FJF-A6-P/2 [MSYSTEM]
Space-saving Plug-in Signal Conditioners F-UNIT;型号: | FJF-A6-P/2 |
厂家: | M-SYSTEM |
描述: | Space-saving Plug-in Signal Conditioners F-UNIT |
文件: | 总3页 (文件大小:107K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: FJF
Space-saving Plug-in Signal Conditioners F-UNIT
[2] OUTPUT
Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
2-input MATH FUNCTION MODULE
(field-programmable)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
Functions & Features
• Providing temperature or pressure compensation for a gas
flow, and other arithmetic operations
• Microprocessor based
[3] POWER INPUT
AC Power
• Equation and parameters
K: 85 – 132 V AC
selectable on site via hand-held programmer PU-2x
• Loop testing
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
• High-density mounting
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
Typical Applications
R: 24 V DC
• Various flowmeters
• Adding two flows
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
• Ratio calculation
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Calculating average temperature
[4] OPTIONS (multiple selections)
Equation (Refer to the EQUATION table)
/1: Temperature compensation for DP flowmeter (ideal gas)
/2: Pressure compensation for DP flowmeter (ideal gas)
/3: Addition/subtraction
26 (1.02)
100
(3.94)
/4: Multiplication
/5: Division
Other Options
137
(5.39)
blank: none
mm (inch)
/Q: Option other than the above (specify the specification)
MODEL: FJF–[1][2]-[3][4]
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ORDERING INFORMATION
• Code number: FJF-[1][2]-[3][4]
/C02: Polyurethane coating
/C03: Rubber coating
Specify a code from below for each of [1] through [4].
(e.g. FJF-6A-K/3/Q)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Parameters
Use Ordering Information Sheet (No. ESU 1980). Default
setting will be used if not otherwise specified.
(K0
= 1, K
1
= 1, K
2
= 1, A
0
= 0 %, A
1
= 0 %, A = 0 %)
2
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 100 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
FJF SPECIFICATIONS
ES-1480 Rev.12 Page 1/3
http://www.m-system.co.jp/
MODEL: FJF
EQUATION
INPUT SPECIFICATIONS
Equation parameters
■ DC Current: Input resistor incorporated
X0: output (%)
X
1
to X
to K
to A
2
: input (%)
INSTALLATION
Power consumption
K0
2: gain ±29.999
A0
2: bias (%) ±299.99 %
•AC: Approx. 4.5 VA
EQUATION
•DC: 24 V approx. 70 mA
/1: Temperature compensation for DP flowmeter (ideal gas)
110 V approx. 20 mA
K1X1
X0 =
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
K2X2+A2
where X0 : compensated flow (linear characteristic)
X1 : uncompensated flow (square root extraction available)
X2 : temperature
Weight: 220 g (0.49 lb)
/2: Pressure compensation for DP flowmeter (ideal gas)
X0 = K1X1 K2X2+A2
where X0 : compensated flow (linear characteristic)
X1 : uncompensated flow (square root extraction available)
X2 : pressure
PERFORMANCE in percentage of span
Accuracy: Input accuracy + output accuracy
Input accuracy: ±0.2 % (gain ≤ 1)
/3: Addition/subtraction
X0 = K0 {K1 (X1+A1) + K2 (X2+A2)} + A0
/4: Multiplication
[±0.2 % × gain] with gain > 1
Output accuracy: ±0.2 %
X0 = K0 (K1X1+A1) (K2X2+A2) + A0
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 1.2 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength
/5:Division
0
K (K1X1+A1)
(K2X2+A2)
X0
=
+ A0
Power input code R:
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
500 V AC @ 1 minute (I/O to power)
Power input code K, L, P:
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
1500 V AC @ 1 minute (I/O to power)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power (non-isolated between
inputs)
Overrange input: Approx. -25 to +125 %
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Adjustments: Programming Unit (model: PU-2x); equation
and parameters, square root extraction, zero and span, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
FJF SPECIFICATIONS
ES-1480 Rev.12 Page 2/3
http://www.m-system.co.jp/
MODEL: FJF
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
26 (1.02)
107 (4.21)
137 (5.39)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Isolation
Digital
Computation
Output
Driver
+
–
+
–
1
2
3
4
5
6
7
8
+
Multiplexer
*
*
INPUT 1
INPUT 2
OUTPUT
POWER
–
U(+)
V(–)
MODULAR JACK
PU-2x
SERIAL TRANSMISSION LINE
Base Socket
*Input shunt resistor incorporated for current inputs.
Specifications are subject to change without notice.
FJF SPECIFICATIONS
ES-1480 Rev.12 Page 3/3