JC-HL-7-12-R [MSYSTEM]
Remote I/O JC Series;型号: | JC-HL-7-12-R |
厂家: | M-SYSTEM |
描述: | Remote I/O JC Series |
文件: | 总11页 (文件大小:445K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: JC-HL
Remote I/O JC Series
HUB MODULE
[4] OPTIONS (multiple selections)
Communication Mode
blank: Full-duplex
/H: Half-duplex
Other Options
53
(2.09)
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
115
(4.52)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9041)
FUNCTIONS & FEATURES
73
The HUB Module for HLS (model: JC-HL) extends total length
of network cable and branch cable of HLS (Hi-speed Link
System). Total max. length is 2.4 km when transfer rate is 3
Mbps. In order to connect the JC-HL, the master unit
configuring HLS must support HUB module.
(2.87)
mm (inch)
MODEL: JC–HL-[1]-1[2]-[3][4]
HLS is the abbreviation for “Hi-speed Link System” of Step
Technica Co., Ltd.
ORDERING INFORMATION
• Code number: JC-HL-[1]-1[2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. JC-HL-7-12-R/H/Q)
RELATED PRODUCTS
• Specify the specification for option code /Q
(e.g. /SET)
• High-speed link system I/O modules (model: R7F4DH,
R7K4DH, R7HL, R7FN etc.)
• MP2200/MP2300 series use HLS master module (model:
MPHLS)
[1] I/O TYPE
3: 3 port (trunk 1 port, feeder 2 port)
7: 7 port (trunk 1 port, feeder 6 port)
GENERAL SPECIFICATIONS
Number of port:
JC-HL-3: Trunk 1 port, feeder 2 port
JC-HL-7: Trunk 1 port, feeder 6 port
Max. number of inserted HUBs: 7
(Depending on specification of master unit)
Connectable devices: The products conforming to HLS
Connection
TERMINAL BLOCK
1: Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
[2] COMMUNICATION CONNECTOR PIN ASSIGNMENT
1: 3, 4 - 5, 6 pair wiring
Network: RJ-45 Modular Jack
(M-System HLS related products standard pin assignment)
2: 4, 5 - 3, 6 pair wiring
Power input: Separable tension clamp terminal
Power on LED: PWR (green) turns on while the power is
supplied.
(Ethernet LAN cable pin assignment)
[3] POWER INPUT
DC Power
HLS COMMUNICATION
Communication mode: Full-duplex or half-duplex
Network cable
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R5: 16 - 32 V DC
• Shield cable
ZHY262PS (Shinko Seisen Industry Co., Ltd.)
ZHT262PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable
(Operational voltage range 15 - 33 V DC, ripple 10 %p-p max.)
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 1/11
https://www.m-system.co.jp/
MODEL: JC-HL
Transmission distance / Transfer rate:
Refer to the table below (Selectable with
DIP switch. Factory default: 12 Mbps)
Terminating resistor:
MOUNTING REQUIREMENTS unit: mm (inch)
Trunk built-in (Selectable with DIP switch. Factory default:
disable)
Feeder built-in
Status indicator LEDs: ERR, LNK
(Refer to the instruction manual for details)
Number of inserted HUBs
Transfer rate
12Mbps
6Mbps
0
1
2
3
4
5
6
7
100m 200m 300m 400m 500m 600m 700m 800m
200m 400m 800m 1km 1.2km 1.4km 1.6km 1.8km
300m 600m 900m 1.2km 1.5km 1.8km 2.1km 2.4km
3Mbps
INSTALLATION
Rated current for power supply connector: 8A
