18SN-60 [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18SN-60
型号: 18SN-60
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总4页 (文件大小:103K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18SN  
Connection  
Rack-mounted DCS Signal Conditioners 18-RACK  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output: M3.5 screw terminals (torque 0.8 N·m) and  
connector  
INPUT LOOP POWERED ISOLATOR  
Functions & Features  
Screw terminal: Nickel-plated steel  
Isolation: Input to output  
• Loop-powered design eliminates output loop power supply  
• 500 V DC input-to-output isolation  
Zero adjustment (front)  
• 350 Ω output drive with 4 – 20 mA  
Voltage output: -5 to +5 %  
Current output: -0.5 to +0.5 %  
Span adjustment (front)  
Typical Applications  
• Isolation between control room and field instrumentation,  
between telemetering system and input device  
• Eliminates ground problems in existing systems thanks to  
easiness of application without requiring additional power  
wiring  
Voltage output: 95 to 105 %  
Current output: 98.5 to 101.5 %  
INPUT & OUTPUT  
■ Input 4 – 20 mA DC / Output 1 – 5 V DC  
Equivalent input impedance: Approx. 250 Ω with 20 mA  
input  
Operational range: 3 – 22 mA DC  
(Accuracy is assured within 4 – 22 mA)  
Load resistance: ≥ 50 kΩ  
■ Input 10 – 50 mA DC / Output 1 – 5 V DC  
Equivalent input impedance: Approx. 100 Ω with 50 mA  
input  
Operational range: 7 – 55 mA DC  
(Accuracy is assured within 8 – 55 mA)  
Load resistance: ≥ 50 kΩ  
MODEL: 18SN–[1][2]0  
ORDERING INFORMATION  
• Code number: 18SN-[1][2]0  
■ Input 4 – 20 mA DC / Output 4 – 20 mA DC  
Equivalent input impedance: 230 Ω plus load resistance with  
20 mA input  
Specify a code from below for each of [1] and [2].  
(e.g. 18SN-A60)  
Operational range: 3 – 22 mA DC  
(Accuracy is assured within 4 – 22 mA)  
Load resistance: 50 – 350 Ω (min. 50 Ω required for  
adequate operation)  
[1] INPUT  
Current  
A: 4 – 20 mA DC  
H: 10 – 50 mA DC  
■ Input 10 – 50 mA DC / Output 4 – 20 mA DC  
Equivalent input impedance: 90 Ω + [load resistance×0.16]  
with 50 mA input  
[2] OUTPUT 1  
Current  
Operational range: 7 – 55 mA DC  
A: 4 – 20 mA DC  
Voltage  
(Accuracy is assured within 8 – 55 mA)  
Load resistance: 50 – 600 Ω (min. 50 Ω required for  
adequate operation)  
6: 1 – 5 V DC  
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC  
5.0  
approx. 5.0  
OUTPUT 2  
0: None  
4.0  
approx.  
3.7  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
3.0  
4
12  
20  
INPUT CURRENT [mA]  
18SN SPECIFICATIONS  
ES-1819 Rev.8 Page 1/4  
http://www.m-system.co.jp/  
MODEL: 18SN  
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC  
INSTALLATION  
5.0  
approx. 5.0  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 150 g (0.33 lb)  
4.0  
approx.  
3.7  
3.0  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
10  
30  
50  
INPUT CURRENT [mA]  
Temp. coefficient  
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC  
Voltage output: ±0.015 %/°C (±0.008 %/°F)  
Current output: ±0.02 %/°C (±0.01 %/°F)  
Response time  
12.0  
approx. 11.6  
(load 350)  
10.0  
8.0  
approx. 9.6  
(load 250)  
Voltage output: ≤ 0.5 sec. (0 – 90 %)  
Current output: Approx. 15 msec. (0 – 90 %)  
Load effect (current output)  
6.0  
approx. 5.0  
approx. 4.6  
approx. 3.8  
approx. 5.6  
(load 50)  
3.0  
4 – 20 mA input: 0.015 %/Ω (50 – 150 Ω)  
0.003 %/Ω (150 – 350 Ω)  
4
12  
20  
INPUT CURRENT [mA]  
10 – 50 mA input: 0.015 %/Ω (50 – 100 Ω)  
0.003 %/Ω (100 – 600 Ω)  
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC  
10.0  
(The unit is calibrated with 250 Ω load at the factory.)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 500 V AC @ 1 minute  
(input to output)  
approx. 9.3  
(load 600)  
8.0  
approx. 6.5  
(load 250)  
approx. 4.9  
(load 50)  
6.0  
approx. 4.7  
approx. 4.1  
approx. 3.8  
3.0  
1500 V AC @ 1 minute  
10  
30  
50  
(input or output to ground)  
INPUT CURRENT [mA]  
18SN SPECIFICATIONS  
ES-1819 Rev.8 Page 2/4  
http://www.m-system.co.jp/  
MODEL: 18SN  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
18SN SPECIFICATIONS  
ES-1819 Rev.8 Page 3/4  
http://www.m-system.co.jp/  
MODEL: 18SN  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
VOLTAGE OUTPUT  
Z
S
Buffer  
Amplifier  
+
1
2
3
4
7
8
Chopper  
Inverter  
5
6
+
INPUT  
OUTPUT  
OUTPUT  
Rectifier  
CURRENT OUTPUT  
S
Isolation  
Inverter  
Load Effect  
Compensation  
+
1
5
6
+
OUTPUT  
Z
INPUT  
2
3
4
7
8
OUTPUT  
Specifications are subject to change without notice.  
18SN SPECIFICATIONS  
ES-1819 Rev.8 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

18SN-A0

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18SN-H0

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18SP50S1

Analog IC
ETC

18SP50S2

Analog IC
ETC

18T-0F

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-0M

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-12

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-12F

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-12M

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-15M

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-1F

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH

18T-1M

Fixed Attenuator, 0MHz Min, 18000MHz Max, ROHS COMPLIANT PACKAGE
APITECH