27HU-B-000T11/S [MSYSTEM]
Head-mounted Two-wire Signal Conditioners 27-UNIT;型号: | 27HU-B-000T11/S |
厂家: | M-SYSTEM |
描述: | Head-mounted Two-wire Signal Conditioners 27-UNIT |
文件: | 总7页 (文件大小:199K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 27HU-B
Head-mounted Two-wire Signal Conditioners
27-UNIT
[2] TEMPERATURE DRIFT
0: Standard (temp. coefficient 0.015 %/°C)
L: Ultra-low temperature drift
(temp. coefficient 0.002 %/°C typ. 0.005 %/°C max.)
2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER
(HART communication, outdoor enclosure, explosion-proof)
Functions & Features
[3] LED INDICATOR
0: Without
• Universal input: DC mV, T/C, RTD and resistance
• High accuracy
1: With (SIL not available)
• HART communication
• Explosion-proof approval
[4] TERMINAL BLOCK
• Suitable for Functional Safety applications up to SIL2
• Programming via hand-held communicator or via PC
• A wide variety of T/C and RTD types
• User’s temperature table can be used
• Self diagnostics
0: None (Output connection: Terminals on module)
(For TIIS, selectable only with ‘No indicator’ option.)
T: Incorporated
(Selectable only with the LED indicator option)
• Ultra-low temp. drift option (20 ppm/°C typ.)
• Stainless steel enclosure optional
[5] WIRING CONDUIT
Confirm selectable combinations of approval and wiring
conduit types in the table below.
0: G 1/2
1: 1/2 NPT
2: M20 × 1.5
3: PG 13.5
[6] MOUNTING BRACKET
0: Without
1: With
[7] OPTIONS
Enclosure Materials
MODEL: 27HU–B–[1][2][3][4][5][6][7]
Blank: Diecast aluminium enclosure
/S: Stainless steel enclosure
(TIIS flameproof approval not selectable)
ORDERING INFORMATION
• Code number: 27HU-B-[1][2][3][4][5][6][7]
Specify a code from below for each of [1] through [7].
(e.g. 27HU-B-0L1T01/S).
I SELECTABLE WIRING CONDUITS SPECIFIC TO EACH APPROVAL
ʻNʼ marked combinations are not selectable.
APPROVAL
Use Ordering Information Sheet (No. ESU-7652). Factory
standard setting will be used if not otherwise specified.
Specify the country in which the product is to be used with
the Safety Approval code 4.
0
3
4
8
WIRING CONDUIT
0
1
2
3
Y
Y
Y
Y
N
Y
N
Y
Y
N
Y
N
N
N
N
N
[1] SAFETY APPROVAL
Confirm selectable combinations of approval and wiring
conduit types in the table below.
0: None
RELATED PRODUCTS
• USB interface Bell202 modem (model: COP-HU)
Usable in ‘non-hazardous’ area only.
• Hand-held communicator
3: FM explosion-proof
4: ATEX flameproof
• PC configurator software (model: 27HUCFG)
Downloadable at M-System’s web site.
• Cable gland (model: BX-E-SXY)
8: TIIS flameproof (CE not available)
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 1/7
http://www.m-system.co.jp/
MODEL: 27HU-B
• Input sensor type and numbers
PACKAGE INCLUDES...
• Cable gland: Two provided for TIIS flameproof type
Model No.: BX-E-SXY
• Number of wires (RTD & resistance)
• Input range (inverted range selectable)
• Burnout
Cable entries: Elastomeric sealing rings
Wiring conduit size: G 1/2
• Output limits (Upper / Lower)
• Damping time (factory set to 0)
• Cold junction compensation (T/C; internal or external
sensor selectable)
Material: Chrome-plated brass (entry)
CR (sealing ring)
Applicable wire size: 8 - 12 dia.
• Mounting screws
• Linearization
• Sensor calibration
Bolt (M8 x 15): 4 pcs.
• Output calibration
Spring washer for M8: 4 pcs.
Material: Stainless steel 304
• Mounting bracket assembly (option)
Mounting bracket: 1 pcs.
• HART communication mode
Refer to the HART setup manual or the PC configurator
users manual for the detail.
M10 U-bolt: 2 pcs.
Nut for M10: 4 pcs.
HART COMMUNICATION
Spring washer for M10: 4 pcs.
Material: Stainless steel 304
Applicable pipe: 1 1/2” min.; 2” max.
• Engineering unit label (1)
Protocol: HART communication protocol
HART address range: 0 – 15 (factory set to 0)
Transmission speed: 1200 bps
Digital current: Approx. 1 mAp-p when communicating
Character format: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit,
1 Stop Bit
GENERAL SPECIFICATIONS
Degree of protection: NEMA 4X, IP66/IP67
Wiring conduit: See ‘Ordering information.’