Power consumtpion:
JC-HL-3: Approx. 1 W
JC-HL-7: Approx. 1.4 W
Operating temperature: -10 to +55°C
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight
JC-HL-3: 150 g (0.33 lb)
JC-HL-7: 160 g (0.35 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
JC-HL-3 (HLS0A or HLS0B to HLS1 or HLS2 or FE to power)
JC-HL-7 (HLS0A or HLS0B to HLS1 or HLS2 or HLS3 or HLS4
or HLS5 or HLS6 or FE to power)
Dielectric strength: 1500 V AC @ 1 minute
JC-HL-3 (HLS0A or HLS0B to HLS1 or HLS2 or FE to power)
JC-HL-7 (HLS0A or HLS0B to HLS1 or HLS2 or HLS3 or HLS4
or HLS5 or HLS6 or FE to power)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 2/11
https://www.m-system.co.jp/
MODEL: JC-HL
EXTERNAL VIEW
■ I/O TYPE : 3 3port
• SIDE VIEW
• FRONT VIEW
Status Indicator LED
PWR
ERR
LNK0
PWR LED
ERR LED
RJ-45 Modular Jack
for Trunk
HLS0A
SW1
ON
➞
HLS0B
RJ-45 Modular Jack
for Feeder
HLS1
LNK1
Operating Mode Setting
)
Status Indicator LED
(
DIP SW SW1
HLS2
LNK2
SW1
1
2
3
4
Transfer Rate
Terminating
Resistor
Power Supply
Connector
ON ➞
PWR+
PWR
-
FE
■ I/O TYPE : 7 7port
• SIDE VIEW
• FRONT VIEW
Status Indicator LED
PWR
ERR
LNK0
PWR LED
ERR LED
RJ-45 Modular Jack
for Trunk
HLS0A
SW1
Status Indicator LED
Status Indicator LED
ON
➞
HLS0B
HLS1
LNK1
Operating Mode Setting
)
LNK5
HLS5
RJ-45 Modular Jack
for Feeder
(
DIP SW SW1
RJ-45 Modular Jack
for Feeder
HLS2
LNK2
SW1
LNK6
HLS6
1
2
3
4
Transfer Rate
HLS3
LNK3
Power Supply
Connector
Terminating
Resistor
Status Indicator LED
ON ➞
PWR+
HLS4
LNK4
PWR-
FE
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 3/11
https://www.m-system.co.jp/
MODEL: JC-HL
CONNECTION DIAGRAMS
■ POWER SUPPLY
Cable connector: TFMC1,5 / 5–STF–3,5
(Phoenix Contact) (included in the package)
Applicable wire size: 0.2 − 1.5 mm2; stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2 (Phoenix Contact)
• AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
• AI0,5−10WH 0.5 mm2 (Phoenix Contact)
• AI0,75−10GY 0.75 mm2 (Phoenix Contact)
• A1−10 1.0 mm2 (Phoenix Contact)
• A1,5−10 1.5 mm2 (Phoenix Contact)
1. PWR + Power Supply
2. PWR − Power Supply
1ꢀ
2
3ꢀ
3. FE
Functional earth
■ NETWORK
Reccommended cable connector: TM21P–88P (Hirose Electric)
(not included in the package)
• COMMUNICATION CONNECTOR PIN ASSIGNMENT CODE: 1
Full-duplex communication
1
2
3
4
5
6
7
8
Trunk (HLS0A, HLS0B)
Feeder (HLS1, HLS2, HLS3, HLS4, HLS5, HLS6)
1. NC
2. NC
Unused
Unused
1. NC
2. NC
Unused
Unused
3. TXD+
4. TXD–
5. RXD+
6. RXD–
7. NC
Network (HUB, transmission +)
Network (HUB, transmission –)
Network (master, transmission +)
Network (master, transmission –)
Unused
3. RXD+
4. RXD–
5. TXD+
6. TXD–
7. NC
Network (slave, transmission +)
Network (slave, transmission –)
Network (HUB, transmission +)
Network (HUB, transmission –)
Unused
8. SLD
Shield
8. SLD
Shield
Half-duplex communication
1
2
3
4
5
6
7
8
Trunk (HLS0A, HLS0B)
Feeder (HLS1, HLS2, HLS3, HLS4, HLS5, HLS6)
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD
Unused
Unused
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD
Unused
Unused
Network (+)
Network (–)
Unused
Network (+)
Network (–)
Unused
Unused
Unused
Shield
Unused
Unused
Shield
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 4/11
https://www.m-system.co.jp/
MODEL: JC-HL
• COMMUNICATION CONNECTOR PIN ASSIGNMENT CODE: 2
Full-duplex communication
1
2
3
4
5
6
7
8
Trunk (HLS0A, HLS0B)
Feeder (HLS1, HLS2, HLS3, HLS4, HLS5, HLS6)
1. NC
2. NC
Unused
Unused
1. NC
2. NC
Unused
Unused
3. TXD+
4. RXD–
5. RXD+
6. TXD–
7. NC
Network (HUB, transmission +)
Network (master, transmission –)
Network (master, transmission +)
Network (HUB, transmission –)
Unused
3. RXD+
4. TXD–
5. TXD+
6. RXD–
7. NC
Network (slave, transmission +)
Network (HUB, transmission –)
Network (HUB, transmission +)
Network (slave, transmission –)
Unused
8. SLD
Shield
8. SLD
Shield
Half-duplex communication
1
2
3
4
5
6
7
8
Trunk (HLS0A, HLS0B)
Feeder (HLS1, HLS2, HLS3, HLS4, HLS5, HLS6)
1. NC
2. NC
3. NC
4. TR–
5. TR+
6. NC
7. NC
8. SLD
Unused
Unused
Unused
1. NC
2. NC
3. NC
4. TR–
5. TR+
6. NC
7. NC
8. SLD
Unused
Unused
Unused
Network (–)
Network (+)
Unused
Network (–)
Network (+)
Unused
Unused
Shield
Unused
Shield
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 5/11
https://www.m-system.co.jp/
MODEL: JC-HL
■ MASTER, SLAVE CONNECTION
• Full-duplex communication
Master Module
TXD+
HUB Module
Slave Module
RXD+
RXD−
RXD+
RXD−
TXD+
TXD−
SLD
TXD−
Terminating
Resistor
Terminating
Resistor
RXD+
TXD+
RXD−
TXD−
SHIELD
SLD
Trunk HLS0A/HLS0B
Slave Module
TXD+
TXD−
RXD+
RXD−
TXD+
TXD−
SLD
Terminating
Resistor
Terminating
Resistor
RXD+
RXD−
SLD
Feeder HLS1 – HLS6
• Half-duplex communication
Slave Module
Master Module
HUB Module
TR+
TR+
TR−
TR+
TR−
SLD
Terminating
Terminating
Resistor
Resistor
TR−
SHIELD
SLD
Trunk HLS0A/HLS0B
Slave Module
TR+
TR−
TR+
TR−
SLD
Terminating
Resistor
Terminating
Resistor
SLD
Feeder HLS1 – HLS6
Note: Be sure to turn ON the switch of the terminating resistor located at both ends of the modules.
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 6/11
https://www.m-system.co.jp/
MODEL: JC-HL
DIMENSIONS unit: mm (inch)
50(1.97)
[3(.12)]
73(2.87)
55(2.17)
[4(.16)]
2–4.3 (.17) dia Mtg Hole
4 (.16) deep
DIN RAIL
(35 mm wide)
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 7/11
https://www.m-system.co.jp/
MODEL: JC-HL
SCHEMATIC CIRCUITRY
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
■ JC−HL−3−11
Isolation
Isolation
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
NC
NC
Comm.
Circuit
Comm.
Circuit
NC
TXD+ (TR+)
TXD− (TR−)
RXD+ (NC)
RXD− (NC)
NC
RXD+ (TR+)
RXD− (TR−)
TXD+ (NC)
TXD− (NC)
NC
HLS0A
COMMUNI-
CATION
HLS1
Control
Circuit
SLD
SLD
Isolation
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
NC
NC
Comm.
Circuit
NC
TXD+ (TR+)
TXD− (TR−)
RXD+ (NC)
RXD− (NC)
NC
RXD+ (TR+)
RXD− (TR−)
TXD+ (NC)
TXD− (NC)
NC
HLS0B
COMMUNI-
CATION
HLS2
SLD
SLD
+
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
■ JC−HL−7−11
Isolation
Isolation
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
NC
NC
NC
Comm.
Circuit
Comm.
