KSP-2Z-H [MSYSTEM]

Plug-in Signal Conditioners K-UNIT;
KSP-2Z-H
型号: KSP-2Z-H
厂家: M-SYSTEM    M-SYSTEM
描述:

Plug-in Signal Conditioners K-UNIT

文件: 总3页 (文件大小:98K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: KSP  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
Plug-in Signal Conditioners K-UNIT  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
4W: -10 – +10 V DC (Load resistance 2000 Ω min.)  
5W: -5 – +5 V DC (Load resistance 1000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
LOW FREQUENCY TRANSMITTER  
(50 Hz minimum, for Mitsubishi inverter)  
Functions & Features  
• Converting the pulse output from FM terminal of  
Mitsubishi inverter into standard process signal  
• Isolation up to 2000 V AC  
[2] POWER INPUT  
AC Power  
• High-density mounting  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
Typical Applications  
• Positive displacement flowmeters, turbine flowmeters and  
vortex flowmeters  
• Proximity switches  
50  
(1.97)  
DC Power  
S: 12 V DC  
R: 24 V DC  
80  
(3.15)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
123  
(4.84)  
Connection: M3.5 screw terminals  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Overrange output: 0 to 120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Input pulse sensing: DC coupled standard  
Input filter: CR filter incorporated  
mm (inch)  
MODEL: KSP-2[1]-[2]-ME  
ORDERING INFORMATION  
• Code number: KSP-2[1]-[2]-ME  
Specify a code from below for each of [1] and [2].  
(e.g. KSP-2A-B-ME)  
(C = 3.3 nF, R = 10 kΩ; parallel connection)  
Low-end cutout: 2 to 5 %  
• Frequency range (e.g. 0 – 1440 Hz)  
Applicable inverter:  
Mitsubishi electric FREQROL series: A024, A200,  
A500, A700, A800, D700, E500, E700, F400, F500, F700,  
F700PJ, F800, S500, U100, B, B3  
INPUT  
2: Voltage pulse  
Mitsubishi electric MELTRAC series: A100, A200,  
V200  
[1] OUTPUT  
Current  
Note) Do NOT connect other devices except the transmitter  
to the inverter's FM terminal. Do NOT bundle the FM and  
motor wirings.  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
INPUT SPECIFICATIONS  
Frequency range: 0 – 50 Hz through 0 - 1440 Hz  
Pulse width (time) requirement: ≥ 280 μsec. (Hi and Lo)  
Voltage Pulse  
Waveform: Square  
Input amplitude: V  
H
4 ±0.7 - 50 V, V 1 ± 0.7 V  
L
Input impedance: ≥ 7 kΩ (for 9 V DC pulse)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
KSP SPECIFICATIONS  
ES-3572-ME Rev.3 Page 1/3  
http://www.m-system.co.jp/  
MODEL: KSP  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ± 2 Hz, approx. 2.5 VA  
DC: Operational voltage range: rating ±10 %,  
ripple 10% p-p max.; approx. 2.5 W (100 mA at 24 V)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 350 g (0.77 lb)  
PERFORMANCE in percentage of span  
Accuracy: ± 0.3 % (output 10 – 100 %)  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
Response time: (0 – 90 %)  
Approx. 2 sec. for 0 – 50 Hz  
Approx. 1 sec. for 0 – 100 Hz  
Approx. 0.5 sec. for 0 – 500 Hz  
Approx. 0.5 sec. for 0 – 10 kHz  
Ripple: 0.2 %p-p max. with input ≥ 10 %  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
6
5
4
3
2–  
4.5 (.18) dia.  
MTG HOLE  
15 (.59) deep  
7
8
1
2
8–  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
123 (4.84)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
KSP SPECIFICATIONS  
ES-3572-ME Rev.3 Page 2/3  
http://www.m-system.co.jp/  
MODEL: KSP  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Isolation  
10kΩ 3.3nF  
Waveform  
Shaper  
Output  
Driver  
+
3
4
5
6
1
2
7
8
+
One-Shot  
Integration  
INPUT  
OUTPUT  
POWER  
U(+)  
V(–)  
Base Socket  
Note: Do NOT connect other devices except the transmitter to the inverter’s FM terminal.  
Do NOT bundle the FM and motor wirings.  
Specifications are subject to change without notice.  
KSP SPECIFICATIONS  
ES-3572-ME Rev.3 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

KSP-2Z-J

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KSP-2Z-R

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KSP-2Z-S

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KSP02J

DIP Switch
OTAX

KSP02L

DIP Switch
OTAX

KSP02S

DIP Switch
OTAX

KSP03J

DIP Switch
OTAX

KSP03L

DIP Switch
OTAX

KSP03S

DIP Switch
OTAX

KSP04J

DIP Switch
OTAX

KSP04L

DIP Switch
OTAX

KSP04S

DIP Switch
OTAX