Connection:
Distance: 1.5 km (0.9 miles)
HART communication mode: Master-Slave Mode and Burst
Mode (factory set to Master-Slave)
HART network mode: Point-to-Point Mode and Multi-drop
Mode; automatically set to Multi-drop Mode when the
address is set to other than 0.
• Without terminal block and indicator: M3 screw terminal in
transmitter
(Torque: 0.5 Nm)
• Without terminal block with indicator:
Input signal: M3 screw terminal in transmitter
(Torque: 0.5 Nm)
LED INDICATOR (option)
LED: 8 mm (.3”) 7-segment, red
Output signal: Euro terminal
Number of display digits: 4
(Applicable wire size: 0.14 to 1.5 mm
2
(AWG26 to 16),
Scaling range: -1999 to 9999
stripped length: 6 mm)
Offset range: -1999 to 9999
• With Terminal block and indicator:
Decimal point position: 10 –1, 10 –2, 10 –3, or no decimal point
Polarity sign: Minus (–) sign added automatically according
to the computation result
Input signal: M3 screw terminal in transmitter
(Torque: 0.5 Nm)
Output signal: M3 screws in terminal block
(Torque: 0.5 Nm)
Read rate: 2.5/s
Over-range warning: All segments dark except the top ones
that blink with the input exceeding the display/measurable
range; or the bottom ones that blink with the input below
the range.
Screw terminal
• Input signal: Nickel-plated brass
• Output signal:
Without terminal block and indicator: Nickel-plated brass
With terminal block and indicator: Nickel-plated steel
Materials
Engineering unit display: Unit label included; LED backlight
provided
Engineering unit indication: Sticker label attached
DC, AC, W, ℃ , °F, V, mV, A, mA, %, kW, mW, kV, kA, psi, K,
bar, barg, Nℓ/min, kvar, Mvar, var, m, mm, kg, kg/h, kPa,
Transmitter Housing: Flame-resistant resin (black)
Indicator Housing: Flame-resistant resin (black)
Enclosure material: Diecast aluminium standard; SCS14
stainless steel casting optional (equivalent to type 316);
silver color,epoxy resin coated
MPa, N·m, Nm
3
/h, m
3
/h, m
3
/sec, m/sec, kgf/cm , ℓ/min, %RH,
2
ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa
Isolation: Input to output to outdoor enclosure
User-configurable items:
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 2/7
http://www.m-system.co.jp/
MODEL: 27HU-B
· Unit
INPUT SPECIFICATIONS
The input is factory set for use with K thermocouple, single
input, 0 to 100°C, internal CJC sensor.
See Table 1 for the available input type, the minimum span
and the maximum range.
Approx. 1.3 kg (2.9 lb), aluminium
Approx. 4.0 kg (8.8 lb), stainless steel
Approx. 2.0 kg (4.4 lb), TIIS flameproof
· Mounting bracket set (option)
Approx. 0.78 kg (1.72 lb)
■ DC mV (dual input available)
Input resistance: ≥ 1 MΩ
■ Thermocouple (dual input available)
Input resistance: ≥ 1 MΩ
PERFORMANCE
Accuracy: See Table 1.
Burnout sensing: 33 μA
Display accuracy: ±0.01 mA
External CJC sensor type: Pt 100
■ RTD (2-wire, 3-wire or 4-wire)
Input resistance: ≥ 1 MΩ
(Refer to 'how to calculate accuracy against scale'.)
Cold junction compensation accuracy: ±0.5°C (±0.9°F) with
internal CJC sensor
Excitation: 0.2 mA
LED indicator temp. coefficient: ±0.015 %/°C
Response time: ≤ 2 sec. (0 – 90 %) with damping time
set to 0 and when not communicating via HART.
Supply voltage effect: ±0.005 % of span/V
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(input to output to outdoor enclosure)
Allowable leadwire resistance: Max. 10 Ω per wire
■ Resistance (2-wire, 3-wire or 4-wire)
Input resistance: ≥ 1 MΩ
Excitation: 0.2 mA
Allowable leadwire resistance: Max. 10 Ω per wire
Safety integrity level according to IEC 61508: Suitable for
use in a safety instrumented system up to SIL2 (together
with sensor) if appropriate safety instructions are observed.
Consult M-System.
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
Operational range: 3.75 – 23 mA
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 8 (V)*) ÷
0.023 (A) (including leadwire resistance)
*12 (V) with LED indicator option.
HOW TO CALCULATE ACCURACY AGAINST SCALE
Example: 4 – 20 mA input, Scale 0 – 100
Burnout: 3.75 – 3.8 mA or 21.5 – 23 mA
(factory set to 23 mA)
Accuracy = 0.01 mA ÷ (20 – 4)mA × 100 = 0.063 %
Display Error = (100 – 0) × 0.063 % = ±0.063 digits
Upper output limit proportional to the input:
20 – 21.5 mA (factory set to 21.5 mA)
Lower output limit proportional to the input:
3.8 – 4 mA (factory set to 3.8 mA)
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Update time: 440 msec. (660 msec. with dual input)
Output characteristics for dual input:
Average or Differential selectable
EEx d EN 50018
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
INSTALLATION
Supply voltage
EN 50581
Non-approved: 8 – 35 V DC (without LED indicator)
12 – 39 V DC (with LED indicator)
ATEX & FM: 8 – 32 V DC (without LED indicator)
12 – 32 V DC (with LED indicator)
TIIS: 8 – 28 V DC (without LED indicator)
12 – 32 V DC (with LED indicator)
Operating temperature
Safety approval:
FM: Explosion-proof and Dust-ignition proof
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
T5 and T6
(Class 3615)
Non-approved: -40 to +85°C (-40 to +185°F)
ATEX & FM: T5, -40 to +80°C (-40 to +176°F)
T6, -40 to +70°C (-40 to +158°F)
TIIS: T6, -20 to +60°C (-4 to +140°F)
Weight:
TIIS: Flameproof
Ex d IIC T6
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 3/7
http://www.m-system.co.jp/
MODEL: 27HU-B
ATEX: FIameproof
II 2G, Ex db IIC, T5, T6 Gb
(EN 60079-0)
(EN 60079-1)
INDICATOR TOP VIEW (option)
Model No. Label
Data Display
27HU-B
°C
Engineering
Unit
ENTR / ESC BACK / DOWN NEXT / UP
NEXT / UP Button
ENTR / ESC Button
BACK / DOWN Button
INPUT TYPE, RANGE & ACCURACY
TEMPERATURE DRIFT
MINIMUM MAXIMUM ACCURACY
1
*
INPUT TYPE
STANDARD
DRIFT *2
ULTRA-LOW
SAPN
SPAN
DRIFT *3
0.5 μV/°C
5 mΩ /°C
DC mV
4 mV
25 Ω
-100 to +800 mV
0 to 4 kΩ
°F
10 μV
0.1 Ω
1.5 μV/°C
15 mΩ /°C
Resistance
°C
TEMPERATURE DRIFT
Thermocouple
MINIMUM MAXIMUM ACCURACY MINIMUM MAXIMUM ACCURACY STANDARD
DRIFT *2
ULTRA-LOW
DRIFT *3
1
1
SAPN
RENGE
*
SAPN
RENGE
*
K (CA)
E (CRC)
J (IC)
50
50
50
-180 to +1372
-100 to +1000
-100 to +1200
0.5
0.5
0.5
90
90
90
-292 to +2501
-148 to +1832
-148 to +2192
0.9
0.9
0.9
0.075°C/°C
0.075°C/°C
0.075°C/°C
0.025°C/°C
0.025°C/°C
0.025°C/°C
T (CC)
B (RH)
R
50
-200 to +400
400 to 1820
0.5
1
90
-328 to +752
752 to 3308
0.9
1.8
1.8
0.075°C/°C
0.3°C/°C
0.3°C/°C
0.025°C/°C
0.1°C/°C
0.1°C/°C
100
100
180
180
4
4
4
4
-50 to +1760
*
1
-58 to +3200
*
S
100
100
100
-50 to +1760
0 to 2300
0 to 2300
*
1
1
1
180
180
180
-58 to +3200
32 to 4172
32 to 4172
*
1.8
1.8
1.8
0.3°C/°C
0.3°C/°C
0.3°C/°C
0.1°C/°C
0.1°C/°C
0.1°C/°C
C (WRe 5-26)
D (WRe 3-25)
N
U
L
50
50
50
-180 to +1300
-200 to +600
-100 to +900
0.5
0.5
0.5
90
90
90
-292 to +2372
-328 to +1112
-148 to +1652
0.9
0.9
0.9
0.075°C/°C
0.075°C/°C
0.075°C/°C
0.025°C/°C
0.025°C/°C
0.025°C/°C
°C
°F
TEMPERATURE DRIFT
RTD
MINIMUM MAXIMUM ACCURACY MINIMUM MAXIMUM ACCURACY STANDARD
1
ULTRA-LOW
DRIFT *3
DRIFT *2
1
*
SAPN
RENGE
*
SAPN
RENGE
Pt 100 (JIS '97, IEC)
Pt 200
Pt 500
10
10
10
-200 to +850
-200 to +850
-200 to +850
0.1
0.1
0.1
18
18
18
-328 to +1562
-328 to +1562
-328 to +1562
0.18
0.18
0.18
0.015°C/°C
0.015°C/°C
0.015°C/°C
0.005°C/°C
0.005°C/°C
0.005°C/°C
Pt 1000
JPt 100 (JIS '89)
Ni 100 (DIN 43760 '87)
10
10
10
-200 to +850
-200 to +510
-60 to +250
0.1
0.1
0.2
18
18
18
-328 to +1562
-328 to +950
-76 to +482
0.18
0.18
0.36
0.015°C/°C
0.015°C/°C
0.015°C/°C
0.005°C/°C
0.005°C/°C
0.005°C/°C
*1. DC mV:
Or 0.05 ꢀ oꢁ aꢂsolute range (greater oꢁ 0 ꢀ and 100 ꢀ range values), whichever is greater.
