ARB-6144-V/BL [MSYSTEM]
Limit Alarms (potentiometer adj.) A-UNIT;型号: | ARB-6144-V/BL |
厂家: | M-SYSTEM |
描述: | Limit Alarms (potentiometer adj.) A-UNIT |
文件: | 总4页 (文件大小:126K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: ARB
5: Pt 50 Ω (JIS'81)
Limit Alarms (potentiometer adj.) A-UNIT
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 100°C, 180°F)
6: Ni 508.4 Ω
RTD ALARM
Functions & Features
(Usable range: -50 to +200°C, -58 to +392°F; min.span: 30°C, 54°F)
0: Specify
• Providing SPDT relay outputs at preset input levels
• Direct input from an RTD
Note: Consult M-System for 2-wire RTD
• Dual (Hi/Lo) trip
SETPOINT ADJUSTMENTS
• Linearization
1: Single-turn screws
• Burnout protection
• "Active bridge" circuit containing two constant current
sources allows large leadwire resistances up to 200 Ω
• Energized or de-energized coil at a tripped condition
selectable
[2] SETPOINT 1 OUTPUT
1: Hi (coil energized at alarm)
2: Hi (coil de-energized at alarm)
3: Lo (coil energized at alarm)
4: Lo (coil de-energized at alarm)
• Hysteresis (deadband) adjustable
• Enclosed relays
• Relays can be powered 110 V DC
• High-density mounting
[3] SETPOINT 2 OUTPUT
1: Hi (coil energized at alarm)
2: Hi (coil de-energized at alarm)
3: Lo (coil energized at alarm)
4: Lo (coil de-energized at alarm)
Typical Applications
• Annunciator
• Various alarm applications
50
(1.97)
[4] POWER INPUT
AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
80
(3.15)
132
(5.20)
mm (inch)
DC Power
S: 12 V DC
MODEL: ARB-[1]1[2][3]-[4][5]
R: 24 V DC
V: 48 V DC
ORDERING INFORMATION
• Code number: ARB-[1]1[2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. ARB-1111-B/BL/Q)
P: 110 V DC
[5] OPTIONS (multiple selections)
Burnout
• Temperature range (e.g. 0 – 200°C)
• Specify the specification for option code /Q
(e.g. /C01/S01)
blank: Upscale burnout
/BL: Downscale burnout
Other Options
blank: none
[1] INPUT RTD (2- or 3-wire)
1: JPt 100 (JIS'89)
/Q: Option other than the above (specify the specification)
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 50°C, 90°F)
3: Pt 100 (JIS'89)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
4: Pt 100 (JIS'97, IEC)
/C02: Polyurethane coating
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
/C03: Rubber coating
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 1/4
http://www.m-system.co.jp/
MODEL: ARB
TERMINAL SCREW MATERIAL
INSTALLATION
Power input
/S01: Stainless steel
• AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
GENERAL SPECIFICATIONS
Construction: Plug-in
• DC: Operational voltage range: rating ±10 %, or 85 – 150
V for 110 V rating (ripple 10 % p-p max.)
approx. 2 W (80 mA at 24 V)
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Setpoint adjustments: 270°-turn screwdriver adjustments
(front); 0 – 100 % independently
Weight: 450 g (0.99 lb)
PERFORMANCE in percentage of span
Trip point repeatability: ±0.5 %
Hysteresis (deadband) adjustments: 1 – 100 % (front)
Linearization: Standard
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Burnout response: ≤ 10 sec.
Front LEDs: LED turns on at a tripped condition; red for
output 1, green for output 2
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output 1
to output 2 to power to ground)
Power ON timer: Relays de-energized for approx. 2 seconds
after power is turned on.
INPUT SPECIFICATIONS
Maximum leadwire resistance: 200 Ω per wire (3-wire)
Sensing current: 2 mA
OUTPUT SPECIFICATIONS
■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 5 x 10 cycles
7
For maximum relay life with inductive loads, external
protection is recommended.
Alarm Trip Operation Terminal No. in parentheses
(9-11)ON
Output 1
(9-10)ON
(1-3)ON
Output 2
(1-2)ON
Input
(%)
0
▲
50
▲
100
Output 2
Setpoint
Output 1
Setpoint
Trip Operation in Power Failure
• Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON
• Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 2/4
http://www.m-system.co.jp/
MODEL: ARB
EXTERNAL VIEW
No.1 Setpoint Adj.
No.1 LED
Span Adj.
Zero Adj.
No.1 Deadband (Hysteresis) Adj.
No.2 Deadband (Hysteresis) Adj.
No.2 LED
No.2 Setpoint Adj.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
9
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Burnout
HYSTERESIS
SETPOINT (DEADBAND)
RTD
*
4
5
6
A
B
B
Z
S
11
10
9
H
Reference
Resistor
+
–
Differential
Amplifier
Comparator
Ry
SETPOINT 1
OUTPUT
L
2mA
2mA
C
*
Linearizer
3
H
Comparator
Ry
SETPOINT 2
OUTPUT
2
L
1
C
HYSTERESIS
(DEADBAND)
SETPOINT
7
U(+)
V(–)
POWER
8
Base Socket
*Relay status for output codes “1” & “4”, at power OFF.
■ Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Varistor or Spark
Quenching Circuit
Diode, Varistor or
CR Circuit
LOAD
LOAD
U
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 3/4
http://www.m-system.co.jp/
MODEL: ARB
Specifications are subject to change without notice.
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 4/4
http://www.m-system.co.jp/
相关型号:
ARB25H
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB25L
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB25M
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB35H
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB35L
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB35M
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB50H
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB50L
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
ARB50M
Rating at 25â Ambient temp. Unless otherwise specified. Single phase, half sine wave, 60HZ,resistive or inductive load.
GXELECTRONICS
©2020 ICPDF网 联系我们和版权申明