MODEL: M1EAXV-1
Multi-output Super-mini Signal Conditioners
with Display M1E-1 Series
INPUT – Field-selectable
◆ DC Input
• Current input: 0 - 50 mA DC
• Voltage input: -1000 - +1000 mV DC
• Voltage input: -10 - +10 V DC
DC ALARM
(PC programmable, quad or octad alarm trip)
Functions & Features
[1] OUTPUT
• Provides relay outputs at preset DC input levels
• Octad or quad trip
A: 8 points; N.O. or make contact
B: 8 points; N.C. or break contact
C: 4 points; SPDT or transfer contact
• Front LCD display indicating values in scaled engineering
unit range is used to program the module
• Adjustable deadband (hysteresis)
• ON delay time selectable
POWER INPUT
DC Power
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
R: 24 V DC
• Settable with front buttons
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Enclosed relays
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
[2] OPTIONS
blank: none
/Q: With options (specify the specification)
Typical Applications
• Annunciator
• Various alarm applications
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
36 (1.42)
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-6031)
99
(3.90)
RELATED PRODUCTS
• Installation base (model: M1E-BS2)
125 (4.92)
• M1EA configurator software (model: M1EACFG)
Downloadable at M-System’s web site.
mm (inch)
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual (EM-5994) for the M1EA configurator for
applicable cable types.
Note: The !gure shows the combination
of the unit and the base.
MODEL: M1EAXV–1-[1]-R[2]
GENERAL SPECIFICATIONS
Construction: Plug-in
ORDERING INFORMATION
• Code number: M1EAXV-1-[1]-R[2]
Specify a code from below for each of [1] and [2].
(e.g. M1EAXV-1-A-R/Q)
Connection
• Connected to base with connector
• Base
• Specify the specification for option code /Q
(e.g. /C01/SET)
M2.6 screw terminals (torque: 0.5 N·m)
Applicable solderless terminal size (M3)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation:
NO. OF CHANNELS
1: 1 channel
• Output code A, B: Input to L1 or L2 alarm output to L3 or
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 1/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
L4 alarm output to L5 or L6 alarm output to L7 or L8 alarm
output to power
OUTPUT SPECIFICATIONS
Relay rating: 100 V AC @ 0.5 A (cos ø = 1)
• Output code C: Input to L1 alarm output to L2 alarm
output to L3 alarm output to L4 alarm output to power
Configuration: Program with front buttons or Via PC.
Programmable features include: Refer to the parameter list.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
120 V AC @ 0.5 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 1 mA
■Recommended solderless terminal size - M3 (unit: mm)
Mechanical life: 5 × 10 cycles
7
3max
4min
Alarm Trip Operation
3.2 dia.
• Example Quad N.O. contacts (LL, L, H, HH)
L1
L2
L3
L4
ON OFF
ON OFF
12max
OFF ON
OFF ON
(mm)
Input
%
DISPLAY
0
▲
▲
50
▲
▲
100
LL
L
H
HH
Display functions: Displays and sets measured range,
Trip operation in power failure
engineering unit
Output code A: All relays turn OFF.
Output code B: All relays turn ON.
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)
Number of pixels: 68 × 95 (horizontal × vertical)
Character color: Yellow (reversing display of the current
value and the alarm setting value when alarm is tripped)
Display life: Approx. 50000 hours
Output code C: Terminals 13 – 15, 16 – 18, 6 – 12,
1 – 7 turn ON.
(Expected time for the Display brightness to be reduced to
50 % when the Display is used continuously with brightness
setting 2 in 25 ℃)
INSTALLATION
Power consumption
•DC: ≤ 6 W
Display type: OEL display
Operating temperature: -5 to +55°C (23 to 131°F)
Storage temperature: -5 to +55°C (23 to 131°F)
Display digit: Negative 5 digits, positive 6 digits (-99999 to
999999)
Operating humidity: 10 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
Decimal point position: Selectable
Weight: 150 g (0.33 lb) except base
INPUT SPECIFICATIONS
■ DC Current
PERFORMANCE in percentage of FS input
Accuracy (display accuracy, setting accuracy):
± (0.1% of FS + 1 digit)
Input resistance: Incorporated (28 Ω)
Input range: 0 - 50 mA DC
Minimum span: 2 mA
See CALCULATION EXAMPLES OF OVERALL ACCURACY.
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time (Filter time constant: 0 sec.): ≤ 0.5 sec.
(0 – 100 % at 90 % setpoint)
The measurement available for -5 - +105% of input setting
range.
■ DC Voltage
•Narrow Spans (mV)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
Input range: -1000 – +1000 mV DC
Minimum span: 100 mV
•Wide Spans (V)
• Output code A, B: 1500 V AC @ 1 minute (Input to L1 or L2
alarm output to L3 or L4 alarm output to L5 or L6 alarm
output to L7 or L8 alarm output to power to ground)
• Output code C: 1500 V AC @ 1 minute (Input to L1 alarm
output to L2 alarm output to L3 alarm output to L4 alarm
output to power to ground
Input range: -10 – +10 V DC
Minimum span: 1 V
Input resistance: 1 MΩ minimum
The measurement available for -5 - +105% of input setting
range.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 2/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Range -10 – +10 V, Input Setting -5 – +5 V
• Accuracy = Input Range Span (20 V) ÷ Input Span Setting
(10 V) × 0.1 % = ±0.2 % + 1 digit
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Pollution Degree 2
• Output code A, B
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
L1 or L2 alarm output to L3 or L4 alarm output to L5 or L6
alarm output to L7 or L8 alarm output: Basic insulation (300
V)
• Output code C
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
L1 alarm output to L2 alarm output to L3 alarm output to L4
alarm output: Basic insulation (300 V)
RoHS Directive
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 3/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
EXTERNAL VIEW
Display
Up Button
Down Button
Set Button
Mode Button
Configurator Jack
■ COMPONENT FUNCTION
COMPONENT
Display
FUNCTION
Indicates present values, setting values and abnormal information. Two types of present values at upper
and lower are displayed by setting.
Mode button
Used to shift from measuring mode to each setting mode. The destination changes depending on how long
the button is held down. Used to return from each setting mode to measuring mode (press and hold for 2
sec. or more).
Up button
Used to shift through setting parameters and to increase or select setting value.
Used to shift through setting parameter and to decrease or select setting value.
Down button
Set button
Used to change setting value of setting parameter. When at setting changeable state, used to enter (save)
the setting value. Used to move through the digits of setting value at setting changeable state.
Used to release latching alarm in measuring mode (press and hold for 2 sec. or more).
Congurator Jack
Used to congure with M1EA congurator software (model: M1EACFG). At the same time, set the lockout
setting of the unit to ‘lock’.
Refer to the operating manual (EM-6031-B) for detailed procedures.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 4/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
TERMINAL ASSIGNMENTS
1
6
2
7
3
8
4
9
5
10
11
16
12
17
13
18
14
19
15
20
• OUTPUT CODE: A, B
• OUTPUT CODE: C
No. FUNCTION
No. FUNCTION
No. FUNCTION
No. FUNCTION
1
2
COM4 (L7, L8)
L7 Alarm output
Input voltage +
Input current +
Input –
11
12
13
14
15
16
17
18
19
20
L5 Alarm output
1
2
COM4 (L4)
NO (L4)
11
12
13
14
15
16
17
18
19
20
NO (L3)
NC (L3)
COM1 (L1)
NO (L1)
NC (L1)
COM2 (L2)
NO (L2)
NC (L2)
Power +
Power –
L6 Alarm output
COM1 (L1, L2)
L1 Alarm output
L2 Alarm output
COM2 (L3, L4)
L3 Alarm output
L4 Alarm output
Power +
3
3
Input voltage +
Input current +
Input –
4
4
5
5
6
COM3 (L5, L6)
L8 Alarm output
No connection
No connection
No connection
6
COM3 (L3)
NC (L4)
7
7
8
8
No connection
No connection
No connection
9
9
10
Power –
10
* Base does not come with the unit. Please order separately.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 5/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
PARAMETER LIST
The following parameters can be set or checked, by the front button operation, or from the PC by using M1EA conguration
software (model: M1EACFG).
