HCE-5G-R [MSYSTEM]

Space-saving Plug-in Signal Conditioners H-UNIT;
HCE-5G-R
型号: HCE-5G-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Plug-in Signal Conditioners H-UNIT

文件: 总3页 (文件大小:108K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: HCE  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
Space-saving Plug-in Signal Conditioners H-UNIT  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
CT TRANSMITTER  
(RMS sensing)  
Functions & Features  
• Converting an alternating current from a current  
transformer into a standard process signal  
• Minimum ripple  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
• RMS sensing  
• CT Protector provided for open-circuit protection  
• Highdensity mounting  
Typical Applications  
• Centralized monitoring and control of motors, pumps or  
heaters by DCS  
POWER INPUT  
DC Power  
• Monitoring power line and power supply current  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
26 (1.02)  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
93 (3.66)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
137 (5.39)  
(mm)  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
MODEL: HCE–[1][2]–R[3]  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
ORDERING INFORMATION  
• Code number: HCE-[1][2]-R[3]  
Specify a code from below for each of [1] through [3].  
(e.g. HCE-1A-R/Q)  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Input waveform: Up to 15 % of 3rd harmonic content  
Overrange output: 0 to 120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
[1] INPUT  
Current  
1: 0 – 1 A AC  
5: 0 – 5 A AC  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
[2] OUTPUT  
Input burden: 0.5 VA max.  
Current  
Overload capacity: 500 % of rating for 5 sec., 120 %  
continuous  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
Operational range: 0 – 120 % of rating  
HCE SPECIFICATIONS  
ES-3444 Rev.2 Page 1/3  
http://www.m-system.co.jp/  
MODEL: HCE  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: 0 – 12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V  
INSTALLATION  
Current consumption: Approx. 55 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail; Standard Rack Mounting  
Frame BX-16H available  
Weight: 200 g (0.44 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.3 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
Ripple: 0.5 %p-p max. (100/120 Hz)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(input to output or power)  
500 V AC @ 1 minute (output to power)  
1500 V AC @ 1 minute  
(input or output or power to ground)  
EXTERNAL DIMENSIONS unit: mm (inch)  
7.8 (.31)  
CLAMP  
(top & bottom)  
1
2
15  
(.59)  
DIN RAIL  
35mm wide  
3
4
2–4.5 (.18)  
HOLE  
15 (.59) deep  
5
6
8–M3.5  
SCREW  
7
8
107 (4.21)  
137 (5.39)  
26 (1.02)  
26 (1.02)  
[3.3 (.13)]  
•When mounting, no extra space is needed between units.  
HCE SPECIFICATIONS  
ES-3444 Rev.2 Page 2/3  
http://www.m-system.co.jp/  
MODEL: HCE  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CT PROTECTOR  
(model: CTM)  
1
2
3
4
5
6
7
8
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
SOURCE  
Z
S
INPUT  
TRANSFORMER  
K
k
RMS  
Operation  
Output  
Driver  
1
2
3
4
5
6
7
8
+
+
OUTPUT  
CT  
l
L
LOAD  
POWER  
CT PROTECTOR  
model: CTM  
Base Socket  
Specifications are subject to change without notice.  
HCE SPECIFICATIONS  
ES-3444 Rev.2 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

HCE-5G-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HCE-5Z-R

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HCE-5Z-R/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HCE0611ABE8P3

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABE8P5

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABE9P3

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABE9P5

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABH8P3

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABH8P5

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABH9P3

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABH9P5

Miniature amplified pressure sensors
SENSORTECHNIC

HCE0611ABQ8P3

Miniature amplified pressure sensors
SENSORTECHNIC