18WT-1A66-R [MSYSTEM]
Rack-mounted DCS Signal Conditioners 18-RACK;型号: | 18WT-1A66-R |
厂家: | M-SYSTEM |
描述: | Rack-mounted DCS Signal Conditioners 18-RACK DCS 分布式控制系统 |
文件: | 总4页 (文件大小:117K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 18WT
Rack-mounted DCS Signal Conditioners 18-RACK
OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
WATT TRANSDUCER
Functions & Features
• Providing two DC output signals in proportion to AC active
POWER INPUT
power
DC Power
• Measuring bidirectional power flow
R: 24 V DC
• DC output containing little ripple is ideal for computer
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
input
• "Time division multiplication" method accepts distorted
waveforms
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Typical Applications
• Centralized monitoring and control of power management
system in a manufacturing facility or building
• SCR – Silicon Controlled Rectifier
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Output 1: Connector
Output 2: Connector
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Voltage input to current input to output 1 to
output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
MODEL: 18WT–[1][2]66–R
ORDERING INFORMATION
• Code number: 18WT-[1][2]66-R
Specify a code from below for each of [1] and [2].
(e.g. 18WT-1166-R)
• Calibration range (e.g. 0 – 1000 W)
• VT ratio, CT ratio (e.g. VT 3300/110 V, CT 250/5 A)
[1] CONFIGURATION
1: 3-phase / 3-wire
2: Single-phase / 2-wire
3: Single-phase / 3-wire
[2] INPUT (unbalanced load)
1: 110 V / 5 A AC
2: 110 V / 1 A AC
3: 220 V / 1 A AC
4: 220 V / 5 A AC
A: 100 V / 200 V / 1 A AC (single-phase / 3- wire)
B: 100 V / 200 V / 5 A AC (single-phase / 3- wire)
OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
18WT SPECIFICATIONS
ES-1866 Rev.7 Page 1/4
http://www.m-system.co.jp/
MODEL: 18WT
INPUT SPECIFICATIONS
Frequency: 50 or 60 Hz
INSTALLATION
Current consumption: Approx. 80 mA
• Current Input
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 200 g (0.44 lb)
Operational range: 0 – 120 % of rating
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10
sec., 120 % continuous
• Voltage Input
Operational range: 0 – 120 % of rating
Overload capacity: 150 % of rating for 10 sec., 120 %
continuous
PERFORMANCE in percentage of span
Accuracy: ±0.5 %
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Response time: ≤ 1 sec. (0 – 90 %)
■ How To Determine Wattage Range
Calibration Range [W] = Measuring Wattage ÷ ((VT Ratio) ×
(CT Ratio))
Ripple: 0.5 %p-p max. (50/60 Hz)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(voltage input to current input to output 1 or output 2 or
power)
Check that the required calibration range is within the
available range in the table. Specify this range when
ordering.
[example]
3-phase / 3-wire, measuring wattage 750 kW,
VT 3300/110 V, CT 250/5 A
500 V AC @ 1 minute (output 1 to output 2 to power)
2000 V AC @ 1 minute (input or output or power to ground)
750 × 10 [W] ÷ ((3300÷110) × (250÷5))= 0 – 500 [W]
3
• 3-phase / 3-wire
INPUT
BURDEN (VA)
AVAILABLE
RANGE
STD.RANGE
CURR.
0.1/phase
0.5/phase
0.1/phase
0.5/phase
VOLT.
110V/1A
110V/5A
220V/1A
220V/5A
±200W
±1000W
±ꢀ00W
±100 – ±2ꢀ0W
±500 – ±1200W
±200 – ±ꢀ40W
±1000 – ±2ꢀ00W
0.2
/phase
0.ꢀ
/phase
±2000W
• Single-phase / 2-wire
INPUT
BURDEN (VA)
VOLT. CURR.
AVAILABLE
RANGE
STD.RANGE
110V/1A
110V/5A
220V/1A
220V/5A
±100W
±500W
±200W
±1000W
0.1/phase
0.2
±50 – ±120W
±250 – ±±00W
±100 – ±2ꢀ0W
±500 – ±1200W
/phase
0.5/phase
0.1/phase
0.ꢀ
/phase
0.5/phase
• Single-phase / 3-wire
INPUT
BURDEN (VA)
VOLT. CURR.
AVAILABLE
RANGE
STD.RANGE
200V/1A
200V/5A
±200W
±100 – ±2ꢀ0W
±500 – ±1200W
0.1/phase
0.5/phase
0.2
/phase
±1000W
OUTPUT SPECIFICATIONS
■ OPERATION DIAGRAM (example)
OUT
5V
OUT
5V
3
1
3
1
0
500
1000W
-1000W
0
+1000W
18WT SPECIFICATIONS
ES-1866 Rev.7 Page 2/4
http://www.m-system.co.jp/
MODEL: 18WT
CONNECTION DIAGRAM
■ 3-PHASE/3-WIRE
■ SINGLE-PHASE/2-WIRE
SOURCE
SOURCE
1
2
3
1
2
VT
VT
FUSE
FUSE
U
V
u
v
P1
P2
U
u
P1
P2
P3
5
6
7
5
6
V
V
v
v
U
u
K
K
K
k
1S
1L
3S
3L
k
l
1S
1L
1
2
3
4
1
2
OUTPUT 1
OUTPUT 2
POWER
OUTPUT 1
OUTPUT 2
POWER
k
CT
CT
L
l
l
L
L
LOAD
LOAD
■ SINGLE-PHASE/3-WIRE
SOURCE
1
N 2
VT
FUSE
U
u
P1
P0
P2
5
6
7
V
V
v
v
U
u
K
K
k
1S
1L
2S
2L
1
2
3
4
OUTPUT 1
OUTPUT 2
POWER
k
CT
l
l
L
L
LOAD
EXTERNAL DIMENSIONS unit: mm (inch)
2–M3
SCREW
8–M3.5
7 (.28)
SCREW
7 (.28)
24 (.94)
32 (1.26)
78 (3.07)
18WT SPECIFICATIONS
ES-1866 Rev.7 Page 3/4
http://www.m-system.co.jp/
MODEL: 18WT
TERMINAL ASSIGNMENTS
7
8
5
6
1
2
3
4
Specifications are subject to change without notice.
18WT SPECIFICATIONS
ES-1866 Rev.7 Page 4/4
http://www.m-system.co.jp/
相关型号: