjust
Input Span !ne adjust
Lockout setting
Display setting
0 – 30
sec.
%
0
-5.000 – 5.000
95.000 – 105.000
Lock / Unlock
0.000
%
100.000
—
Lock
Advanced
Upper: choose from 3 types
Lower: choose from 5 types
1 (darkest) – 4 (brightest)
0 (always on), 1 – 60
OFF / RESET
*
—
Upper: INPUT (Scaling)
Lower: ALARM
*
92
93
94
95
01
Brightness
—
min.
—
4
Display timeout
Reset all settings
Version indication
Lockout setting
10
OFF
—
—
—
Lock / Unlock
—
Lock
Linearization
100 Linearization
Linear, Square root, User’s table
2 – 128
—
Linear
2
166 Number of points
—
Table
167 –
422
-7.50 – 107.50 (X)
-99999 – 999999 (Y)
% (X)
— (Y)
X001 -7.50
Y001 -7.50
X002 107.50
Y002 107.50
01
Lockout setting
Lock / Unlock
—
Lock
* For detailed types, refer to the operating manual (EM-5169-B).
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 5/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
6 (.23)
3
2
5
1
4
2–4.2x5
(.17x.20)
6
MTG HOLE
6 (.24) deep
DIN RAIL
35mm wide
9
8
7
11–M3
SCREW
11 10
22 (.87)
29 (1.14)
94 (3.70)
124 (4.88)
29.5 (1.16)
8
[4 (.16)]
(.31)
• When mounting, no extra space is needed between units.
M2EAXDY SPECIFICATIONS
ES-5169 Rev.1 Page 6/7
http://www.m-system.co.jp/
MODEL: M2EAXDY
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■OUTPUT CODE 2: N.O. Relay
■OUTPUT CODE 3:
N.C. Relay
2-WIRE
TRANSMITTER
RY
24V DC
Supply
Shortcircui
Portection
9
6
L4 OUTPUT
L1 OUTPUT
COM
9
6
3
8
7
5
L4 OUTPUT
L1 OUTPUT
COM
+
+
–
1
2
RY
–
Digital
Computation
Circuit
200Ω
3
+
4
MONITOR
V
(1 – 5V DC)
RY
RY
–
50Ω
8
L3 OUTPUT
L2 OUTPUT
COM
L3 OUTPUT
L2 OUTPUT
COM
7
CONFIGURATOR
JACK
5
Display
Circuit
10
11
U(+)
POWER
CONTROL
SW
V(–)
Base Socket
■OUTPUT CODE 5: SPDT Relay
2-WIRE
TRANSMITTER
24V DC
Supply
Shortcircui
Portection
9
6
N.C.
N.O.
COM
N.C.
N.O.
COM
U(+)
+
+
–
1
2
RY
RY
L1 OUTPUT
–
Digital
Computation
Circuit
200Ω
3
+
4
MONITOR
V
(1 – 5V DC)
–
50Ω
8
7
CONFIGURATOR
JACK
L2 OUTPUT
POWER
5
Display
Circuit
10
CONTROL
SW
11 V(–)
Base Socket
■ Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Varistor or Spark
Quenching Circuit
Diode, Varistor or
CR Circuit
LOAD
LOAD
U
■
When 24V DC is Not Used
No Connection
1
2
4
+
200Ω
50Ω
INPUT
–
Specifications are subject to change without notice.