HDY2-241-R [MSYSTEM]

Space-saving Plug-in Signal Conditioners H-UNIT;
HDY2-241-R
型号: HDY2-241-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Plug-in Signal Conditioners H-UNIT

文件: 总2页 (文件大小:99K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: HDY2  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
Space-saving Plug-in Signal Conditioners H-UNIT  
POWER INPUT  
DC Power  
CURRENT LOOP SUPPLY  
(isolated)  
R: 24 V DC  
Functions & Features  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
• Powering a 4 – 20 mA DC current loop  
• Shortcircuit protection  
• Applicable to smart transmitters  
• High-density mounting  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
Typical Applications  
• Various 2-wire transmitters  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
26 (1.02)  
/C02: Polyurethane coating  
93  
(3.66)  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
137  
(5.39)  
mm (inch)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
MODEL: HDY2–24[1]–R[2]  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
ORDERING INFORMATION  
• Code number: HDY2-24[1]-R[2]  
Specify a code from below for each of [1] and [2].  
(e.g. HDY2-246-R/Q)  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
SUPPLY OUTPUT  
(across the terminals 1 – 2)  
Output voltage:  
SUPPLY OUTPUT  
24: 24 V DC  
24 – 28 V DC with no load  
18 V DC min. at 20 mA  
INPUT  
Current  
Current rating: ≤ 22 mA DC  
Shortcircuit Protection  
Current limited: 30 mA max.  
Protected time duration: No limit  
4 – 20 mA DC (Input resistance 300 Ω)  
[1] OUTPUT  
Current  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
Voltage  
INSTALLATION  
Current consumption: Approx. 90 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail; Standard Rack Mounting  
Frame BX-16H available  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
HDY2 SPECIFICATIONS  
ES-3427 Rev.3 Page 1/2  
http://www.m-system.co.jp/  
MODEL: HDY2  
Weight: 200 g (0.44 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
Line voltage effect  
Supply output: ±3 % over voltage range  
Output signal: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 500 V AC @ 1 minute  
(input to output to power)  
1500 V AC @ 1 minute (input or output or power to ground)  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
7.8 (.31)  
CLAMP  
(top & bottom)  
1
2
15  
(.59)  
DIN RAIL  
35mm wide  
3
4
2–4.5 (.18)  
HOLE  
15 (.59) deep  
5
6
8–M3.5  
SCREW  
7
8
107 (4.21)  
137 (5.39)  
26 (1.02)  
26 (1.02)  
[3.3 (.13)]  
•When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
2-WIRE  
TRANSMITTER  
Isolation  
Output  
Driver  
+
+
2
1
4
3
5
6
7
8
+
+
50Ω  
OUTPUT  
POWER  
+
MONITOR  
(1 – 5V DC)  
V
Current  
Limiter  
250Ω  
Base Socket  
Specifications are subject to change without notice.  
HDY2 SPECIFICATIONS  
ES-3427 Rev.3 Page 2/2  
http://www.m-system.co.jp/  

相关型号:

HDY2-241-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-242-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-242-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-243-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-243-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-244-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-244-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-245-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-245-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-246-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-246-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HDY2-24A-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM