DA3-Z11-P [MSYSTEM]
Plug-in Signal Conditioners M-UNIT;型号: | DA3-Z11-P |
厂家: | M-SYSTEM |
描述: | Plug-in Signal Conditioners M-UNIT |
文件: | 总7页 (文件大小:179K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: DA3
Plug-in Signal Conditioners M-UNIT
[3] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
D/A CONVERTER
(16-bit resolution)
47 – 66 Hz)
DC Power
Functions & Features
R3: 12 – 24 V DC
• Converts parallel digital signal into a DC output
• BCD, binary, offset binary, two's complement, reflected
binary inputs
(Operational voltage range 10.8 - 26.4 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Positive or negative logic selectable
• Display can be scaled in convenient engineering unit
• Scalable DC output range
[4] OPTIONS (multiple selections)
• Parity check
Input
Blank: TTL level
Typical Applications
/A: 24 V DC
• Interface of analog signal for computers and PLC
Other Options
blank: none
/Q: Option other than the above (specify the specification)
50
(1.97)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
80
(3.15)
/C02: Polyurethane coating
/C03: Rubber coating
139
(5.47)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
mm (inch)
MODEL: DA3–[1][2]–[3][4]
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable (model: MCN26)
ORDERING INFORMATION
• Code number: DA3-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. DA3-V11-M2/A/Q)
GENERAL SPECIFICATIONS
Construction: Plug-in
• Specify the specification for option code /Q
(e.g. /C01/S01)
Connection
Input: 26-pin connector(OMRON XG4A-2634)
Paired connector: OMRON XG4M-2630-T, XG5M-263x-N
Cover: OMRON XG5S-2612
Use Ordering Information Sheet (No. ESU-1395) for
specifying programmable variables. Default setting will be
used if not specified.
Output, power: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
[1] OUTPUT
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
■DISPLAY
Current
Z1: Range 0 – 20 mA DC (Load resistance 600Ω max.)
Voltage
V1: Range -1 – +1 V DC (Load resistance 1000Ω min.)
V2: Range -10 – +10 V DC (Load resistance 10kΩ min.)
LED: 7 mm (.28") 7 segment, red
Number of display digits: 4 digits for DATA display; 2 digits
for ITEM display
[2] RESPONSE TIME
1: 400 msec.
PV indication: Input signal in engineering unit
Overrange indication: LEDs blinking
Power saving mode: Displays turn off if the keys are
untouched for a preset time period
2: 10 msec.
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 1/7
https://www.m-system.co.jp/
MODEL: DA3
PL1 (POL) LED: Red LED turns on at negative polarity.
PL2 (LOAD) LED: Red LED turns on at LOAD.
Setting: Via the front key pad
• Display range scaling
Operational range: -11.5 – +11.5 V DC
Minimum increment: 100 mV
INSTALLATION
Power consumption
• Available number of bits
• Data input logic
•AC: Approx. 10 VA
• POL input
•DC: Approx. 4 W (160 mA at 24 V)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)
• LOAD input
• Parity check
For detailed information, refer to the instruction manual.
INPUT SPECIFICATIONS
■ Input Code: Code, logic and scaling are user-selectable.
BCD with polarity (Settable range: -9999 - 9999)
Binary with polarity (Settable range: -7FFF - 7FFF)
Offset binary (Settable range: 0000 - FFFF)
Two’s complement (Settable range: 8000 - 7FFF)
Reflected binary (Settable range: 0000 - FFFF)
Output code, logic, scaling are settable.
■ Available number of bits
PERFORMANCE in percentage of max. span
Accuracy: ±0.1 %
Min. span required to ensure the accuracy: 20 % of the
nominal output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Resolution: 16 bits
Response time: ≤ 400 msec. or ≤ 10 msec. (0 – 90 %)
as specified by model suffix code, with ITEM 16 set to 0.0.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Selectable from 8, 10, 12, 14, 16 bits
■ Input Specifications
• TTL Level: TTL level (5 V-CMOS level) or open
collector (sink type), dry contact(detecting voltage: approx.
5 V, saturation voltage: ≤ 1 V, sink current: 1 mA)
Saturation voltage: ≤ 1 V
STANDARDS & APPROVALS
EU conformity:
Sink current: 1 mA
Common: Negative
EMC Directive
• 24 V DC: Open collector (source type)
Rated voltage: 24 V DC ±10%, ripple 5 %p-p max.