Or 0.2 ꢀ oꢁ aꢂsolute negative range ꢁor two inputs including negative ranges, whichever is greater.
Or 0.05 ꢀ oꢁ aꢂsolute range (greater oꢁ 0 ꢀ and 100 ꢀ range values), whichever is greater.
Resistance:
Thermocouple: Or 0.05 ꢀ oꢁ span, whichever is greater. Add cold junction compensation error.
RTD: Or 0.05 ꢀ oꢁ maꢃ. range (greater oꢁ 0 ꢀ and 100 ꢀ range values converted into °C), whichever is greater.
(For 2- or 3-wire RTD, the value is valid ꢂy the sensor caliꢂration aꢁter wiring is complete.)
*2. Or 0.015 ꢀ oꢁ aꢂsolute range/°C (greater oꢁ 0 ꢀ and 100 ꢀ range values), whichever is greater.
*3. Or 0.005 ꢀ oꢁ aꢂsolute range/°C (greater oꢁ 0 ꢀ and 100 ꢀ range values), whichever is greater.
*4. Conꢁormance range: 50 to 1760°C or 122 to 3200°F
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 4/7
http://www.m-system.co.jp/
MODEL: 27HU-B
EXTERNAL DIMENSIONS unit: mm (inch)
MOUNTING BRACKET (optional)
CABLE GLAND
*
(TIIS flameproof option)
G 1/2
92 (3.62)
4–M8, 12 (.47)deep
110 (4.33)
SPACE REQUIRED TO REMOVE COVER
78 (3.07) max.
114 (4.49)
110 (4.33)
78 (3.07) max.
2–G 1/2 or 1/2NPT or
M20x1.5 or PG13.5
*Two sets of cable gland are attached with TIIS flameproof option.
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 5/7
http://www.m-system.co.jp/
MODEL: 27HU-B
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ WITHOUT TERMINAL BLOCK (Output connection: Terminals on module)
• Without LED Indicator
HART
Comm.
Isolation
24V DC
Input
Computation
Output
Computation
Output
Driver
+
–
4
3
2
1
2
*
Low Drift
Amplifier
LOAD
OUTPUT
4 – 20mA DC
INPUT *1
CJC
Sensor
• With LED Indicator
HART
Comm.
Isolation
Input
Computation
Output
Computation
Output
Driver
+
–
4
Low Drift
Amplifier
3
INPUT *1
2
1
CJC
Sensor
24V DC
LOAD
ENTR / ESC
5
6
7
8
LED Display
2
*
OUTPUT
4 – 20mA DC
BACK / DOWN
NEXT / UP
Internal
Bridge
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 6/7
http://www.m-system.co.jp/
MODEL: 27HU-B
■ WITH TERMINAL BLOCK
HART
Comm.
Isolation
24V DC
Input
Computation
Output
Computation
Output
Driver
+
–
4
9
Low Drift
Amplifier
3
2
1
10
2
*
INPUT *1
OUTPUT
LOAD
11
12
4 – 20mA DC
CJC
Sensor
ENTR / ESC
5
6
7
8
LED Display
BACK / DOWN
NEXT / UP
Internal
Bridge
*1. Input Connection Examples
■ DC MILLIVOLT
■ THEMOCOUPLE
• Internal CJC
■ RTD & RESISTANCE
• Two-wire
• Two Inputs, Internal CJC
• Four-wire
–
+
+
4
3
2
1
4
4
3
2
1
4
3
2
1
4
3
2
1
B
B
comp. leadwire
–
SENSOR 2
SENSOR 1
–
–
+
3
2
1
–
–
+
+
B
A
A
INPUT
+
+
comp. leadwire
A
• Two Inputs
• External CJC
• Two Inputs, External CJC
• Three-wire
–
+
+
–
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
B
B
comp. leadwire
–
–
SENSOR 2
SENSOR 1
+
+
–
–
+
+
INPUT 2
INPUT 1
+
+
comp. leadwire
A
*2. Limited to 250 – 1100 Ω for HART communication
Specifications are subject to change without notice.
27HU-B SPECIFICATIONS
ES-7652 Rev.18 Page 7/7
http://www.m-system.co.jp/