Circuit
TXD+ (TR+)
TXD− (TR−)
RXD+ (NC)
RXD− (NC)
NC
RXD+ (TR+)
RXD− (TR−)
TXD+ (NC)
TXD− (NC)
NC
HLS0A
COMMUNI-
CATION
HLS1
Control
Circuit
SLD
SLD
1
2
3
4
5
6
7
8
NC
NC
Isolation
1
2
3
4
5
6
7
8
NC
Comm.
Circuit
TXD+ (TR+)
TXD− (TR−)
RXD+ (NC)
RXD− (NC)
NC
NC
HLS0B
COMMUNI-
CATION
RXD+ (TR+)
RXD− (TR−)
TXD+ (NC)
TXD− (NC)
NC
HLS6
SLD
SLD
+
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 8/11
https://www.m-system.co.jp/
MODEL: JC-HL
■ JC−HL−3−12
Isolation
Isolation
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
Comm.
Circuit
Comm.
Circuit
NC
TXD+ (NC)
RXD− (TR−)
RXD+ (TR+)
TXD− (NC)
NC
RXD+ (NC)
TXD− (TR−)
TXD+ (TR+)
RXD− (NC)
NC
HLS0A
COMMUNI−
CATION
HLS1
Control
Circuit
SLD
SLD
Isolation
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
Comm.
Circuit
NC
TXD+ (NC)
RXD− (TR−)
RXD+ (TR+)
TXD− (NC)
NC
RXD+ (NC)
TXD− (TR−)
TXD+ (TR+)
RXD− (NC)
NC
HLS0B
COMMUNI−
CATION
HLS2
SLD
SLD
+
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
■ JC−HL−7−12
Isolation
Isolation
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
NC
NC
Comm.
Circuit
Comm.
Circuit
TXD+(NC)
RXD+(NC)
TXD−(TR−)
TXD+(TR+)
RXD−(NC)
NC
HLS0A
COMMUNI-
CATION
RXD−(TR−)
RXD+(TR+)
TXD−(NC)
NC
HLS1
Control
Circuit
SLD
SLD
NC
NC
1
2
3
4
5
6
7
8
Isolation
1
2
3
4
5
6
7
8
NC
Comm.
Circuit
TXD+(NC)
RXD−(TR−)
RXD+(TR+)
TXD−(NC)
NC
NC
HLS0B
COMMUNI-
CATION
RXD+(NC)
TXD−(TR−)
TXD+(TR+)
RXD−(NC)
NC
HLS6
SLD
SLD
+
PWR+
1
2
3
Power
Circuit
POWER (IN)
PWR
−
−
FE
PWR+
1
2
3
POWER (OUT)
PWR−
FE
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 9/11
https://www.m-system.co.jp/
MODEL: JC-HL
SYSTEM CONFIGURATION EXAMPLES
High-speed link System I/O Modules
(Model: R7F4DH etc.)
HUB Module
(Model: JC−HL)
Slave
High-speed link System I/O Modules
(Model: R7F4DH etc.)
Slave
HUB Module
(Model: JC−HL)
Rt
Rt
Rt
Master Module
Rt
Rt
Rt
Rt
Number of insert: 1
High-speed link System I/O Modules
(Model: R7F4DH etc.)
HUB Module
(Model: JC−HL)
Slave
Rt
Rt
Rt
Number of insert: 2
High-speed link System I/O Modules
(Model: R7F4DH etc.)
HUB Module
(Model: JC−HL)
Slave
Rt
Rt
Rt
Rt
Number of insert: 3
Rt : Terminating Resistor
Note 1) Max. transmission distance between master module and HUB module, HUB module and HUB module, HUB module and slave module is as
follows. 100 m at 12 Mbps, 200 m at 6 Mbps and 300 m at 3 Mbps.
Note 2) Be sure to connect HLS0A/HLS0B to the host side.
Note 3) The terminating resistor must be enabled for the modules at both end of the communication line. The terminating resistor is incorporated
in the feeder side port of the HUB module.
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 10/11
https://www.m-system.co.jp/
MODEL: JC-HL
Specifications are subject to change without notice.
JC-HL SPECIFICATIONS
ES-9041 Rev.3 Page 11/11
https://www.m-system.co.jp/
相关型号: