CSP-471-AK4 [MSYSTEM]

Final Control Elements;
CSP-471-AK4
型号: CSP-471-AK4
厂家: M-SYSTEM    M-SYSTEM
描述:

Final Control Elements

文件: 总4页 (文件大小:110K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: CSP  
Final Control Elements  
[3] POWER INPUT  
AC Power  
K4: 100 V AC, 50/60 Hz or 110 V AC, 60 Hz  
L4: 200 V AC, 50/60 Hz or 220 V AC, 60 Hz  
SERVO-TOP VALVE ACTUATOR TYPE C  
(linear type)  
Functions & Features  
•Actuator for a control valve  
•Lightweight, compact design  
•Simple field adjustments  
GENERAL SPECIFICATIONS  
Environmental protection: IP 56  
Action: Direct or reverse; field selectable with DIP switches  
(factory set to “reverse”)  
•Torque limiters  
•Electronic limiters for the full-open and -closed positions  
are easy to adjust.  
(In “reverse” action with upright mount, the output stem  
goes up with an input signal increase.)  
Operation at abnormally low input: Extend, Retract or Stop;  
field selectable with DIP switches; default set to Stop.  
Detectable input drop level: 0.37 ±0.1 V DC; converted into  
voltage  
•ISO standard flange  
Wiring conduits: G 1 female thread (two)  
Material  
Body: Aluminum alloy  
Cover: Steel  
Terminal screws: Nickel-plated steel (torque 0.8 N·m)  
Paint color: Munsell N6 (handle: red)  
Drive: AC motor (15-minute rating)  
Startup current: 3.2A (power input code K4)  
1.6A (power input code L4)  
MODEL: CSP–[1]71-[2][3]  
Insulation class: B  
(thermal protector incorporated; 120 ±5°C)  
Power control element: Semiconductor switch  
Position detection: Potentiometer  
Deadband adjustment: 0.2 – 3.0 % (default set to approx.  
1.5 %)  
ORDERING INFORMATION  
• Code number: CSP-[1]71-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. CSP-471-AK4)  
Restart limiting timer adjustment: 0 – 30 sec. (default set to  
approx. 4 sec.)  
[1] MAXIMUM STROKE  
4: 40 mm (1.57")  
Isolation: Signals to power to sequential signals to metallic  
housing  
7: 75 mm (2.95")  
Zero adjustment: 0 – 25 %  
Span adjustment: 50 - 100 %  
Torque limiting mechanism: Incorporated  
Space heater: Incorporated  
OPERATION TIME, MAXIMUM THRUST  
7: 34 seconds / 20 mm, 12000 N  
Manual operation: Available  
OUTPUT STEM TYPE  
1: M22 male screw, pitch 1.5  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
[2] INPUT  
Current  
OUTPUT SPECIFICATIONS  
Speed & Thrust (at rated power input voltage)  
Operation time (thrust 10000 N): 34 sec./20 mm (50 Hz), 29  
sec./20 mm (60 Hz)  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
Voltage  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
Maximum thrust: 12000 N  
Position Signal: 4 – 20 mA DC  
Load resistance: 300 Ω maximum  
(The output signal increases when the stem retracts.)  
CSP SPECIFICATIONS  
ES-4826 Rev.4 Page 1/4  
http://www.m-system.co.jp/  
MODEL: CSP  
Sequential Control Signal: "Full-open", "full-closed" and  
"Alarm"  
NPN open collector: 30 V DC @ 100 mA max.  
Saturation voltage: 1 V DC  
INSTALLATION  
Supply voltage  
Operational voltage range:  
Code K4: 100V AC ±10% at 50 Hz, 90 – 121V AC at 60 Hz  
Code L4: 200V AC ±10% at 50 Hz, 180 – 242V AC at 60 Hz  
Power consumtpion:  
Code K4: 200 VA at rated current  
Code L4: 240 VA at rated current  
Operating temperature: -10 to +60°C (14 to 140°F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Vibration: ≤ 19.6 m/s (2G) at 50 Hz  
2
Mounting position: Standing to horizontal  
Weight: 15 kg (33.1 lb)  
PERFORMANCE  
Hysteresis: 1 mm or less  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(signal to power to sequential signals)  
2000 V AC @ 1 minute  
(sequential signals to metallic housing)  
1500 V AC @ 1 minute  
(power to metallic housing)  
1000 V AC @ 1 minute  
(signal to metallic housing)  
TERMINOLOGY  
Torque Limiting Mechanism  
Torque switches are equipped to protect the motor from  
overload caused by foreign objects stuck in the valve.  
The switches can be activated within 2 to 98 % range to  
stop the motor and to output an alarm signal, with the RUN  
LED flashes in 0.5 sec. intervals.  
Restart Limiting Timer  
A timer is incorporated to protect the motor and other  
incorporated components from overheating. The timer  
prevents the motor from restarting for a certain interval (0  
to 30 sec. selectable) once the motor has been stopped  
within deadband.  
Electronic Limiter  
This model is equipped with electronic limiters in order to  
prevent mechanical locks when the input goes below 0 % or  
above 100 %.  
Limiters are set at approx. -1.5 % for the full-closed side,  
approx. 101.5 % for the full-open side.  
CSP SPECIFICATIONS  
ES-4826 Rev.4 Page 2/4  
http://www.m-system.co.jp/  
MODEL: CSP  
EXTERNAL DIMENSIONS unit: mm (inch)  
150 (5.91)  
81 (3.19)  
ø216 (8.50)  
10 (.39)  
2x2–M8x16  
130 (5.12)  
Space required to  
remove cover  
79 (3.11) 40  
(1.57)  
Handle knob position at use  
2–G1 WIRING CONDUIT  
4–ø11  
Yoke Mounting Requirements  
65  
65  
YOKE SURFACE  
M22, 1.5 pitch  
(2.56) (2.56)  
ø70 00..003706 ((22..775553))  
[
] for CSP-4  
CSP SPECIFICATIONS  
ES-4826 Rev.4 Page 3/4  
http://www.m-system.co.jp/  
MODEL: CSP  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
min.  
Position  
Input  
Circuit  
max.  
TORQUE SW  
(extended)  
TORQUE SW  
(retracted)  
Current Output  
Driver  
+
+
5
6
3
4
POSITION  
OUTPUT  
RUN INP  
SSR for  
Braking  
*
INPUT  
CPU  
SSR  
SSR  
AC MOTOR  
M
Isolation  
FULL-OPEN/-CLOSED  
SIGNAL (retracted)  
7
8
FULL-OPEN/-CLOSED  
SIGNAL (extended)  
SEQUENTIAL  
CONTROL  
SIGNALS  
Fuse  
1 2 3 4  
9
ALARM  
COM2  
U
V
1
2
MODE DEADBAND  
ADJ.  
POWER  
SELECTOR  
10  
*Input shunt resistor incorporated for current input.  
Specifications are subject to change without notice.  
CSP SPECIFICATIONS  
ES-4826 Rev.4 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

CSP-471-AL4

Final Control Elements
MSYSTEM

CSP-5-D-02-SP-A

Interconnection Device
SAMTEC

CSP-5-D-02-SP-P

Interconnection Device
SAMTEC

CSP-5-D-02-SP-ST4

Interconnection Device
SAMTEC

CSP-5-D-02-SP-ST8

Interconnection Device
SAMTEC

CSP-5-D-02-SP-V

Interconnection Device
SAMTEC

CSP-5-D-X-SP-P

Interconnection Device
SAMTEC

CSP-5-D-X-SP-ST2

Interconnection Device
SAMTEC

CSP-5-D-X-SP-ST3

Interconnection Device
SAMTEC

CSP-5-D-X-SP-ST4

Interconnection Device
SAMTEC

CSP-5-S-02-SP-ST2

Interconnection Device
SAMTEC

CSP-5-S-02-SP-ST3

Interconnection Device
SAMTEC