KWYV-A6A-B/Q [MSYSTEM]
Plug-in Signal Conditioners K-UNIT;型号: | KWYV-A6A-B/Q |
厂家: | M-SYSTEM |
描述: | Plug-in Signal Conditioners K-UNIT |
文件: | 总3页 (文件大小:108K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: KWYV
Plug-in Signal Conditioners K-UNIT
[3] OUTPUT 2
Current
A: 4 – 20 mA DC (Load resistance 350 Ω max.)
Voltage
ISOLATOR
(two isolated outputs)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
Functions & Features
• Standard instrumentation signal isolator with two
outputs
POWER INPUT
AC Power
• Isolation up to 2000 V AC
• High-density mounting
B: 100 V AC
Typical Applications
[4] OPTIONS
blank: none
• Isolation between control room and field instrumentation
/Q: With options (specify the specification)
50
(1.97)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
80
(3.15)
/C02: Polyurethane coating
/C03: Rubber coating
132
TERMINAL SCREW MATERIAL
/S01: Stainless steel
(5.20)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Plug-in
MODEL: KWYV–[1][2][3]–B[4]
Connection: M3.5 screw terminals
ORDERING INFORMATION
• Code number: KWYV-[1][2][3]-B[4]
Specify a code from below for each of [1] through [4].
(e.g. KWYV-6AA-B/Q)
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Adjustable individually for each output 1 and output 2.
• Specify the specification for option code /Q
(e.g. /C01/S01)
Note: When the user requires a current and a voltage
output, specify the current to be the Output 1 which allows
a greater load.
INPUT SPECIFICATIONS
■ DC Current:
[1] INPUT
Current
Shunt resistor attached to the input terminals (0.5 W)
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
INSTALLATION
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
Power input
•AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
[2] OUTPUT 1
Current
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
Weight: 400 g (0.88 lb)
KWYV SPECIFICATIONS
ES-3517 Rev.5 Page 1/3
http://www.m-system.co.jp/
MODEL: KWYV
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute
(input to output to power to ground)
1000 V AC @ 1 minute (output 1 to output 2)
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
9
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
8
7
6
5
4
9
3
2
10 11
1
Input shunt resistor attached
for current input.
KWYV SPECIFICATIONS
ES-3517 Rev.5 Page 2/3
http://www.m-system.co.jp/
MODEL: KWYV
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
Z
S
Isolation
Low Drift
Amplifier
Output
Driver
+
–
5
6
4
3
9
1
2
+
–
*
INPUT
R
OUTPUT 1
S
Output
Driver
10 +
11 –
OUTPUT 2
POWER
7
8
U
V
Base Socket
*Input shunt resistor attached for current input.
Specifications are subject to change without notice.
KWYV SPECIFICATIONS
ES-3517 Rev.5 Page 3/3