KS2V2-61-R [MSYSTEM]

Plug-in Signal Conditioners K-UNIT;
KS2V2-61-R
型号: KS2V2-61-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Plug-in Signal Conditioners K-UNIT

文件: 总4页 (文件大小:142K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: KS2V2  
Plug-in Signal Conditioners K-UNIT  
[2] OPTIONS  
blank: none  
/Q: Options other than the above (specify the specification)  
DC INPUT LIMIT ALARM  
(digital adjustments; dual alarm trip; burnout)  
Functions & Features  
SPECIFICATIONS OF OPTION: Q  
EX-FACTORY SETTING  
• Providing relay contact closures at preset DC input levels  
• Dual (Hi/Lo) trip  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-3608)  
• Front digital displays  
• Programmable with front keys  
RELATED PRODUCTS  
• Resistor module (model: REM)  
500 Ω for 2 – 10 mA DC  
Typical Applications  
• Various alarm applications  
250 Ω for 4 – 20 mA DC  
50 (1.97)  
100 Ω for 10 – 50 mA DC  
70 (2.76)  
110 (4.33)  
mm (inch.)  
MODEL: KS2V2–61–[1][2]  
ORDERING INFORMATION  
• Code number: KS2V2-61-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. KS2V2-61-R/Q)  
• Specify the specification for option code /Q  
(e.g. /SET)  
INPUT  
Voltage  
6: 1 – 5 V DC  
(Use a resistor module for current input)  
OUTPUT  
1: Relay; SPDT or transfer contact  
[1] POWER INPUT  
AC Power  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
KS2V2 SPECIFICATIONS  
ES-3608 Rev.10 Page 1/4  
https://www.m-system.co.jp/  
MODEL: KS2V2  
Measured Value (PV) indicator: Green LED turns on when PV  
display is set.  
GENERAL SPECIFICATIONS  
Construction: Panel flush mounting, plug-in  
Connection: M3.5 screw terminals  
Alarm SET1 indicator: Red LED turns on when the Alarm  
SET1 is in tripped conditions.  
Screw terminal: Chromated steel  
Alarm SET2 Indicator: Red LED turns on when the Alarm  
SET2 is in tripped conditions.  
Housing material: Flame-resistant resin (gray)  
Isolation: Input to SET1 to SET2 to power  
Time constant for the input filter (P-dF): 0.0 to 900.0 sec. (0  
– 63 %)  
Engineering unit indication: Sticker label attached;  
DC, AC, W, °C, °F, V, mV, A, mA, %, kW, mW,  
kV, kA, kvar, Mvar, var, m, mm, kg, kg/h,  
Alarm relay switching delay time (P-d1, P-d2): 1 to 10 sec.;  
programmable independently for each setpoint  
Programming: Front key  
kPa, MPa, N·m, Nm  
3
/h, m  
3
/h, m /sec, m/sec,  
3
ℓ/min, %RH, ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa.  
Setpoint adjustment (ST1, ST2): -5 to +105 %;  
programmable independently for each setpoint  
Deadband (hysteresis) (HYS1, HYS2): 0 – 102 %;  
programmable independently for each setpoint  
Burnout: Upscale (standard), downscale (available to  
change)  
INPUT SPECIFICATIONS  
DC Voltage: -5 – +105 %  
Input resistance: ≥ 1 MΩ  
OUTPUT SPECIFICATIONS  
Relay Contact: SPDT relays  
Power ON delay (P-d0): 0 to 20 sec.  
Read rate: 0.5 sec.  
220 V AC @3 A (cos ø = 1)  
Alarm mode (P-A1, P-A2): Programmable independently for  
each setpoint; See Table below.  
30 V DC @3 A (resistive load)  
Caution: N.O. and N.C. contacts could be conductive at the  
same time. DO NOT connect both contacts at the same  
time.  
Param.  
Code  
Alarm Modes  
Latching  
Hold*  
Trip  
Operation  
Set Value  
Relay & LED  
Behavior in  
Tripped Conditions  
(P-A1)  
(P-A2)  
Maximum switching voltage: 220 V AC or 30 V DC  
Maximum switching power: 660 VA or 90 W  
Minimum load: 10 V DC @1 mA  
0
1
No alarm  
High  
----  
----  
----  
Absolute value  
Without  
LED ON  
Coil energized  
2
3
4
5
6
7
8
Low  
High  
Low  
High  
Low  
High  
Low  
Absolute value  
Absolute value  
Absolute value  
Absolute value  
Absolute value  
Absolute value  
Absolute value  
Without  
With  
LED ON  
Coil energized  
Mechanical life: 2 × 10 cycles with no loads  
7
For maximum relay life with inductive loads, external  
protection is recommended.  
LED ON  
Coil energized  
With  
LED ON  
Coil energized  
Without  
Without  
With  
LED ON  
Coil de-energized  
INSTALLATION  
Power consumption  
LED ON  
Coil de-energized  
AC:  
LED ON  
Coil de-energized  
Approx. 3.1 VA at 100 V  
Approx. 4.1 VA at 200 V  
With  
LED ON  
Coil de-energized  
Approx. 4.8 VA at 264 V  
*Without latching hold function, the unit is tripped upon starting operation when  
the unit is set to Low alarm.  
DC: Approx. 1.7 W  
With the function, the unit is NOT tripped until the temperature goes once above  
and then below the setpoint.  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Panel flush mounting with attached  
mounting bracket, surface or DIN rail  
Weight: 200 g (0.44 lb)  
DISPLAY  
Display: 4 digits of 10 mm (.39”) height, 7-segment LED  
Scaling range: -1999 to 9999 counts  
Measured Value (PV)/Alarm (SET1) display: Red LEDs  
Alarm (SET2) parameter display: Green LEDs  
PV display at abnormal input: Over range or under range  
displayed  
PERFORMANCE  
Display accuracy: ±0.5% FS ±1 digit  
Setpoint accuracy: Display accuracy ± 0.1 % FS  
Trip point repeatability: Included in the setpoint accuracy  
Line voltage effect: Included in the display accuracy  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @1 minute  
Front LEDs  
Power indicator: Green LED turns on while the power is  
turned on.  
KS2V2 SPECIFICATIONS  
ES-3608 Rev.10 Page 2/4  
https://www.m-system.co.jp/  
MODEL: KS2V2  
(input to SET1 or SET2 to power)  
500 V AC @1 minute (SET1 to SET2)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Installation Category II (power)  
Measurement Category II (output)  
Pollution Degree 2  
Input to output to power: Basic insulation (300 V)  
RoHS Directive  
EXTERNAL VIEW  
H. Alarm SET1 Indicator LED  
J. Alarm SET2 Indicator LED  
G. Power Indicator LED  
A. Measured Value (PV) /  
Alarm SET1 Display  
B. Measured Value (PV)  
Indicator LED  
C. Alarm SET2 / Parameter Display  
D. SELECT Key  
F. DOWN Key  
E. UP Key  
Component Name  
Ref.  
Function  
A
B
Measured Value (PV) / Alarm SET1 Display Displaying either of Measured Value (PV) or Alarm Setpoint Value (SET1)  
LED turns on when the Measured Value (PV) is displayed.  
Measured Value (PV) Indicator LED  
Alarm SET2 / Parameter Display  
SELECT Key  
Displaying either of Alarm Setpoint Value (SET2) or parameter type code.  
Used for confirming current setpoints and switching between parameter blocks.  
C
D
E
F
Pressing the key increases display values.  
UP Key  
They change continuously when it is kept pressed.  
Pressing the key decreases display values.  
DOWN Key  
They change continuously when it is kept pressed.  
LED turns on while the power is turned on.  
Power Indicator LED  
Alarm SET1 Indicator LED  
Alarm SET2 Indicator LED  
G
H
J
LED turns on when the Alarm SET1 is in tripped conditions.  
LED turns on when the Alarm SET2 is in tripped conditions.  
KS2V2 SPECIFICATIONS  
ES-3608 Rev.10 Page 3/4  
https://www.m-system.co.jp/  
MODEL: KS2V2  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
CLAMP  
110 (4.33)  
(top & bottom)  
7.5  
(.3)  
71.5 (2.81)  
1.5 (.06) PACKING  
7.8 (.31)  
48 (1.89)  
DIN RAIL  
35mm wide  
8
7
6
5
4
3
2–4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
10 11  
1
2
MOUNTING  
BRACKET  
1 1–M3.5  
SCREW  
PANEL  
t
[3.5] (.14)  
40 (1.57)  
50 (1.97)  
1 ≤ t ≤ 8  
(.04 ≤ t ≤.31)  
PANEL CUTOUT unit: mm  
■PANEL CUTOUT  
+0.5  
45 0  
63 MIN.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
5
6
4
11 N.C.  
10 N.O. SET1  
+
RY  
INPUT  
A/D  
Converter  
9
3
2
1
7
8
COM  
Digital  
Computation  
N.C.  
RY  
N.O. SET2  
COM  
Display/  
Setting  
U(+)  
POWER  
V(–)  
Base Socket  
Specifications are subject to change without notice.  
KS2V2 SPECIFICATIONS  
ES-3608 Rev.10 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

KS2V2-61-R/Q

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS2V3

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS2V3-61-M2

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS2V3-61-M2/Q

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS2V3-61-R

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS2V3-61-R/Q

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KS300

THE GLOBAL EXPERT IN SOLID STATE RELAY TECHNOLOGY
CRYDOM

KS3004JTE10N

General Purpose Inductor, 0.01uH, 5%, 1 Element, Air-Core, SMD
KOA

KS3004KTE10N

General Purpose Inductor, 0.01uH, 10%, 1 Element, Air-Core, SMD
KOA

KS3004LBK10NJ

General Purpose Inductor, 0.01uH, 5%, 1 Element, Air-Core, SMD, CHIP
KOA

KS3004LBK10NK

General Purpose Inductor, 0.01uH, 10%, 1 Element, Air-Core, SMD, CHIP
KOA

KS3004LTE10NJ

General Purpose Inductor, 0.01uH, 5%, 1 Element, Air-Core, SMD, CHIP
KOA