18JDL-A466-R [MSYSTEM]
Rack-mounted DCS Signal Conditioners 18-RACK;型号: | 18JDL-A466-R |
厂家: | M-SYSTEM |
描述: | Rack-mounted DCS Signal Conditioners 18-RACK DCS 分布式控制系统 |
文件: | 总3页 (文件大小:131K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 18JDL
Rack-mounted DCS Signal Conditioners 18-RACK
LINEARIZATION CODE
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
DEFAULT
Linear
–––
CURRENT LOOP SUPPLY
(linearizing; field-programmable)
K
0 – 1000°C
Functions & Features
Pt 100 0 – 100°C
• Powering a 4 – 20 mA DC current loop
• Microprocessor based
• Shortcircuit protection
INPUT
Current
• Applicable to smart transmitters
• Field-programmable linearization data
• Loop testing via hand-held programmer PU-2x
• Usable as Linearizer for 4 – 20 mA DC signals
• Second channel output available at the front terminals
and at the Standard Rack connector
A: 4 – 20 mA DC (Input resistance 250 Ω)
[1] LINEARIZATION
0: None
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
Typical Applications
• Various 2-wire transmitters
• Providing isolation and linearization for a 2-wire
temperature transmitter
• Linearizing weir flowmeter output to provide a linear-to-
volume signal
OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
POWER INPUT
DC Power
R: 24 V DC
MODEL: 18JDL–A[1]66–R
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
ORDERING INFORMATION
• Code number: 18JDL-A[1]66-R
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
Specify a code from below for [1].
(e.g. 18JDL-A366-R)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Default setting (table next) will be used if not otherwise
specified.
No linearization data will be programmed if you don't
specify type of linearization and required data.
• Linearization data
Code 1 segment data: Use Ordering Information Sheet (No.
ESU-1669) to specify linearization data.
Code 3 T/C, Code 4 RTD: Specify input sensor type and
temperature range.
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Output 1: Connector
Output 2: M3.5 screw terminals (torque 0.8 N·m)
18JDL SPECIFICATIONS
ES-1874 Rev.13 Page 1/3
http://www.m-system.co.jp/
MODEL: 18JDL
and connector
• Thermocouple linearizable range
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
USABLE RANGE
°C
T/C
°F
Isolation: Input to output 1 to output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Linearization: 16 points max. represented as percentage of
full-scale
(PR)
K (CA)
E (CRC)
0 to 1760
-270 to +1370
-270 to +1000
32 to 3200
-454 to +2498
-454 to +1832
J (IC)
T (CC)
B (RH)
-210 to +1200
-270 to +400
0 to 1820
-346 to +2192
-454 to +752
32 to 3308
Adjustments: Programming Unit (model: PU-2x);
linearization data, zero and span, simulating output, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
R
S
-50 to +1760
-50 to +1760
-58 to +3200
-58 to +3200
Note: For the temperatures that range below 0°C, the
transmitter may partially not satisfy the described accuracy.
Consult factory.
SUPPLY OUTPUT
Output voltage: 24 – 28 V DC with no load
Current rating: ≤ 22 mA DC
• Shortcircuit Protection
• RTD linearizable range
USABLE RANGE
RTD
°C
°F
Current limited: 30 mA max.
Protected time duration: No limit
JPt 100 (JIS ’89)
Pt 100 (JIS ’89)
Pt 100 (JIS ’97, IEC)
Pt 50Ω (JIS ’81)
Ni 508.4 Ω
-200 to +500
-200 to +650
-200 to +650
-200 to +500
-50 to +200
-328 to +932
-328 to +1202
-328 to +1202
-328 to +932
-58 to +392
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
Note:Pt100(JIS’89)isdeviatedfromPt100(JIS’97) only
within the described accuracy.
OUTPUT SPECIFICATIONS
The output goes below 0 % when the input is open.
INSTALLATION
Current consumption: Approx. 85 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 150 g (0.33 lb)
LINEARIZATION
• No linearization: The output is proportional to the input.
• Segment data: 16 points (15 segments) max. within the
range of -15.00 to +115.00 % input or output represented
as percentage of fullscale
• Square root extraction
PERFORMANCE in percentage of span
Accuracy: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain]
with segment gain > 1
Low-end cutout: 5 % (output); curve characteristics as in the
figure below
■ Square root extraction
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
Output signal: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to output 1 or output 2 or power)
500 V AC @ 1 minute
6%
5%
0
INPUT
(output 1 to output 2 to power)
1500 V AC @ 1 minute
(input or output or power to ground)
18JDL SPECIFICATIONS
ES-1874 Rev.13 Page 2/3
http://www.m-system.co.jp/
MODEL: 18JDL
EXTERNAL DIMENSIONS unit: mm (inch)
2–M3
SCREW
8–M3.5
7 (.28)
SCREW
7 (.28)
24 (.94)
32 (1.26)
78 (3.07)
TERMINAL ASSIGNMENTS
7
8
5
6
1
2
3
4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ When Used as Linearizer
Z
S
2-WIRE
TRANSMITTER
Isolation
No Connection
1
2
3
Current
Limiter
Output
Driver
+
+
–
1
2
3
4
7
8
5
6
+
OUTPUT 2
–
+
4 – 20mA DC
–
Digital
Computation
–
250Ω
+
MONITOR
V
(1 – 5V DC)
Output
Driver
250Ω
–
OUTPUT 1
OUTPUT 2
POWER
MODULAR JACK
PU-2x
SERIAL TRANSMISSION LINE
Specifications are subject to change without notice.
18JDL SPECIFICATIONS
ES-1874 Rev.13 Page 3/3
http://www.m-system.co.jp/
相关型号: