LTCEC-275F-V/Q [MSYSTEM]

Power Transducer Series LT-UNIT;
LTCEC-275F-V/Q
型号: LTCEC-275F-V/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Power Transducer Series LT-UNIT

文件: 总6页 (文件大小:175K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: LTCEC  
Power Transducer Series LT-UNIT  
[2] INPUT  
10: 0 – 10 A AC  
15: 0 – 15 A AC  
20: 0 – 20 A AC  
30: 0 – 30 A AC  
40: 0 – 40 A AC  
50: 0 – 50 A AC  
60: 0 – 60 A AC  
75: 0 – 75 A AC  
100: 0 – 100 A AC  
125: 0 – 125 A AC  
150: 0 – 150 A AC  
175: 0 – 175 A AC  
200: 0 – 200 A AC  
225: 0 – 225 A AC  
250: 0 – 250 A AC  
300: 0 – 300 A AC  
350: 0 – 350 A AC  
400: 0 – 400 A AC  
500: 0 – 500 A AC  
AC CURRENT TRANSDUCER  
(clamp-on current sensor; RMS sensing)  
Functions & Features  
• Converts an alternating current into a standard  
process signal  
• Easy-to-install clamp-on type current sensor  
without needing a current transformer  
• Clamp-on current sensor included  
• Wide input range from 10 A up to 600 A  
• Input frequency 50 / 60 / 400 Hz  
• Over-voltage clamp element for safety in open  
circuit  
• High-density mounting  
Typical Applications  
• Centralized monitoring and control of motors at  
a supervisory panel  
• Monitoring abnormal load current at motors to  
detect pump malfunctions  
600: 0 – 600 A AC (Not selectable with the sensor type  
code 1 'Leadwire type CLSA')  
72  
(2.83)  
[3] OUTPUT  
Current  
A: 4 – 20 mA DC (Load resistance 500 Ω max.)  
D: 0 – 20 mA DC(Load resistance 500 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1000 Ω max.)  
G: 0 – 1 mA DC (Load resistance 10 kΩ max.)  
J: 0 – 5 mA DC (Load resistance 2000 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
111  
(4.37)  
143 (5.63)  
mm (inch)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
MODEL: LTCEC–[1][2][3]–[4][5]  
ORDERING INFORMATION  
• Code number: LTCEC–[1][2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. LTCEC-150A-B/T/Q)  
[4] AUXILIARY POWER SUPPLY  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01)  
AC Power  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
DC Power  
R: 24 V DC  
[1] SENSOR  
1: Leadwire type CLSA  
2: Screw terminal type CLSB  
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 1/6  
http://www.m-system.co.jp/  
MODEL: LTCEC  
V: 48 V DC  
Weight: 45 g (1.6 oz)  
P: 110 V DC  
0 – 60 A through 0 – 100 A Use  
Sensor model No.: CLSB-10  
Applicable cable diameter: Max. 16.0  
Weight: 80 g (2.8 oz)  
[5] OPTIONS (multiple selections)  
Terminal Cover  
0 – 125 A through 0 – 200 A Use  
Sensor model No.: CLSB-20  
blank: Without  
/T: With  
Applicable cable diameter: Max. 24.0  
Weight: 200 g (7.1 oz)  
Other Options  
blank: none  
0 – 225 A through 0 – 400 A Use  
Sensor model No.: CLSB-40  
/Q: Option other than the above (specify the specification)  
Applicable cable diameter: Max. 35.0  
Weight: 300 g (10.6 oz)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
0 – 500 A through 0 – 600 A Use  
Sensor model No.: CLSB-60  
/C02: Polyurethane coating  
Applicable cable diameter: Max. 35.0  
Weight: 360 g (12.7 oz)  
/C03: Rubber coating  
Note 1: The output values may vary depending on the  
accuracy of engagement at the clamp connection.  
