17TG-36-R [MSYSTEM]
Rack-mounted Power Transducers 17-RACK;型号: | 17TG-36-R |
厂家: | M-SYSTEM |
描述: | Rack-mounted Power Transducers 17-RACK |
文件: | 总3页 (文件大小:87K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 17TG
Rack-mounted Power Transducers 17-RACK
POWER INPUT
DC Power
R: 24 V DC
TACHOGENERATOR CONVERTER
Functions & Features
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Converting an AC voltage from a tachogenerator
(tachometer) into a standard process signal
• Wide input range
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Typical Applications
Connection:
• Measuring rotating or moving speed of multispeed
motors, belt conveyers, metering pumps
Input: M3.5 screw terminals (torque 0.8 N·m)
Output: Connector
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
INPUT SPECIFICATIONS
Input: 0 – 250 V AC
Minimum span: 50 mV
Input resistance: 200 kΩ minimum
Frequency: 15 Hz min., 1 kHz max. with 100 % input
MODEL: 17TG–[1]6-R
ORDERING INFORMATION
• Code number: 17TG-[1]6-R
Specify a code from below for [1].
(e.g. 17TG-16-R)
INSTALLATION
Current consumption: Approx. 35 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 40 to 85 % RH (non-condensing)
Mounting: Standard Rack 17BXE
• Special input range (For code U)
Weight: 150 g (0.33 lb)
[1] INPUT
Voltage
PERFORMANCE in percentage of span
Accuracy: ±0.3 %
1: 0 – 35 V AC (Input resistance 200 kΩ min.)
2: 0 – 50 mV AC (Input resistance 200 kΩ min.)
3: 0 – 60 mV AC (Input resistance 200 kΩ min.)
4: 0 – 100 mV AC (Input resistance 200 kΩ min.)
5: 0 – 1 V AC (Input resistance 200 kΩ min.)
6: 0 – 10 V AC (Input resistance 200 kΩ min.)
7: 0 – 100 V AC (Input resistance 200 kΩ min.)
8: 0 – 110 V AC (Input resistance 200 kΩ min.)
9: 0 – 150 V AC (Input resistance 200 kΩ min.)
A: 0 – 200 V AC (Input resistance 200 kΩ min.)
B: 0 – 250 V AC (Input resistance 200 kΩ min.)
U: Specify voltage (See INPUT SPECIFICATIONS)
(0 % input must be 0 V.)
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Ripple: 0.5 %p-p max.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to output or power)
500 V AC @ 1 minute (outut to power)
1500 V AC @ 1 minute (input or output or power to ground)
OUTPUT
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
http://www.m-system.co.jp/
17TG SPECIFICATIONS
ES-2939 Rev.0 Page 1/3
MODEL: 17TG
DIMENSIONS unit: mm (inch)
2–M3
SCREW
8–M3.5
7 (.28)
SCREW
7 (.28)
24 (.94)
32 (1.26)
78 (3.07)
TERMINAL ASSIGNMENTS
7
8
5
6
1
2
3
4
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
Isolation
AC
Amplifier
RMS
Operation
Output
Driver
1
2
3
4
5
6
7
8
INPUT
OUTPUT
POWER
http://www.m-system.co.jp/
17TG SPECIFICATIONS
ES-2939 Rev.0 Page 2/3
MODEL: 17TG
Specifications are subject to change without notice.
http://www.m-system.co.jp/
17TG SPECIFICATIONS
ES-2939 Rev.0 Page 3/3