MODE
ITEM SETTING PARAMETER
RANGE
UNIT
—
INITIAL VALUE
Lock
Input setting
01
11
Lockout setting
Input range
Lock / Unlock
0 – 50 mA
-1000 – +1000 mV
-10 – +10 V
—
0 – 50 mA
12
13
0 % input setting
0.00 – 48.00
-1000.0 – 900.0
-10.000 – 9.000
mA
mV
V
4.00
100 % input setting
2.00 – 50.00
-900.0 – 1000.0
-9.000 – 10.000
mA
mV
V
20.00
14
15
16
0 % input scaling
100 % input scaling
Input decimal point
-99999 – 999999
-99999 – 999999
—
—
—
0.00
100.00
No decimal point
The number of decimal places : 1 – 5
2 places of decimals
17
79
80
81
30
31
32
33
34
40
41
Unit (INP Scaling)
Filter time constant
Input Zero ne adjust
Input Span ne adjust
L1 alarm enable
L1 alarm setpoint
L1 trip action
Choose from 68 types
0 – 30
*
—
sec.
%
%
0
-5.000 – 5.000
95.000 – 105.000
Disable / Enable
0.000
100.000
Enable
10.00
Low
%
Alarm setting
—
—
—
—
—
—
—
-99999 – 999999
High / Low
*
L1 deadband
0 – 999999
*
0.01
L1 coil at alarm
Energized / De-energized
Disable / Enable
Energized
Enable
L2 alarm enable
L2 alarm setpoint
-99999 – 999999
*
30.00 (4 points alarm)
20.00 (8 points alarm)
42
43
44
50
51
L2 trip action
High / Low
—
—
—
—
—
Low
L2 deadband
0 – 999999
*
0.01
L2 coil at alarm
L3 alarm enable
L3 alarm setpoint
Energized / De-energized
Disable / Enable
Energized
Enable
-99999 – 999999
*
70.00 (4 points alarm)
30.00 (8 points alarm)
52
L3 trip action
High / Low
—
High (4 points alarm)
Low (8 points alarm)
53
54
60
61
L3 deadband
0 – 999999
*
—
—
—
—
0.01
L3 coil at alarm
L4 alarm enable
L4 alarm setpoint
Energized / De-energized
Disable / Enable
Energized
Enable
-99999 – 999999
*
90.00 (4 points alarm)
40.00 (8 points alarm)
62
L4 trip action
High / Low
—
High (4 points alarm)
Low (8 points alarm)
63
64
L4 deadband
0 – 999999
*
—
—
0.01
L4 coil at alarm
Energized / De-energized
Energized
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 6/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
MODE
ITEM SETTING PARAMETER
130 L5 alarm enable
131 L5 alarm setpoint
132 L5 trip action
RANGE
UNIT
—
INITIAL VALUE
Enable
60.00
Alarm setting
Disable / Enable
-99999 – 999999*
High / Low
—
—
High
133 L5 deadband
0 – 999999*
—
0.01
134 L5 coil at alarm
140 L6 alarm enable
141 L6 alarm setpoint
142 L6 trip action
Energized / De-energized
Disable / Enable
-99999 – 999999*
High / Low
—
Energized
Enable
70.00
—
—
—
High
143 L6 deadband
0 – 999999*
—
0.01
144 L6 coil at alarm
150 L7 alarm enable
151 L7 alarm setpoint
152 L7 trip action
Energized / De-energized
Disable / Enable
-99999 – 999999*
High / Low
—
Energized
Enable
80.00
—
—
—
High
153 L7 deadband
0 – 999999*
—
0.01
154 L7 coil at alarm
160 L8 alarm enable
161 L8 alarm setpoint
162 L8 trip action
Energized / De-energized
Disable / Enable
-99999 – 999999*
High / Low
—
Energized
Enable
90.00
—
—
—
High
163 L8 deadband
0 – 999999*
—
0.01
164 L8 coil at alarm
Energized / De-energized
0 – 999
—
Energized
0
70
71
72
89
01
Alarm ON-delay time
Power ON-delay time
Latching alarm
sec.
sec.
—
0 – 999
5
Disable / Enable
—
Disable
Cancel
Lock
Alarm test
—
Lockout setting
Lock / Unlock
—
Advanced
201 Display setting
Upper: choose from 4 types*
Lower: choose from 5 types*
—
Upper: INPUT (Scaling)
Lower: ALARM
203 Brightness
1 (darkest) – 4 (brightest)
0 (always on), 1 – 60
OFF / RESET
—
—
min.
—
4
204 Display timeout
205 Reset all settings
206 Version indication
10
OFF
—
—
01
Lockout setting
Lock / Unlock
—
Lock
* For details, refer to the operating manual (EM-6031-B).
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
125 (4.92)
[4 (.16)]
45 (1.77)
36 (1.42)
1
6
2
7
3
8
4
9
5
10
DIN RAIL
35mm wide
11 12 13 14 15
16
18 19 20
17
* Base does not come with the unit.
Please order separately.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 7/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
MOUNTING REQUIREMENTS unit: mm [inch]
2–M4 SCREW
* Mounting requirements for base.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 8/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ OUTPUT CODE A: N.O. RELAY
+
RY
RY
Isolation
L2 OUTPUT
L1 OUTPUT
COM1
15
14
13
18
17
16
12
11
6
3
+
INPUT
Low Drift
4
VOLTAGE
INPUT
CURRENT
Amplifier
5
–
28Ω
–
RY
RY
L4 OUTPUT
L3 OUTPUT
COM2
CONFIGURATOR
JACK
Digital
Computation
Circuit
8
9
RY
RY
L6 OUTPUT
L5 OUTPUT
COM3
10
RY
RY
7
L8 OUTPUT
L7 OUTPUT
COM4
2
1
Display
Circuit
+
19
20
POWER
Front
Button
–
Base
■ OUTPUT CODE B: N.C. RELAY
15
14
13
18
17
16
L2 OUTPUT
L1 OUTPUT
COM1
L4 OUTPUT
L3 OUTPUT
COM2
12
11
6
L6 OUTPUT
L5 OUTPUT
COM3
7
L8 OUTPUT
L7 OUTPUT
COM4
2
1
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 9/10
https://www.m-system.co.jp/
MODEL: M1EAXV-1
■ OUTPUT CODE C: SPDT RELAY
+
3
Isolation
N.C.
N.O.
COM1
N.C.
N.O.
COM2
N.C.
N.O.
COM3
N.C.
N.O.
COM4
+
15
14
13
18
17
16
12
11
6
+
RY
RY
INPUT
Low Drift
Amplifier
L1 OUTPUT
L2 OUTPUT
L3 OUTPUT
4
VOLTAGE
INPUT
CURRENT
5
–
–
28Ω
CONFIGURATOR
JACK
Digital
Computation
Circuit
8
9
RY
RY
10
7
L4 OUTPUT
POWER
2
1
Display
Circuit
19
20
Front
Button
–
Base
• Relay Protection
· AC Powered
· DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Diode, Varistor or
CR Circuit
Varistor or Spark
Quenching Circuit
LOAD
LOAD
U
Specifications are subject to change without notice.
M1EAXV-1 SPECIFICATIONS
ES-6031 Rev.2 Page 10/10
https://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明