ON voltage/current: ≥ 18 V / 2.5 mA DC
OFF voltage/current: ≤ 3 V / 0.4 mA DC
Input current: ≤ 3.5 mA @24 V DC
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input resistance: Approx. 7.5 kΩ
Common: Negative
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
■ POL input (Polarity): Same logic and level as for the
input code; logic user-selectable
■ LOAD input: Same logic and level as for the
input code; logic user-selectable
■ Odd or even parity: Same logic and level as for the
input code; logic user-selectable
OUTPUT SPECIFICATIONS
■ DC Current: 0 – 20 mA DC
Operational range: 0 – 24.0 mA DC
Minimum increment: 0.1 mA
■ DC Voltage
Code V1: -1.00 – +1.00 V DC
Operational range: -1.15 – +1.15 V DC
Minimum increment: 10 mV
Code V2: -10.0 – +10.0 V DC
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 2/7
https://www.m-system.co.jp/
MODEL: DA3
EXTERNAL VIEW
DATA Display
DATA
ITEM Display
26-pin Connector
(Pin Assignments)
ITEM
PL1 (POL) LED
PL2 (LOAD) LED
1
2
ITEM
DATA
ITEM
UP-DOWN Keys
DATA
UP-DOWN Keys
25
26
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 3/7
https://www.m-system.co.jp/
MODEL: DA3
PARAMETER LIST
It is available to configure or confirm settings shown below by using front key pad.
MDF.
ITEM
P
DATA
CONTENTS
DEFAULT
CODE
N/A
-9999 – 9999 Input display in engineering unit, BCD (as set in ITEM 08/09)
(-FFFF – FFFF) ( ) for binary, offset binary, two's complement, re!ected binary
–
1
01
1, 2 , 3
Modi"cation code
1 : Data indication only.
2 : All parameters are modi"able.
3 : ITEM 22 only.
02
N/A
2
0 – 99
Status indication (“0” is normally indicated.)
–
–
0: Normal 1: Memory error 10: Out of input range -15 – 115%
Input indicated in % (of the range set in ITEM 17/18)
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
03/L
-15.0 – 115.0
04
05
06
2
2
2
-99.99 – 99.99 Zero adjustment (%) ("ne adj. of the value set in ITEM 17)
-99.99 – 99.99 Span adjustment (%) ("ne adj. of the value set in ITEM 18)
0.00
0.00
0
0, 1, 2, 3, 4
Display code
0 : BCD with polarity (decimal)
1 : Binary with polarity 2 : Offset binary
3 : Two’s complement
4 : Re!ected binary
07
2
0, 1, 2, 3, 4
Available number of bits
0
0: 16 bits 1: 14 bits 2: 12 bits 3: 10 bits 4: 8 bits
08
09
08
09
08
09
08
09
08
09
10
2
2
2
2
2
2
2
2
2
2
2
-9999 – 9999 BCD
-9999 – 9999
-7FFF – 7FFF Binary
-7FFF – 7FFF
Display range scaling 0% *1
Display range scaling 100% *1
Display range scaling 0% *1
Display range scaling 100% *1
Display range scaling 0% *1
Display range scaling 100% *1
Display range scaling 0% *1
Display range scaling 100% *1
Display range scaling 0% *1
Display range scaling 100% *1
0 : Positive
-9999
9999
-7FFF
7FFF
0000
FFFF
8000
7FFF
0000
FFFF
1
0000 – FFFF
0000 – FFFF
8000 – 7FFF
8000 – 7FFF
0000 – FFFF
0000 – FFFF
0, 1
Offset binary
Two’s complement
Re!ected binary
Data input logic*2
1 : Negative
ITEM 11 and 13 are independent from ITEM 10.
LOAD input
11
2
0, 1, 2
0: LOAD at Low or shortcircuit*3
0
1 : LOAD at High or opencircuit*4
2 : Unavailable (unused)
0 : Unavailable (unused)
12
13
14
15
16
2
2
2
2
2
0, 1
0, 1
POL input
POL input
Parity check
1
1 : Available (used)
0: Negative at High or opencircuit*4
1 : Negative at Low or shortcircuit*3
1
0, 1, 2
0, 1
0
0: Disable 1: Enable Parity per each digit 2: Enable Parity for all digits
0 : Odd
Odd or even parity
0
1 : Even
Delay buffer (seconds, 0 – 90%)
0.0 – 60.0
0.0
When the Response Time model suffix code is speci"ed to 1, the set value is
only effective at 0.5 or higher value.
17
18
17
18
17
18
19
20
2
2
2
2
2
2
2
2
-1.00 – 1.00
-1.00 – 1.00
-10.0 – 10.0
-10.0 – 10.0
0.0 – 20.0
0.0 – 20.0
0 – 99
Output code V1
Output code V2
Output code Z1
0% output voltage (V) *5
100% output voltage (V) *5
0% output voltage (V) *5
100% output voltage (V) *5
0% output voltage (V) *5
100% output voltage (V) *5
-1.00
1.00
-10.0
10.0
4.0
20.0
5
10
Power ON-delay time (seconds)
Power-saving mode
0, 1 – 60
0 : Continuous display
1 – 60 : Time before display turned off (minutes)
21
2
0 – 9999
Parity check error count
–
The count value is reset to 0 with double-clicking the DATA DOWN key.
Reset all settings
ROM version
22
23
3
N/A
0, 1
—
0
–
*1. ITEM 08 < ITEM 09.
*2. Open collector input logic
LOGIC ITEM 10
DATA
0 : Positive logic
1 : Negative logic
INPUT
0
1
0
1
TTL level, open collector sink type (TTL level)
24V DC, open collector source type
Short (LOW) Open (HIGH) Open (HIGH) Short (LOW)
Open Short Short Open
*3. “Opencircuit” with 24V DC input
*4. “Shortcircuit” with 24V DC input
*5. Of the range set in ITEM 08/09. ITEM 17 < ITEM 18.
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 4/7
https://www.m-system.co.jp/
MODEL: DA3
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
6
5
4
3
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
7
8
1
2
8–M3.5
SCREW
16
(.63)
50 (1.97)
103 (4.06)
123 (4.84)
40 (1.57)
50 (1.97)
55 (2.17) min.
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
PL1 PL2
(POL) (LOAD)
Isolation
D/A
Converter
INPUT
1
2
7
8
+
OUTPUT
POWER
–
Digital
Computation
Circuit
U(+)
V(–)
DATA
3
4
5
6
ITEM
Base Socket
■ Input Connection Examples
• Standard type
TTL level
PLC
• Option /A
24V DC
Open collector, sink type
PLC
DA3
DA3
PLC
DA3
5V
24V
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 5/7
https://www.m-system.co.jp/
MODEL: DA3
INPUT CONNECTOR (26-pin)
■ BCD INPUT
■ BINARY TWO'S COMPLEMENT INPUTS
PIN NO.
ASSIGNMENT
1×100
2×100
4×100
8×100
1×101
2×101
4×101
8×101
1×102
2×102
4×102
8×102
1×103
2×103
4×103
8×103
PIN NO.
17
ASSIGNMENT
COM (–)
COM (–)
No connection
POL
PIN NO.
ASSIGNMENT
PIN NO.
17
ASSIGNMENT
COM (–)
1
2
1
2
B0
B1
B2
B3
B4
B5
B6
B7
B8
18
18
COM (–)
3
19
3
19
No connection
POL
*1
4
20
4
20
5
21
LOAD*1
LOAD*1
P0 *2
P1
P2
5
21
LOAD
*1
6
22
6
22
LOAD
7
23
7
23
P0*3
P1
P2
8
24
8
24
9
25
9
25
10
11
12
13
14
15
16
26
P3
10
11
12
13
14
15
16
B9
26
P3
B10
B11
B12
B13
B14
B15
*1. Pin No. 21 and 22 are internally connected.
*2. P0 corresponds to n 100, P1 to n 101, P2 to n 102, P3 to n 103. Only P0 corresponds when the parity for all digits are valid.
× ×
×
×
*3. P0 corresponds to B0 through B3, P1 to B4 through B7, P2 to B8 through B11, P3 to B12 through B15. Only P0 corresponds when the parity
for all digits are valid.
Note: With the number of bits set to 14 (or 12, 10, 8) with ITEM 07, Pin No. 1 – 14 (or 1 – 12, 1 – 10, 1 – 8) are valid.
TIMING CHART
• Example: TTL Level Input (setting)
10 ms min.
LOAD INPUT
1 ms min.
DATA INPUT
The unit reads data upon detecting a change of LOAD input status.
DO NOT change LOAD input setting when the data input logic is changed.
Note: Even if LOAD signal is entered, the unit does not convert into analog
and hold previous value until entering next normal data, when error
isdetected by parity check.
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 6/7
https://www.m-system.co.jp/
MODEL: DA3
INPUT-OUTPUT RELATION EXAMPLES
• FS
-FS stands for -15 % of the input range (0 to 100 %), which is configured by ITEM 08, display range scalingꢀ0 % and ITEM 09,
display range scalingꢀ100 %. +FS stands for +115 % of the input range.
• OR
When one of the following conditions is true, the digital input overflows (OR).
1) When the input signal is out of the range between -FS and +FS.
2) When the display value (= input signal) exceeds the display range.
The display range differs according to input code. For example, in case of BCD with polarity, it is -9999 to 9999. Please refer to
the instruction manual for detail.
■ BCD, BINARY (WITH POLARITY)
ANALOG OUTPUT
DATA
POLARITY
OR
POL
MSB
LSB
–FS
DIGITAL INPUT
■ OFFSET BINARY & TWO’S COMPLEMENT
+FS
0%
OR
DATA
UNUSED
POL
MSB
LSB
Specifications are subject to change without notice.
DA3 SPECIFICATIONS
ES-1395 Rev.14 Page 7/7
https://www.m-system.co.jp/