Note 2: The sensor is detachable up to 100 times (approx.).  
Note 3: The sensor’s mechanical construction may cause it  
to generate resonance sound. However, it does not affect  
the performance of the sensor.  
ACCESSORIES  
The clamp-on current sensor is included in the product  
package.  
CLAMP-ON CURRENT SENSOR (leadwire type CLSA)  
0 – 10 A through 0 – 75 A Use  
Sensor model No.: CLSA-08  
Sensor cable model No.: CLSA-08C-30  
Applicable cable diameter: Max. 10.0  
Sensor leadwire: AWG 22  
GENERAL SPECIFICATIONS  
Connection: M4 screw terminals (torque 1.2 N·m)  
Screw terminal: Chrome-plated steel  
Weight: 45 g (1.6 oz)  
Housing material: Flame-resistant resin (black)  
Isolation: Sensor core to sensor output or input to output to  
auxiliary power  
0 – 100 A Use  
Sensor model No.: CLSA-12  
Sensor cable model No.: CLSA-08C-30  
Applicable cable diameter: Max. 16.0  
Sensor leadwire: AWG 22  
Input waveform: Up to 15 % of 3rd harmonic content  
Overrange output: 0 to 120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Weight: 70 g (2.5 oz)  
Span adjustment: 95 to 105 % (front)  
0 – 125 A through 0 – 300 A Use  
Sensor model No.: CLSA-30  
INPUT SPECIFICATIONS  
Frequency: 50 / 60 / 400 Hz  
Overload capacity  
Applicable cable diameter: Max. 24.0  
Sensor leadwire: AWG 18, 200 mm  
Weight: 200 g (7.1 oz)  
CLSA-08: 120 A continuous  
0 – 350 A through 0 – 500 A Use  
Sensor model No.: CLSA-50  
CLSA-12: 300 A continuous  
CLSA-30: 360 A continuous  
Applicable cable diameter: Max. 36.0  
Sensor leadwire: AWG 18, 200 mm  
Weight: 300 g (10.6 oz)  
CLSA-50: 600 A continuous  
CLSB-05: 100 A continuous  
CLSB-10: 200 A continuous  
CLAMP-ON CURRENT SENSOR (screw terminal type CLSB)  
Connection: M3 screw terminal (torque 0.5 N·m)  
Screw terminal: Nickel-plated steel  
Output wiring: Use AWG22 or thicker wires for the output.  
Twist the paired wires, extendable up to 30 meters.  
0 – 10 A through 0 – 50 A Use  
Sensor model No.: CLSB-05  
CLSB-20: 300 A continuous  
CLSB-40: 600 A continuous  
CLSB-60: 720 A continuous  
Operational range: 0 – 120 % of rating  
Note: Be sure that the input voltage is of 440 V or less.  
Applicable cable diameter: Max. 10.0  
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 2/6  
http://www.m-system.co.jp/  
MODEL: LTCEC  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 10 V max.  
DC Voltage: 0 – 12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V  
• Operation Diagram (example)  
OUT  
20mA  
OUT  
10V  
12  
4
5
0
0
25  
50A  
IN  
0
25  
50A  
IN  
INSTALLATION  
Auxiliary Power  
AC: Operational voltage range: rating -15/+10 %,  
50/60 Hz, approx. 3 VA  
DC: Operational voltage range for R, V: Rating  
±10 % or P: 85 – 150 V; ripple 10 %p-p max.  
approx. 1.7 W (15 mA at 110 V)  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 450 g (0.99 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.5 % (±1.0 % at 400 Hz) at 23°C ±10°C  
or 73.4°F ±18°F, 45 – 65 Hz  
Magnetic field (ext. origin) effect: ± 0.5 % (400 A/m)  
Response time: ≤ 1 sec. (0 – 100 % ±1 %)  
Ripple: 0.5 %p-p max.  
Line voltage effect: ±0.25 % over voltage range  
Insulation resistance: ≥100 MΩ with 500 V DC  
(input to output to auxiliary power)  
≥100 MΩ with 500 V DC  
(sensor core to sensor output)  
Dielectric strength: 2000 V AC @ 1 minute  
(input to output to auxiliary power to ground)  
1000 V AC @ 1 minute  
(sensor core to sensor output)  
Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV  
(input to output or ground)  
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 3/6  
http://www.m-system.co.jp/  
MODEL: LTCEC  
CONNECTION DIAGRAM  
SOURCE  
CONNECTOR*  
k
1
2
11  
12  
15  
16  
+
OUTPUT  
CLAMP-ON SENSOR  
l
U(+)  
V(–)  
LOAD  
AUXILIARY POWER  
*Connector provided only for the CLSA-08 and CLSA-12.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 (.39)  
16–M4 SCREW  
2–M4 MTG HOLE  
TERMINAL COVER (option /T)  
DIN RAIL  
35mm wide  
1
2
3
4
5
6
7
8
9
10  
11 12 13 14 15 16  
8 (.31)  
[4 (.16)]  
54 (2.13)  
72 (2.83)  
3
(.12)  
143 (5.63)  
• When mounting, no extra space is needed between units.  
■ Sensor model No.: CLSA-08  
■ Sensor model No.: CLSA-30  
64 (2.52)  
40 (1.57)  
200 (7.87)  
41 (1.61)  
10 (.39)  
150 (5.91)  
3000 (118)  
24 (.94)  
dia.  
4
34 (1.34)  
4
26 (1.02)  
27 (1.05)  
dia.  
(.16)  
(.16)  
k
l
k
L
K
l
K
L
■ Sensor model No.: CLSA-12  
44.5 (1.75)  
16 (.63)  
150 (5.91)  
3000 (118)  
■ Sensor model No.: CLSA-50  
30 (1.18)  
dia.  
31 (1.22)  
80 (3.15)  
50 (1.97)  
200 (7.87)  
36 (1.41)  
4
38 (1.50)  
4
dia.  
l
(.16)  
(.16)  
k
k
L
K
l
K
L
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 4/6  
http://www.m-system.co.jp/  
MODEL: LTCEC  
■ Sensor model No.: CLSB-05  
8.6 26.3 (1.04) 8.6  
48 (1.89)  
(.34)  
(.34)  
2–M3 SCREW  
10 dia. (.39)  
l
l
k
k
K
L
TERMINAL COVER  
(detachable)  
■ Sensor model No.: CLSB-10  
7.5 30.5 (1.20) 7.5  
53.7 (2.11)  
(.30)  
(.30)  
2–M3 SCREW  
16 dia. (.63)  
l
k
l
k
K
L
TERMINAL COVER  
(detachable)  
■ Sensor model No.: CLSB-20  
8.3  
(.33)  
35.9  
(1.41)  
8.3  
(.33)  
75.7 (2.98)  
2–M3 SCREW  
24 dia. (.94)  
l
l
k
k
K
L
TERMINAL COVER  
(detachable)  
■ Sensor model No.: CLSB-40  
8.8 35.5  
8.8  
(.35)  
93 (3.66)  
2–M3 SCREW  
(.35)  
(1.40)  
35 dia. (1.38)  
l
l
k
k
K
L
TERMINAL COVER  
(detachable)  
■ Sensor model No.: CLSB-60  
8.8 35.5  
8.8  
(.35)  
93 (3.66)  
(.35)  
(1.40)  
2–M3 SCREW  
35 dia. (1.38)  
l
l
k
k
K
L
TERMINAL COVER  
(detachable)  
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 5/6  
http://www.m-system.co.jp/  
MODEL: LTCEC  
Specifications are subject to change without notice.  
LTCEC SPECIFICATIONS  
ES-3373 Rev.9 Page 6/6  
http://www.m-system.co.jp/  

相关型号:

LTCHK

20mA, 3V to 80V Low Dropout Micropower Linear Regulator
Linear

LTCHN

20mA, 3V to 80V Low Dropout Micropower Linear Regulator
Linear

LTCMN

Dual High Voltage, High Side Current Sense Amplifier
Linear

LTCN5M

SMD ceramic package with silicone resin with lens
OSRAM

LTCN5M-GAHB-25-1

Camera Flash and Video Light
OSRAM

LTCNE

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-13

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-13/Q

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-13/T

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-14

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-14/Q

Power Transducer Series LT-UNIT
MSYSTEM

LTCNE-14/T

Power Transducer Series LT-UNIT
MSYSTEM