10PP-330-R [MSYSTEM]
High-density Signal Conditioners 10-RACK;型号: | 10PP-330-R |
厂家: | M-SYSTEM |
描述: | High-density Signal Conditioners 10-RACK |
文件: | 总4页 (文件大小:111K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 10PP
High-density Signal Conditioners 10-RACK
[3] OUTPUT 2
0: None
2: Open collector (max. 10 kHz)
PULSE ISOLATOR
Functions & Features
• Galvanically isolating pulse rate signals
• Input frequency = output frequency
• Various outputs (relay, open collector and voltage pulses)
• Optional second channel output available at the front
terminals and at the Standard Rack connector
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS
blank: none
Typical Applications
• Isolating field pulse signals in order to reduce noises
• Changing e.g. dry contact signal to e.g. 5 V signals
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals at the front and via card-edge connector at the
rear; terminal cover provided
Connection: M3.5 screw terminals (torque 0.8 N·m) and
card-edge connector
MODEL: 10PP–[1][2][3]–R[4]
Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
ORDERING INFORMATION
• Code number: 10PP-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
(e.g. 10PP-332-R/Q)
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Frequency range: Input and output are the same.
Chattering protection: Filter provided for mechanical
contact input
• Frequency range (e.g. 0 – 1000 Hz)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT SPECIFICATIONS
Excitation: 12V DC ±2 V @ 30 mA; shortcircuit protection
■ Open Collector
Note: Output 1 and 2 frequency is equal.
[1] INPUT
Maximum frequency: 10 kHz
1: Mechanical contact (max. 30 Hz)
2: Open collector (max. 10 kHz)
3: Voltage pulse (max. 10 kHz)
Pulse width time requirement: 10 μsec. min. for ON and OFF
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 200 Ω / 3.5 V for ON, ≥ 100 kΩ / 7 V for OFF
■ Mechanical Contact
Maximum frequency: 30 Hz
[2] OUTPUT 1
Pulse width time requirement: 10 msec. min. for ON and
OFF
1: Low frequency open collector (max. 30 Hz)
2: High frequency open collector (max. 10 kHz)
3: 5 V pulse (max. 10 kHz)
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 200 Ω / 3.5 V for ON, ≥ 100 kΩ / 7 V for OFF
■ Voltage Pulse
4: 12 V pulse (max. 10 kHz)
5: 24 V pulse (max. 10 kHz)
Maximum frequency: 10 kHz
8: Photo MOSFET relay pulse (max. 30 Hz)
Pulse width time requirement: 10 μsec. min. for high and
low levels
10PP SPECIFICATIONS
ES-0861 Rev.9 Page 1/4
http://www.m-system.co.jp/
MODEL: 10PP
Waveforms: Square or sine
Hi/Lo level: 2 – 50 V for high level; ≤1 V for low level
Input impedance: 10 kΩ min.
OUTPUT SPECIFICATIONS
■ Low Frequency Open Collector (Output 1)
50 V DC @ 100 mA (resistive load)
Maximum frequency: 30 Hz
Timer: Limits ON time within 75 ±25 msec. for wider than
75 msec. pulses
Saturation voltage: 0.5 V DC
■ High Frequency Open Collector (Output 1)
50 V DC @ 100 mA (resistive load)
Maximum frequency: 10 kHz
Saturation voltage: 0.5 V DC
■ Open Collector (Output 2)
40 V DC @ 100 mA (resistive load)
Maximum frequency: 10 kHz
Timer: Limits ON time within 75 ±25 msec. for wider than
75 msec. pulses (Timer is provided when output 1 is low
frequency open collector or photo MOSFET relay pulse.)
Saturation voltage: 0.5 V DC
■ Voltage Pulse
Maximum frequency: 10 kHz
High level: Rating (5, 12 or 24 V) ±10 %
Low level: ≤ 0.5V
Load resistance:
≥ 250 Ω for 5 V
≥ 600 Ω for 12 V
≥ 1200 Ω for 24 V
■ Photo MOSFET Relay Pulse
Maximum frequency: 30 Hz
Timer: Limits ON time within 75 ±25 msec. for wider than
75 msec. pulses
Rating: 132 V AC @ 200 mA (cos ø = 1)
30 V DC @ 200 mA (resistive load)
ON resistance: ≤ 2 Ω
INSTALLATION
Current consumption: Approx. 80 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 10BXx
Weight: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output 1 to output 2 to power)
1500 V AC @ 1 minute (input or output or power to ground)
10PP SPECIFICATIONS
ES-0861 Rev.9 Page 2/4
http://www.m-system.co.jp/
MODEL: 10PP
OUTPUT LOGIC
Applicable for both Output 1 and 2.
VOLTAGE PULSE
OUTPUT
OPEN COLLECTOR or
PHOTO MOSFET RELAY PULSE OUTPUT
INPUT TYPE
Voltage Pulse
INPUT
H
H
OFF
L
L
ON
OFF
H
OFF
Mechanical Contact
Open Collector
ON
L
ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7–M3.5 SCREW
8 (.31)
2–4.3 (.17) dia.
MTG HOLE
TERMINAL COVER
1
5
2
6
3
7
8
3 (.12)
25 (.98)
51 (2.01)
130 (5.12)
10PP SPECIFICATIONS
ES-0861 Rev.9 Page 3/4
http://www.m-system.co.jp/
MODEL: 10PP
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Isolation
*
Waveform
Shaper
Output
Driver
+
–
1
2
3
7
8
+
–
Timer
INPUT
OUTPUT 1
OUTPUT 2
SENSOR EXCITATION
+
12 V Supply
Output
Driver
5
6
+
–
Isolation
OUTPUT 2**
POWER
* Timer is provided for low frequency open collector or photo MOSFET relay pulse output.
**
For 1 output channel type, OUTPUT 1 is also connected to the card-edge connector inside.
Note: The section enclosed by broken line is only for 2nd output channel.
Input Connection Examples
Output Connection Examples
■ Mechanical Contact or Open Collector
■ Open Collector
■ Photo MOSFET Relay Pulse
• AC Powered
Relay or
Counter Coil
+
–
–
+
+
–
+
1
2
3
+
–
+
–
7
8
7
Varistor or Spark
Quenching Circuit
LOAD
8
+12V
PWR
U
4kΩ
■ Voltage Pulse
• DC Powered
■ Voltage Pulse
Relay or
Counter Coil
7
8
+
–
+
–
7
8
Spark Quenching
Diode
+
–
–
+
+
–
+
1
2
3
LOAD
+12V
PWR
Specifications are subject to change without notice.
10PP SPECIFICATIONS
ES-0861 Rev.9 Page 4/4
http://www.m-system.co.jp/
相关型号: