KGS5D-RB/Q [MSYSTEM]

Plug-in Signal Conditioners K-UNIT;
KGS5D-RB/Q
型号: KGS5D-RB/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Plug-in Signal Conditioners K-UNIT

文件: 总3页 (文件大小:99K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: KGS  
6: 10 mV/V  
7: 20 mV/V  
Plug-in Signal Conditioners K-UNIT  
0: Specify (strain gauge and excitation)  
STRAIN GAUGE TRANSMITTER  
(isolated)  
[2] OUTPUT  
Functions & Features  
Current  
• Providing a DC output signal proportional to a  
bridge type strain gauge utilized in load cells, pressure  
transducers  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Supplying required excitation voltage  
• Drives bridges 80 Ω or above  
• Excitation adjustable from 2 V to 10 V  
• Wide-range adjustment: 0 – 80 % for zero, 20 –100 % for  
span  
• Isolation up to 2000 V AC  
• Fast response type available  
• Highdensity mounting  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
4W: -10 – +10 V DC (Load resistance 2000 Ω min.)  
5W: -5 – +5 V DC (Load resistance 1000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
Typical Applications  
• Weighing system for tanks, hoppers, silos  
• Weighing system using cranes  
• Float level meter utilizing strain gauges  
50  
(1.97)  
80  
(3.15)  
[3] POWER INPUT  
AC Power  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
132  
(5.20)  
mm (inch)  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
MODEL: KGS–[1][2]–[3][4]  
DC Power  
ORDERING INFORMATION  
• Code number: KGS-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. KGS-2A-B/K/Q)  
R: 24 V DC  
[4] OPTIONS (multiple selections)  
Response Time (0 – 90 %)  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
blank: Standard (≤ 0.5 sec.)  
/K: Fast response approx. 25 msec.  
(Not available when DC power is selected.)  
Other Options  
[1] INPUT STRAIN GAUGE  
1: 1 mV/V  
blank: none  
/Q: Option other than the above (specify the specification)  
12: 1.25 mV/V  
15: 1.5 mV/V  
2: 2 mV/V  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
3: 3 mV/V  
4: 4 mV/V  
/C02: Polyurethane coating  
5: 5 mV/V  
KGS SPECIFICATIONS  
ES-3527 Rev.2 Page 1/3  
http://www.m-system.co.jp/  
MODEL: KGS  
/C03: Rubber coating  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 % (input ≥ 3 mV)  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute for AC power  
1000 V AC @1 minute for DC power  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
(input or output to power)  
1000 V AC @1 minute (input to output)  
2000 V AC @1 minute  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Excitation adjustment: 2 – 10 V (front)  
Zero adjustments (tare): 0 – 80 % (front)  
(Excitation voltage: factory default)  
Span adjustment: 100 – 20 % (front)  
(Excitation voltage: factory default)  
(input or output or power to ground)  
INPUT SPECIFICATIONS  
Input: Bridge voltage from load cells  
Strain Gauge  
Rated output from strain gauge: 1 – 20 mV/V;  
Input to the transmitter must be over 3 mV.  
Excitation: 2 – 10 V adjustable (5 V standard)  
Maximum current: 35 mA at 10 V, 65 mA at ≤ 7.5 V  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 3 VA  
DC: Operational voltage range: 24 V ±10 %,  
approx. 150 mA, ripple 10 %p-p max.  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 430 g (0.95 lb)  
KGS SPECIFICATIONS  
ES-3527 Rev.2 Page 2/3  
http://www.m-system.co.jp/  
MODEL: KGS  
EXTERNAL VIEW  
Excitation Adj.  
Zero Adj.  
Span Adj.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Isolation  
STRAIN  
GAUGE  
Low Drift  
Amplifier  
Output  
Driver  
+
+
+
10  
11  
3
1
2
7
8
OUTPUT  
POWER  
U(+)  
V(–)  
Low Drift  
DC Volt.  
Stabilizer  
EXC.  
9
6
Base Socket  
Specifications are subject to change without notice.  
KGS SPECIFICATIONS  
ES-3527 Rev.2 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

KGS5D-S

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KGS5D-S/K

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KGS5D-S/Q

Plug-in Signal Conditioners K-UNIT
MSYSTEM

KGS6N4252BT

Tactile Switches 6mm×6mm Top Push Surface Mounting Type
HOKURIKU

KGSWIVEL.073

PARTS/ACCESSORIES
PULSE

KGSWIVEL.100

PARTS/ACCESSORIES
PULSE

KGT12N120NDH

High speed switching
KEC

KGT15N120KDA

SEMICONDUCTOR TECHNICAL DATA
KEC

KGT15N120NDA

SEMICONDUCTOR TECHNICAL DATA
KEC

KGT15N120NDH

High speed switching
KEC

KGT15N120NDS

High speed switching
KEC

KGT15N135NDH

KEC NPT IGBTs offer low switching losses, high energy efficiency and high avalanche ruggedness for soft switching application such as IH(induction heating), microwave oven, etc.
KEC