60D-162-R [MSYSTEM]
Field Network Modules 60-UNIT Series;型号: | 60D-162-R |
厂家: | M-SYSTEM |
描述: | Field Network Modules 60-UNIT Series |
文件: | 总4页 (文件大小:140K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 60D
Field Network Modules 60-UNIT Series
[4] OPTIONS
blank: none
/Q: With options (specify the specification)
ANALOG I/O MODULE
(DeviceNet)
Functions & Features
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with DeviceNet
• Saving power and I/O wiring inside an instrumentation
panel
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
72
(2.83)
80
(3.15)
RELATED PRODUCTS
•Special cable (model: MCN34)
• Programming Unit (model: PU-2x)
153
(6.02)
GENERAL SPECIFICATIONS
Construction: Plug-in
mm (inch)
Connection
DeviceNet: Euro type connector terminal (applicable
MODEL: 60D-[1][2]-[3][4]
wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminal
ORDERING INFORMATION
• Code number: 60D-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. 60D-161-K/Q)
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to DeviceNet to power to FG1
Power indicator: Green LED turns on with power supplied.
• Specify the specification for option code /Q
(e.g. /C01/S01)
DeviceNet COMMUNICATION
Transmission cable: Approved for DeviceNet
Node address setting: DIP switch; 00 – 63
Baud rate setting: DIP switch
[1] NO. OF CHANNELS
04: 4 points
08: 8 points
16: 16 points
MS (Module Status) indicator: Bi-color (green/red) LED
indicates device status.
[2] I/O TYPE
1: Input
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.
2: Output
INPUT SPECIFICATIONS
■ Analog Input
[3] POWER INPUT
AC Power
Input range: 1 – 5 V DC
K: 85 – 132 V AC
Input resistance: ≥ 1 MΩ
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
(CE not available)
DC Power
R: 24 V DC
A/D conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 1770 (0 – 6000). -15 to 0 % is represented by 2’s
complements.
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Overall range is represented by hexadecimal FC7C – 1AF4
60D SPECIFICATIONS
ES-6604 Rev.15 Page 1/4
https://www.m-system.co.jp/
MODEL: 60D
(-900 – +6900), for -15 – +115 %.
• Output Connector Pin Assignment
Note: In the firmware version 3.00 or later, analog input
range 0 – 100% can be converted into hexadecimal 0000 –
2710 (0 – 10000).
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Output
Output
Output
Output
Output
Output
Output
Output
Output
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
In addition, negative values of analog input range -15 to 0%
can be converted into signed absolute values.
Refer to the instruction manual for details.
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
• Input Connector Pin Assignment
COM
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
COM
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
No connection
COM
3
4
COM
COM
5
6
COM
COM
7
8
COM
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
COM
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
COM
COM
COM
No connection
COM
Output 1 – 4 for 4 points, 1 – 8 for 8 points.
Input 10
Input 11
COM
COM
Input 12
COM
INSTALLATION
Power consumption
Input 13
COM
Input 14
COM
•AC: Approx. 4 VA
Input 15
COM
•DC: Approx. 4 W (160 mA)
Input 16
COM
No connection
No connection
Supply voltage to network: 11 – 25 V DC supplied through
the network terminal block
Input 1 – 4 for 4 points, 1 – 8 for 8 points.
Supply current to network: 60 mA max. @ 24 V
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
OUTPUT SPECIFICATIONS
■ Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held.
Weight: 450 g (0.99 lb)
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output
to DeviceNet to power)
D/A conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s
complements.
Overall range is represented by hexadecimal FC7C – 1AF4
(-900 – +6900), for -15 – +115 %.
2000 V AC @ 1 minute (input or output or DeviceNet or
power to FG1)
Note: In the firmware version 3.00 or later, analog output
range 0 – 100% can be converted into hexadecimal 0000 –
2710 (0 – 10000).
STANDARDS & APPROVALS
EU conformity:
In addition, negative values of analog output range -15 to
0% can be converted into signed absolute values.
Refer to the instruction manual for details.
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
60D SPECIFICATIONS
ES-6604 Rev.15 Page 2/4
https://www.m-system.co.jp/
MODEL: 60D
EXTERNAL VIEW
PU-2x Modular Jack
Power LED
CN1
MS Indicator LED
NS Indicator LED
I/O Connector
PWR
MS
Euro Type Connector Terminal
for DeviceNet
NS
NA0
NA1
NA2
NA3
NA4
NA5
DR0
DR1
Node
Address
Setting
Baud Rate
Setting
ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
7
14
6
5
12
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
8
9
15 10
1
11
2
14–M3.5
SCREW
14
72 (2.83)
(.55)
109 (4.29)
139 (5.47)
60 (2.36)
72 (2.83)
38 (1.50)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
60D SPECIFICATIONS
ES-6604 Rev.15 Page 3/4
https://www.m-system.co.jp/
MODEL: 60D
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG1 terminal to ground.
Caution: FG1 terminal is NOT a protective conductor terminal.
COMMUNICATION MODULE
INDICATOR
LED
DIP SW
V+
CAN_H
Drain
CAN_L
V–
To 10-RACK, 18-RACK etc.
To Other
DeviceNet
Devices
DeviceNet
Comm. CPU
A / D
or
D / A
Conv.
I / O
CPU
MODULAR JACK
PU-2x
SERIAL
TRANSMISSION
LINE
7
U(+)
POWER
V(–)
FG1
14
8
■ CABLE IDENTIFICATION
The following table defines wire insulation colors and
designations. The terminal block is labeled also in
the same colors so that the correct assignment can
be confirmed.
COLOR
black
blue
DESIG.
V –
DESCRIPTION
Power (–)
CAN_L
Drain
CAN_H
V +
Signal Low
Shield
bare
white
red
Signal High
Power (+)
Specifications are subject to change without notice.
60D SPECIFICATIONS
ES-6604 Rev.15 Page 4/4
https://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明